Help with identifying fault and error codes
Use the tool below for instant help with common error codes on Hamworthy commercial boilers and water heaters.
Simply select the product and then type in the error code as displayed on the screen. For boilers with Siemens LMS controls do not include any letters. For all other products make sure you include the letters and numbers, e.g. E161
*Note - This tool only displays fault codes for the following products:
- Boilers with Siemens LMS controls - Upton, Purewell Variheat mk2, Wessex ModuMax mk3, Modumax mk4, Stratton mk2, and Varmax.
- Boilers with Siemens LMU controls - Purewell VariHeat, Fleet, Stratton mk1, and Wessex ModuMax mk2 & HE.
- Water Heaters - Dorchester DR-FC Evo, Dorchester DR-CC
For all other products please refer to the operating manual as these list all the fault codes and explanations per product.
If you still need help, please email technical@hamworthy-heating.com or call us on 01202 662505.
Error codes that are not listed and any work on commercial boilers and water heaters should only be investigated by a trained and competent person.
Should an error code appear which cannot be reset, or an error code repeatedly occurs, contact our technical team for assistance. Do not continue to operate or use the boiler/water heater as this may cause damage to the controls.
You may also want to refer to the product operating manual. If you don’t have a copy to hand you can download an electronic copy in the online technical library.
| Product | Error code | Cause & action | Description |
|---|---|---|---|
| Wessex ModuMax | 10 | Cause: Fault outside sensor. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax | 28 | Cause: Fault flue gas sensor. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax | 32 | Cause: Fault flow temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax | 50 | Cause: Fault DHW temperature sensor 1. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax | 52 | Cause: Fault DHW temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Wessex ModuMax | 62 | Cause: Wrong room unit 1 or wrong radio clock connected. Action: Connect compatible room control unit. | |
| Wessex ModuMax | 77 | Cause: Fault air pressure sensor. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax | 78 | Cause: Fault water pressure sensor. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax | 82 | Cause: Address collision on LPB. Action: Check addresses of connected modules. | |
| Wessex ModuMax | 91 | Cause: Data overflow in EEPROM. Action: Hardware fault, LMU may need replacing. | |
| Wessex ModuMax | 92 | Cause: Hardware fault in electronics. Action: Hardware fault, LMU may need replacing. | |
| Wessex ModuMax | 95 | Cause: Invalid time of day. Action: Set correct time. | |
| Wessex ModuMax | 100 | Cause: 2 clock time masters. Action: Check settings of LMU, only 1 master allowed. | |
| Wessex ModuMax | 105 | Cause: Maintenance message. Action: P629 to reset : change from 0 to 1. | |
| Wessex ModuMax | 110 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Wessex ModuMax | 111 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Wessex ModuMax | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Wessex ModuMax | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor | |
| Wessex ModuMax | 118 | Cause: Water pressure too low. Action: Check system pressure, check water pressure sensor | |
| Wessex ModuMax | 119 | Cause: Water pressure switch has cut out. Action: Check water pressure. | |
| Wessex ModuMax | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Wessex ModuMax | 129 | Cause: Fan speed maximum/minimum has been violated. Action: Check fan. | |
| Wessex ModuMax | 130 | Cause: Flue gas limit temperature exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Wessex ModuMax | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Wessex ModuMax | 133 | Cause: No flame on completion of safety time. Action: Check operation of gas valve. Check spark igniter. | |
| Wessex ModuMax | 134 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Wessex ModuMax | 140 | Cause: Inadmissible LPB segment number/device N°. Action: Check settings of LMU and boiler address settings. | |
| Wessex ModuMax | 148 | Cause: Incompatibility LPB... interface / basic unit. Action: Check settings of LMU | |
| Wessex ModuMax | 151 | Cause: Internal fault with LMU. Action: Check connections to clip in, replace module, check LMU. | |
| Wessex ModuMax | 152 | Cause: Fault in connection with LMU settings. Action: Check LMU settings. | |
| Wessex ModuMax | 153 | Cause: LMU has locked out. Action: Press reset button (code appears if reset button is pressed when there are no faults). | |
| Wessex ModuMax | 154 | Cause: Flow Problems. Action: Check water flow through the boiler & check the pumps. | |
| Wessex ModuMax | 160 | Cause: Fan speed threshold not reached. Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris. | |
| Wessex ModuMax | 161 | Cause: Maximum fan speed exceeded. Action: Check parameters. | |
| Wessex ModuMax | 162 | Cause: Fault air pressure switch (does not close). Action: Check air pressure switch and cable and connections. | |
| Wessex ModuMax | 164 | Cause: Fault heating circuit flow switch / pressure switch. Action: Check air pressure switch and cable and connections. | |
| Wessex ModuMax | 166 | Cause: Fault air pressure switch (does not open). Action: Check air pressure switch and cable and connections. | |
| Wessex ModuMax | 180 | Cause: Chimney sweep function active. Action: Check boiler operation setting. | |
