Hamworthy Heating

Ensbury pressure jet boiler

  • Low temperature, high efficiency, floor standing steel boiler.
  • Available in 3 models with outputs (at 80/60°C) of 440, 510 and 580kW.
  • Hamworthy Web Icons JBs base set BLUE-11
  • Hamworthy Web Icons JBs base set BLUE-46
  • 6c30888e71fd-Product-icon-turndown-3
  • Hamworthy Web Icons JBs base set BLUE-20
6f00fae28c57-Ensbury-LT-boiler-web
3787a343ae14-Ensbury-heat-exchanger-diagram

Product information

  • Advanced return distribution within boiler allows operation with return temperatures as low as 15°C. (Minimum flow temperatures apply).

  • Operating efficiencies of up to 95% nett (86% gross) at part load.

  • Suitable for use on open vented or sealed low temperature hot water heating systems .

  • Robust three-pass heat exchanger design helps to achieve European Class 5 performance for NOx emissions.

  • Suitable for use with liquid biofuel as a renewable energy choice. Natural Gas, LPG (propane) or oil are other fuel options.

  • Extensive back up and support from our team of experienced engineers across the UK.

  • Long term commitment to spare parts.

Ideal uses/applications

Optional extras

  • Can be installed with the Arne flue gas economiser to increase operating efficiency by up to 18%.

  • Choose from a wide range of service contracts to help maintain optimum performance.

  • Book commissioning at the same time as placing your order for improved warranty terms.

  • Flues available

  • Energy

    Units

    ELT440

    ELT510

    ELT580

    Building regulations Part L seasonal efficiency

    % gross

    85.05

    85.11

    84.97

    Boiler output 80/60°C

    kW

    440

    510

    580

    Boiler input (gross) - maximum

    kW

    537

    622

    707

    Boiler input (nett) - maximum

    kW

    483

    560

    637

    Boiler output - minimum 80/60°C, NG

    kW

    100

    100

    165

    Boiler output - minimum 80/60°C, oil

    kW

    127

    127

    219

  • Water

    Units

    ELT440

    ELT510

    ELT580

    Water content

    litres

    540

    540

    540

    System design flow rate @ 20°C ∆T rise

    l/s

    5.26

    6.1

    6.94

    Water side pressure loss @ 20°C ∆T rise

    mbar

    20

    27

    35

    System design flow rate @ 10°C ∆T rise

    l/s

    10.53

    12.2

    13.88

    Water side pressure loss @ 10°C ∆T rise

    mbar

    81

    108

    140

    Water flow rate - minimum

    l/s

    No min flow rate

    No min flow rate

    No min flow rate

    Minimum water pressure

    barg

    0.5

    0.5

    0.5

    Maximum water pressure

    barg

    4

    4

    4

    Maximum water flow temperature

    °C

    90

    90

    90

    Minimum water flow temperature - NG

    °C

    60

    60

    60

    Minimum water flow temperature - oil

    °C

    50

    50

    50

    Minimum water return temperature

    °C

    15

    15

    15

  • Gas

    Units

    ELT440

    ELT510

    ELT580

    Gas flow rate, NG - maximum

    m3/hr

    51.2

    59.3

    67.4

    Inlet pressure for NG - nominal

    mbar

    20

    20

    20

    Inlet pressure for NG - maximum

    mbar

    50

    50

    50

    Input rate for oil (35sec)

    l/h

    50.8

    58.8

    66.9

  • Flue

    Units

    ELT440

    ELT510

    ELT580

    Approx. flue gas volume @ 15°C, 9% CO2, N.T.P

    m3/hr

    614.9

    707.1

    830.1

    Flue gas temperature @ 80/60°C

    °C

    182

    192

    197

    Combustion chamber resistance

    mbar

    2.53

    3.83

    5.86

  • Connection

    Units

    ELT440

    ELT510

    ELT580

    Water flow/return connections

    PN6 - DN80

    PN6 - DN80

    PN6 - DN80

    Gas inlet connection pipe thread size

    Rc1 ½"

    Rc2"

    Rc2"

    Safety valve connection

    Rc1 ½"

    Rc1 ½"

    Rc1 ½"

    Drain connection

    R1"

    R1"

    R1"

    Flue diameter (O/D) - nominal

    mm

    250

    250

    250

  • Connection

    Units

    ELT440

    ELT510

    ELT580

    Water flow/return connections

    PN6 - DN80

    PN6 - DN80

    PN6 - DN80

    Gas inlet connection pipe thread size

    Rc1 ½"

    Rc2"

    Rc2"

    Safety valve connection

    Rc1 ½"

    Rc1 ½"

    Rc1 ½"

    Drain connection

    R1"

    R1"

    R1"

    Flue diameter (O/D) - nominal

    mm

    250

    250

    250

  • Electrics

    Units

    ELT440

    ELT510

    ELT580

    Electrical supply for boiler

    230V 1Ph 50Hz

    230V 1Ph 50Hz

    230V 1Ph 50Hz

    Electrical supply for burner

    230V 1Ph 50Hz*

    230V 1Ph 50Hz*

    230V 1Ph 50Hz*

    Approx shipping weight (excluding burner)

    kg

    973

    976

    980

    *400V 3Ph 50Hz Dependant on burner selection

Relevant customer case studies

Pitfield Street Mixed Development

Pitfield Street Mixed Development

Read More
Drayton Manor Hotel, Staffordshire

Drayton Manor Hotel, Staffordshire

Read More
Christchurch Police Station

Christchurch Police Station

Read More

Partnerships

CIBSE Patron WhiteSoPHE Logo
BESA logo
ICOM

Hamworthy Heating 2025. All Rights Reserved

  • Youtube
  • Linkedin