| Wessex ModuMax | 181 | Cause: Controller stop function active. Action: Check boiler operation setting. | |
| Wessex ModuMax | 183 | Cause: LMU in parameter setting mode. Action: Unit in programme mode. | |
| Wessex ModuMax mk2 | 10 | Cause: Fault outside sensor. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax mk2 | 28 | Cause: Fault flue gas sensor. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax mk2 | 32 | Cause: Fault flow temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax mk2 | 50 | Cause: Fault DHW temperature sensor 1. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax mk2 | 52 | Cause: Fault DHW temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax mk2 | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Wessex ModuMax mk2 | 62 | Cause: Wrong room unit 1 or wrong radio clock connected. Action: Connect compatible room control unit. | |
| Wessex ModuMax mk2 | 77 | Cause: Fault air pressure sensor. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax mk2 | 78 | Cause: Fault water pressure sensor. Action: Check connection, check sensor, check cable. | |
| Wessex ModuMax mk2 | 82 | Cause: Address collision on LPB. Action: Check addresses of connected modules. | |
| Wessex ModuMax mk2 | 91 | Cause: Data overflow in EEPROM. Action: Hardware fault, LMU may need replacing. | |
| Wessex ModuMax mk2 | 92 | Cause: Hardware fault in electronics. Action: Hardware fault, LMU may need replacing. | |
| Wessex ModuMax mk2 | 95 | Cause: Invalid time of day. Action: Set correct time. | |
| Wessex ModuMax mk2 | 100 | Cause: 2 clock time masters. Action: Check settings of LMU, only 1 master allowed. | |
| Wessex ModuMax mk2 | 105 | Cause: Maintenance message. Action: P629 to reset : change from 0 to 1. | |
| Wessex ModuMax mk2 | 110 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Wessex ModuMax mk2 | 111 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Wessex ModuMax mk2 | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Wessex ModuMax mk2 | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor | |
| Wessex ModuMax mk2 | 118 | Cause: Water pressure too low. Action: Check system pressure, check water pressure sensor | |
| Wessex ModuMax mk2 | 119 | Cause: Water pressure switch has cut out. Action: Check water pressure. | |
| Wessex ModuMax mk2 | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Wessex ModuMax mk2 | 129 | Cause: Fan speed maximum/minimum has been violated. Action: Check fan. | |
| Wessex ModuMax mk2 | 130 | Cause: Flue gas limit temperature exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Wessex ModuMax mk2 | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Wessex ModuMax mk2 | 133 | Cause: No flame on completion of safety time. Action: Check operation of gas valve. Check spark igniter. | |
| Wessex ModuMax mk2 | 134 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Wessex ModuMax mk2 | 140 | Cause: Inadmissible LPB segment number/device N°. Action: Check settings of LMU and boiler address settings. | |
| Wessex ModuMax mk2 | 148 | Cause: Incompatibility LPB... interface / basic unit. Action: Check settings of LMU | |
| Wessex ModuMax mk2 | 151 | Cause: Internal fault with LMU. Action: Check connections to clip in, replace module, check LMU. | |
| Wessex ModuMax mk2 | 152 | Cause: Fault in connection with LMU settings. Action: Check LMU settings. | |
| Wessex ModuMax mk2 | 153 | Cause: LMU has locked out. Action: Press reset button (code appears if reset button is pressed when there are no faults). | |
| Wessex ModuMax mk2 | 154 | Cause: Flow Problems. Action: Check water flow through the boiler & check the pumps. | |
| Wessex ModuMax mk2 | 160 | Cause: Fan speed threshold not reached. Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris. | |
| Wessex ModuMax mk2 | 161 | Cause: Maximum fan speed exceeded. Action: Check parameters. | |
| Wessex ModuMax mk2 | 162 | Cause: Fault air pressure switch (does not close). Action: Check air pressure switch and cable and connections. | |
| Wessex ModuMax mk2 | 164 | Cause: Fault heating circuit flow switch / pressure switch. Action: Check air pressure switch and cable and connections. | |
| Wessex ModuMax mk2 | 166 | Cause: Fault air pressure switch (does not open). Action: Check air pressure switch and cable and connections. | |
| Wessex ModuMax mk2 | 180 | Cause: Chimney sweep function active. Action: Check boiler operation setting. | |
| Wessex ModuMax mk2 | 181 | Cause: Controller stop function active. Action: Check boiler operation setting. | |
| Wessex ModuMax mk2 | 183 | Cause: LMU in parameter setting mode. Action: Unit in programme mode. | |
| Wessex ModuMax mk3 | 10 | Cause: Outside temperature sensor error Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 20 | Cause: Boiler temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 25 | Cause: Boiler temperature solid fuel sensor error Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 26 | Cause: Common flow temprerature sensor error Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 28 | Cause: Flue gas temperature sensor fault. Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 30 | Cause: Flow temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 31 | Cause: Flow temperature 1 cooling sensor error Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 32 | Cause: Flow temperature 2 sensor error Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 38 | Cause: Flow temperature primary controller Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 40 | Cause: Return temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 46 | Cause: Cascade return tremperature sensor error Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 47 | Cause: Common return termperature sensor error Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 50 | Cause: DHW temperature sensor/thermostat 1 fault. Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 52 | Cause: DHW temperature sensor/thermostat 2 fault. Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 54 | Cause: Flow temperature DHW Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 57 | Cause: DHW Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 60 | Cause: Room temperature 1, sensor error Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Wessex ModuMax mk3 | 65 | Cause: Room temperature 2 Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 68 | Cause: Room temperature 3 Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 70 | Cause: Storage tank temperature 1 (top) Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 71 | Cause: Storage tank temperature 2 (bottom) Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 72 | Cause: Storage tank temrperature 3 (middle) Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 73 | Cause: Collector temperature 1 Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 74 | Cause: Collector temperature 2 sensor error. Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 78 | Cause: Water pressure Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 81 | Cause: LPB short-circuit or no bus power supply. Action: Check wiring, check polarity | |
| Wessex ModuMax mk3 | 82 | Cause: LPB address collision. Action: Check connection, check address | |
| Wessex ModuMax mk3 | 83 | Cause: BSB-Wire short-circuit or no communication. Action: Check wiring, check polarity | |
| Wessex ModuMax mk3 | 84 | Cause: BSB wire address collision. Action: Check wiring, check polarity | |
| Wessex ModuMax mk3 | 85 | Cause: BSB radio communication fault. Action: Connect compatible room control unit. Check wireless communication. | |
| Wessex ModuMax mk3 | 91 | Cause: Data overrun in EEPROM. Action: Contact Hamworthy Heating. | |
| Wessex ModuMax mk3 | 98 | Cause: Mixing valve clip in 1 fault. Action: Check wiring, check polarity | |
| Wessex ModuMax mk3 | 99 | Cause: Mixing valve clip in 2 fault. Action: Check wiring, check polarity | |
| Wessex ModuMax mk3 | 100 | Cause: Two clock time masters. Action: Check parameter setting. | |
| Wessex ModuMax mk3 | 102 | Cause: Clock time master without power reserve. Action: Check wiring, check polarity | |
| Wessex ModuMax mk3 | 105 | Cause: Maintenance message. Action: Reset in parameters. | |
| Wessex ModuMax mk3 | 109 | Cause: Supervision boiler temperature. Action: Allow the boiler to cool, investigate cause of overheating. | |
| Wessex ModuMax mk3 | 110 | Cause: SLT lockout. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Wessex ModuMax mk3 | 111 | Cause: Temperature limiter safety shutdown. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Wessex ModuMax mk3 | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Wessex ModuMax mk3 | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor. | |
| Wessex ModuMax mk3 | 118 | Cause: Water pressure too low 6. Action: Check system pressure, check water pressure sensor. | |
| Wessex ModuMax mk3 | 119 | Cause: Water pressure switch has cut out 6. Action: Check water pressure. | |
| Wessex ModuMax mk3 | 125 | Cause: Maximum boiler temperature exceeded. Action: Check water flow rate, check pumps, check controls. | |
| Wessex ModuMax mk3 | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Wessex ModuMax mk3 | 130 | Cause: Flue gas temperature limit exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Wessex ModuMax mk3 | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Wessex ModuMax mk3 | 133 | Cause: Safety time for establishment of flame exceeded. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Wessex ModuMax mk3 | 146 | Cause: Sensor/actuator configuration error. Action: Check parameter setting. | |
| Wessex ModuMax mk3 | 151 | Cause: BMU fault internal. Action: Check connections to clip in, replace module, check LMS. | |
| Wessex ModuMax mk3 | 152 | Cause: Parameterization error. Action: Check parameters. | |
| Wessex ModuMax mk3 | 153 | Cause: Unit manually locked. Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults). | |
| Wessex ModuMax mk3 | 160 | Cause: Fan speed threshold not reached. Action: Check fan connection, replace fan | |
| Wessex ModuMax mk3 | 162 | Cause: Air pressure switch does not close. Action: Check air pressure switch cable and connections | |
| Wessex ModuMax mk3 | 164 | Cause: Flow/pressure switch heating circuit error Action: Check flow pressure switch and cable and connections. | |
| Wessex ModuMax mk3 | 166 | Cause: Air pressure switch error does not open Action: Check air pressure switch and cable and connections. | |
| Wessex ModuMax mk3 | 170 | Cause: Water pressure primary. Action: Check flow pressure switch cable and connections. | |
| Wessex ModuMax mk3 | 176 | Cause: Water pressure 2 too high. Action: Check system pressure. | |
| Wessex ModuMax mk3 | 177 | Cause: Water pressure 2 too low. Action: Check system pressure. | |
| Wessex ModuMax mk3 | 178 | Cause: Limit thermostat HC1. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Wessex ModuMax mk3 | 179 | Cause: Limit thermostat HC2. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Wessex ModuMax mk3 | 183 | Cause: Unit in parameterization mode. Action: Escape back to main screen. | |
| Wessex ModuMax mk3 | 193 | Cause: Start prevention. Action: Check external controls. | |
| Wessex ModuMax mk3 | 217 | Cause: Sensor error. Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 320 | Cause: DHW charging temp sensor fault. Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 321 | Cause: DHW outlet sensor fault. Action: Check connection, check sensor, check cable | |
| Wessex ModuMax mk3 | 322 | Cause: Water pressure 3 too high. Action: Check system pressure. | |
| Wessex ModuMax mk3 | 323 | Cause: Water pressure 3 too low. Action: Check system pressure. | |
| Wessex ModuMax mk3 | 324 | Cause: Same sensor Input BX. Action: Check parameters. | |
| Wessex ModuMax mk3 | 325 | Cause: Same sensor Input BX/extension module. Action: Check parameters. | |
| Wessex ModuMax mk3 | 326 | Cause: Same sensor Input BX/mixing valve group. Action: Check parameters. | |
| Wessex ModuMax mk3 | 327 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Wessex ModuMax mk3 | 328 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Wessex ModuMax mk3 | 329 | Cause: Same funct ext module/mixing valve group. Action: Check parameters. | |
| Wessex ModuMax mk3 | 330 | Cause: Sensor input BX1 no function. Action: Sensor not Parameterised. | |
| Wessex ModuMax mk3 | 331 | Cause: Sensor input BX2 no function. Action: Sensor not Parameterised. | |
| Wessex ModuMax mk3 | 332 | Cause: Sensor input BX3 no function. Action: Sensor not Parameterised. | |
| Wessex ModuMax mk3 | 333 | Cause: Sensor input BX4 no function. Action: Sensor not Parameterised. | |
| Wessex ModuMax mk3 | 335 | Cause: Sensor input BX21 no function. Action: Sensor not Parameterised. | |
| Wessex ModuMax mk3 | 336 | Cause: Sensor input BX22 no function. Action: Sensor not Parameterised. | |
| Wessex ModuMax mk3 | 337 | Cause: Sensor input B1 no function. Action: Sensor not Parameterised. | |
| Wessex ModuMax mk3 | 338 | Cause: Sensor input B12 no function. Action: Sensor not Parameterised. | |
| Wessex ModuMax mk3 | 353 | Cause: Cascade flow sensor B10 missing. Action: Sensor not Parameterised. | |
| Wessex ModuMax mk3 | 372 | Cause: Limit thermostat HC3. Action: Allow the boiler to cool and reset thermostat | |
| Wessex ModuMax mk3 | 385 | Cause: Mains undervoltage. Action: Check incoming voltage. | |
| Wessex ModuMax mk3 | 386 | Cause: Fan speed tolerance. Action: Check fan connection | |
| Wessex ModuMax mk3 | 387 | Cause: Air pressure tolerance. Action: Check air pressure switch | |
| Wessex ModuMax mk3 | 388 | Cause: DHW sensor no function. Action: Sensor not parameterised . | |
| Wessex ModuMax mk3 | 429 | Cause: Dyn water pressure too high. Action: Check water pressure. | |
| Wessex ModuMax mk3 | 430 | Cause: Dyn water pressure too low. Action: Check water pressure. | |
| Wessex ModuMax mk3 | 432 | Cause: Function ground missing. Action: Check earth connection. | |
| Wessex ModuMax mk3 | 433 | Cause: Heat exchanger temperature. Action: Allow the boiler to cool and reset thermostat | |
| Modumax mk4 | 10 | Cause: Outside temperature sensor error Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 20 | Cause: Boiler temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 25 | Cause: Boiler temperature solid fuel sensor error Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 26 | Cause: Common flow temprerature sensor error Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 28 | Cause: Flue gas temperature sensor fault. Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 30 | Cause: Flow temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 31 | Cause: Flow temperature 1 cooling sensor error Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 32 | Cause: Flow temperature 2 sensor error Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 38 | Cause: Flow temperature primary controller Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 40 | Cause: Return temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 46 | Cause: Cascade return tremperature sensor error Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 47 | Cause: Common return termperature sensor error Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 50 | Cause: DHW temperature sensor/thermostat 1 fault. Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 52 | Cause: DHW temperature sensor/thermostat 2 fault. Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 54 | Cause: Flow temperature DHW Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 57 | Cause: DHW Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 60 | Cause: Room temperature 1, sensor error Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Modumax mk4 | 65 | Cause: Room temperature 2 Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 68 | Cause: Room temperature 3 Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 70 | Cause: Storage tank temperature 1 (top) Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 71 | Cause: Storage tank temperature 2 (bottom) Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 72 | Cause: Storage tank temrperature 3 (middle) Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 73 | Cause: Collector temperature 1 Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 74 | Cause: Collector temperature 2 sensor error. Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 78 | Cause: Water pressure Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 81 | Cause: LPB short-circuit or no bus power supply. Action: Check wiring, check polarity | |
| Modumax mk4 | 82 | Cause: LPB address collision. Action: Check connection, check address | |
| Modumax mk4 | 83 | Cause: BSB-Wire short-circuit or no communication. Action: Check wiring, check polarity | |
| Modumax mk4 | 84 | Cause: BSB wire address collision. Action: Check wiring, check polarity | |
| Modumax mk4 | 85 | Cause: BSB radio communication fault. Action: Connect compatible room control unit. Check wireless communication. | |
| Modumax mk4 | 91 | Cause: Data overrun in EEPROM. Action: Contact Hamworthy Heating. | |
| Modumax mk4 | 98 | Cause: Mixing valve clip in 1 fault. Action: Check wiring, check polarity | |
| Modumax mk4 | 99 | Cause: Mixing valve clip in 2 fault. Action: Check wiring, check polarity | |
| Modumax mk4 | 100 | Cause: Two clock time masters. Action: Check parameter setting. | |
| Modumax mk4 | 102 | Cause: Clock time master without power reserve. Action: Check wiring, check polarity | |
| Modumax mk4 | 105 | Cause: Maintenance message. Action: Reset in parameters. | |
| Modumax mk4 | 109 | Cause: Supervision boiler temperature. Action: Allow the boiler to cool, investigate cause of overheating. | |
| Modumax mk4 | 110 | Cause: SLT lockout. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Modumax mk4 | 111 | Cause: Temperature limiter safety shutdown. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Modumax mk4 | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Modumax mk4 | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor. | |
| Modumax mk4 | 118 | Cause: Water pressure too low 6. Action: Check system pressure, check water pressure sensor. | |
| Modumax mk4 | 119 | Cause: Water pressure switch has cut out 6. Action: Check water pressure. | |
| Modumax mk4 | 125 | Cause: Maximum boiler temperature exceeded. Action: Check water flow rate, check pumps, check controls. | |
| Modumax mk4 | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Modumax mk4 | 130 | Cause: Flue gas temperature limit exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Modumax mk4 | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Modumax mk4 | 133 | Cause: Safety time for establishment of flame exceeded. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Modumax mk4 | 146 | Cause: Sensor/actuator configuration error. Action: Check parameter setting. | |
| Modumax mk4 | 151 | Cause: BMU fault internal. Action: Check connections to clip in, replace module, check LMS. | |
| Modumax mk4 | 152 | Cause: Parameterization error. Action: Check parameters. | |
| Modumax mk4 | 153 | Cause: Unit manually locked. Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults). | |
| Modumax mk4 | 160 | Cause: Fan speed threshold not reached. Action: Check fan connection, replace fan | |
| Modumax mk4 | 162 | Cause: Air pressure switch does not close. Action: Check air pressure switch cable and connections | |
| Modumax mk4 | 164 | Cause: Flow/pressure switch heating circuit error Action: Check flow pressure switch and cable and connections. | |
| Modumax mk4 | 166 | Cause: Air pressure switch error does not open Action: Check air pressure switch and cable and connections. | |
| Modumax mk4 | 170 | Cause: Water pressure primary. Action: Check flow pressure switch cable and connections. | |
| Modumax mk4 | 176 | Cause: Water pressure 2 too high. Action: Check system pressure. | |
| Modumax mk4 | 177 | Cause: Water pressure 2 too low. Action: Check system pressure. | |
| Modumax mk4 | 178 | Cause: Limit thermostat HC1. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Modumax mk4 | 179 | Cause: Limit thermostat HC2. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Modumax mk4 | 183 | Cause: Unit in parameterization mode. Action: Escape back to main screen. | |
| Modumax mk4 | 193 | Cause: Start prevention. Action: Check external controls. | |
| Modumax mk4 | 217 | Cause: Sensor error. Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 320 | Cause: DHW charging temp sensor fault. Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 321 | Cause: DHW outlet sensor fault. Action: Check connection, check sensor, check cable | |
| Modumax mk4 | 322 | Cause: Water pressure 3 too high. Action: Check system pressure. | |
| Modumax mk4 | 323 | Cause: Water pressure 3 too low. Action: Check system pressure. | |
| Modumax mk4 | 324 | Cause: Same sensor Input BX. Action: Check parameters. | |
| Modumax mk4 | 325 | Cause: Same sensor Input BX/extension module. Action: Check parameters. | |
| Modumax mk4 | 326 | Cause: Same sensor Input BX/mixing valve group. Action: Check parameters. | |
| Modumax mk4 | 327 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Modumax mk4 | 328 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Modumax mk4 | 329 | Cause: Same funct ext module/mixing valve group. Action: Check parameters. | |
| Modumax mk4 | 330 | Cause: Sensor input BX1 no function. Action: Sensor not Parameterised. | |
| Modumax mk4 | 331 | Cause: Sensor input BX2 no function. Action: Sensor not Parameterised. | |
| Modumax mk4 | 332 | Cause: Sensor input BX3 no function. Action: Sensor not Parameterised. | |
| Modumax mk4 | 333 | Cause: Sensor input BX4 no function. Action: Sensor not Parameterised. | |
| Modumax mk4 | 335 | Cause: Sensor input BX21 no function. Action: Sensor not Parameterised. | |
| Modumax mk4 | 336 | Cause: Sensor input BX22 no function. Action: Sensor not Parameterised. | |
| Modumax mk4 | 337 | Cause: Sensor input B1 no function. Action: Sensor not Parameterised. | |
| Modumax mk4 | 338 | Cause: Sensor input B12 no function. Action: Sensor not Parameterised. | |
| Modumax mk4 | 353 | Cause: Cascade flow sensor B10 missing. Action: Sensor not Parameterised. | |
| Modumax mk4 | 372 | Cause: Limit thermostat HC3. Action: Allow the boiler to cool and reset thermostat | |
| Modumax mk4 | 385 | Cause: Mains undervoltage. Action: Check incoming voltage. | |
| Modumax mk4 | 386 | Cause: Fan speed tolerance. Action: Check fan connection | |
| Modumax mk4 | 387 | Cause: Air pressure tolerance. Action: Check air pressure switch | |
| Modumax mk4 | 388 | Cause: DHW sensor no function. Action: Sensor not parameterised . | |
| Modumax mk4 | 429 | Cause: Dyn water pressure too high. Action: Check water pressure. | |
| Modumax mk4 | 430 | Cause: Dyn water pressure too low. Action: Check water pressure. | |
| Modumax mk4 | 432 | Cause: Function ground missing. Action: Check earth connection. | |
| Modumax mk4 | 433 | Cause: Heat exchanger temperature. Action: Allow the boiler to cool and reset thermostat | |
| Purewell VariHeat c | 10 | Cause: Fault outside sensor. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat c | 28 | Cause: Fault flue gas sensor. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat c | 32 | Cause: Fault flow temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat c | 50 | Cause: Fault DHW temperature sensor 1. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat c | 52 | Cause: Fault DHW temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat c | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Purewell VariHeat c | 62 | Cause: Wrong room unit 1 or wrong radio clock connected. Action: Connect compatible room control unit. | |
| Purewell VariHeat c | 77 | Cause: Fault air pressure sensor. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat c | 78 | Cause: Fault water pressure sensor. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat c | 82 | Cause: Address collision on LPB. Action: Check addresses of connected modules. | |
| Purewell VariHeat c | 91 | Cause: Data overflow in EEPROM. Action: Hardware fault, LMU may need replacing. | |
| Purewell VariHeat c | 92 | Cause: Hardware fault in electronics. Action: Hardware fault, LMU may need replacing. | |
| Purewell VariHeat c | 95 | Cause: Invalid time of day. Action: Set correct time. | |
| Purewell VariHeat c | 100 | Cause: 2 clock time masters. Action: Check settings of LMU, only 1 master allowed. | |
| Purewell VariHeat c | 105 | Cause: Maintenance message. Action: P629 to reset : change from 0 to 1. | |
| Purewell VariHeat c | 110 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Purewell VariHeat c | 111 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Purewell VariHeat c | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Purewell VariHeat c | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor | |
| Purewell VariHeat c | 118 | Cause: Water pressure too low. Action: Check system pressure, check water pressure sensor | |
| Purewell VariHeat c | 119 | Cause: Water pressure switch has cut out. Action: Check water pressure. | |
| Purewell VariHeat c | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Purewell VariHeat c | 129 | Cause: Fan speed maximum/minimum has been violated. Action: Check fan. | |
| Purewell VariHeat c | 130 | Cause: Flue gas limit temperature exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Purewell VariHeat c | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Purewell VariHeat c | 133 | Cause: No flame on completion of safety time. Action: Check operation of gas valve. Check spark igniter. | |
| Purewell VariHeat c | 134 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Purewell VariHeat c | 140 | Cause: Inadmissible LPB segment number/device N°. Action: Check settings of LMU and boiler address settings. | |
| Purewell VariHeat c | 148 | Cause: Incompatibility LPB... interface / basic unit. Action: Check settings of LMU | |
| Purewell VariHeat c | 151 | Cause: Internal fault with LMU. Action: Check connections to clip in, replace module, check LMU. | |
| Purewell VariHeat c | 152 | Cause: Fault in connection with LMU settings. Action: Check LMU settings. | |
| Purewell VariHeat c | 153 | Cause: LMU has locked out. Action: Press reset button (code appears if reset button is pressed when there are no faults). | |
| Purewell VariHeat c | 154 | Cause: Flow Problems. Action: Check water flow through the boiler & check the pumps. | |
| Purewell VariHeat c | 160 | Cause: Fan speed threshold not reached. Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris. | |
| Purewell VariHeat c | 161 | Cause: Maximum fan speed exceeded. Action: Check parameters. | |
| Purewell VariHeat c | 162 | Cause: Fault air pressure switch (does not close). Action: Check air pressure switch and cable and connections. | |
| Purewell VariHeat c | 164 | Cause: Fault heating circuit flow switch / pressure switch. Action: Check air pressure switch and cable and connections. | |
| Purewell VariHeat c | 166 | Cause: Fault air pressure switch (does not open). Action: Check air pressure switch and cable and connections. | |
| Purewell VariHeat c | 180 | Cause: Chimney sweep function active. Action: Check boiler operation setting. | |
| Purewell VariHeat c | 181 | Cause: Controller stop function active. Action: Check boiler operation setting. | |
| Purewell VariHeat c | 183 | Cause: LMU in parameter setting mode. Action: Unit in programme mode. | |
| Purewell VariHeat he | 10 | Cause: Fault outside sensor. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat he | 28 | Cause: Fault flue gas sensor. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat he | 32 | Cause: Fault flow temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat he | 50 | Cause: Fault DHW temperature sensor 1. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat he | 52 | Cause: Fault DHW temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat he | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Purewell VariHeat he | 62 | Cause: Wrong room unit 1 or wrong radio clock connected. Action: Connect compatible room control unit. | |
| Purewell VariHeat he | 77 | Cause: Fault air pressure sensor. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat he | 78 | Cause: Fault water pressure sensor. Action: Check connection, check sensor, check cable. | |
| Purewell VariHeat he | 82 | Cause: Address collision on LPB. Action: Check addresses of connected modules. | |
| Purewell VariHeat he | 91 | Cause: Data overflow in EEPROM. Action: Hardware fault, LMU may need replacing. | |
| Purewell VariHeat he | 92 | Cause: Hardware fault in electronics. Action: Hardware fault, LMU may need replacing. | |
| Purewell VariHeat he | 95 | Cause: Invalid time of day. Action: Set correct time. | |
| Purewell VariHeat he | 100 | Cause: 2 clock time masters. Action: Check settings of LMU, only 1 master allowed. | |
| Purewell VariHeat he | 105 | Cause: Maintenance message. Action: P629 to reset : change from 0 to 1. | |
| Purewell VariHeat he | 110 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Purewell VariHeat he | 111 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Purewell VariHeat he | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Purewell VariHeat he | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor | |
| Purewell VariHeat he | 118 | Cause: Water pressure too low. Action: Check system pressure, check water pressure sensor | |
| Purewell VariHeat he | 119 | Cause: Water pressure switch has cut out. Action: Check water pressure. | |
| Purewell VariHeat he | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Purewell VariHeat he | 129 | Cause: Fan speed maximum/minimum has been violated. Action: Check fan. | |
| Purewell VariHeat he | 130 | Cause: Flue gas limit temperature exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Purewell VariHeat he | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Purewell VariHeat he | 133 | Cause: No flame on completion of safety time. Action: Check operation of gas valve. Check spark igniter. | |
| Purewell VariHeat he | 134 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Purewell VariHeat he | 140 | Cause: Inadmissible LPB segment number/device N°. Action: Check settings of LMU and boiler address settings. | |
| Purewell VariHeat he | 148 | Cause: Incompatibility LPB... interface / basic unit. Action: Check settings of LMU | |
| Purewell VariHeat he | 151 | Cause: Internal fault with LMU. Action: Check connections to clip in, replace module, check LMU. | |
| Purewell VariHeat he | 152 | Cause: Fault in connection with LMU settings. Action: Check LMU settings. | |
| Purewell VariHeat he | 153 | Cause: LMU has locked out. Action: Press reset button (code appears if reset button is pressed when there are no faults). | |
| Purewell VariHeat he | 154 | Cause: Flow Problems. Action: Check water flow through the boiler & check the pumps. | |
| Purewell VariHeat he | 160 | Cause: Fan speed threshold not reached. Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris. | |
| Purewell VariHeat he | 161 | Cause: Maximum fan speed exceeded. Action: Check parameters. | |
| Purewell VariHeat he | 162 | Cause: Fault air pressure switch (does not close). Action: Check air pressure switch and cable and connections. | |
| Purewell VariHeat he | 164 | Cause: Fault heating circuit flow switch / pressure switch. Action: Check air pressure switch and cable and connections. | |
| Purewell VariHeat he | 166 | Cause: Fault air pressure switch (does not open). Action: Check air pressure switch and cable and connections. | |
| Purewell VariHeat he | 180 | Cause: Chimney sweep function active. Action: Check boiler operation setting. | |
| Purewell VariHeat he | 181 | Cause: Controller stop function active. Action: Check boiler operation setting. | |
| Purewell VariHeat he | 183 | Cause: LMU in parameter setting mode. Action: Unit in programme mode. | |
| Purewell VariHeat mk2 | 10 | Cause: Outside temperature sensor error Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 20 | Cause: Boiler temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 25 | Cause: Boiler temperature solid fuel sensor error Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 26 | Cause: Common flow temprerature sensor error Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 28 | Cause: Flue gas temperature sensor fault. Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 30 | Cause: Flow temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 31 | Cause: Flow temperature 1 cooling sensor error Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 32 | Cause: Flow temperature 2 sensor error Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 38 | Cause: Flow temperature primary controller Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 40 | Cause: Return temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 46 | Cause: Cascade return tremperature sensor error Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 47 | Cause: Common return termperature sensor error Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 50 | Cause: DHW temperature sensor/thermostat 1 fault. Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 52 | Cause: DHW temperature sensor/thermostat 2 fault. Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 54 | Cause: Flow temperature DHW Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 57 | Cause: DHW Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 60 | Cause: Room temperature 1, sensor error Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Purewell VariHeat mk2 | 65 | Cause: Room temperature 2 Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 68 | Cause: Room temperature 3 Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 70 | Cause: Storage tank temperature 1 (top) Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 71 | Cause: Storage tank temperature 2 (bottom) Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 72 | Cause: Storage tank temrperature 3 (middle) Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 73 | Cause: Collector temperature 1 Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 74 | Cause: Collector temperature 2 sensor error. Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 78 | Cause: Water pressure Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 81 | Cause: LPB short-circuit or no bus power supply. Action: Check wiring, check polarity | |
| Purewell VariHeat mk2 | 82 | Cause: LPB address collision. Action: Check connection, check address | |
| Purewell VariHeat mk2 | 83 | Cause: BSB-Wire short-circuit or no communication. Action: Check wiring, check polarity | |
| Purewell VariHeat mk2 | 84 | Cause: BSB wire address collision. Action: Check wiring, check polarity | |
| Purewell VariHeat mk2 | 85 | Cause: BSB radio communication fault. Action: Connect compatible room control unit. Check wireless communication. | |
| Purewell VariHeat mk2 | 91 | Cause: Data overrun in EEPROM. Action: Contact Hamworthy Heating. | |
| Purewell VariHeat mk2 | 98 | Cause: Mixing valve clip in 1 fault. Action: Check wiring, check polarity | |
| Purewell VariHeat mk2 | 99 | Cause: Mixing valve clip in 2 fault. Action: Check wiring, check polarity | |
| Purewell VariHeat mk2 | 100 | Cause: Two clock time masters. Action: Check parameter setting. | |
| Purewell VariHeat mk2 | 102 | Cause: Clock time master without power reserve. Action: Check wiring, check polarity | |
| Purewell VariHeat mk2 | 105 | Cause: Maintenance message. Action: Reset in parameters. | |
| Purewell VariHeat mk2 | 109 | Cause: Supervision boiler temperature. Action: Allow the boiler to cool, investigate cause of overheating. | |
| Purewell VariHeat mk2 | 110 | Cause: SLT lockout. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Purewell VariHeat mk2 | 111 | Cause: Temperature limiter safety shutdown. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Purewell VariHeat mk2 | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Purewell VariHeat mk2 | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor. | |
| Purewell VariHeat mk2 | 118 | Cause: Water pressure too low 6. Action: Check system pressure, check water pressure sensor. | |
| Purewell VariHeat mk2 | 119 | Cause: Water pressure switch has cut out 6. Action: Check water pressure. | |
| Purewell VariHeat mk2 | 125 | Cause: Maximum boiler temperature exceeded. Action: Check water flow rate, check pumps, check controls. | |
| Purewell VariHeat mk2 | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Purewell VariHeat mk2 | 130 | Cause: Flue gas temperature limit exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Purewell VariHeat mk2 | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Purewell VariHeat mk2 | 133 | Cause: Safety time for establishment of flame exceeded. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Purewell VariHeat mk2 | 146 | Cause: Sensor/actuator configuration error. Action: Check parameter setting. | |
| Purewell VariHeat mk2 | 151 | Cause: BMU fault internal. Action: Check connections to clip in, replace module, check LMS. | |
| Purewell VariHeat mk2 | 152 | Cause: Parameterization error. Action: Check parameters. | |
| Purewell VariHeat mk2 | 153 | Cause: Unit manually locked. Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults). | |
| Purewell VariHeat mk2 | 160 | Cause: Fan speed threshold not reached. Action: Check fan connection, replace fan | |
| Purewell VariHeat mk2 | 162 | Cause: Air pressure switch does not close. Action: Check air pressure switch cable and connections | |
| Purewell VariHeat mk2 | 164 | Cause: Flow/pressure switch heating circuit error Action: Check flow pressure switch and cable and connections. | |
| Purewell VariHeat mk2 | 166 | Cause: Air pressure switch error does not open Action: Check air pressure switch and cable and connections. | |
| Purewell VariHeat mk2 | 170 | Cause: Water pressure primary. Action: Check flow pressure switch cable and connections. | |
| Purewell VariHeat mk2 | 176 | Cause: Water pressure 2 too high. Action: Check system pressure. | |
| Purewell VariHeat mk2 | 177 | Cause: Water pressure 2 too low. Action: Check system pressure. | |
| Purewell VariHeat mk2 | 178 | Cause: Limit thermostat HC1. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Purewell VariHeat mk2 | 179 | Cause: Limit thermostat HC2. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Purewell VariHeat mk2 | 183 | Cause: Unit in parameterization mode. Action: Escape back to main screen. | |
| Purewell VariHeat mk2 | 193 | Cause: Start prevention. Action: Check external controls. | |
| Purewell VariHeat mk2 | 217 | Cause: Sensor error. Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 320 | Cause: DHW charging temp sensor fault. Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 321 | Cause: DHW outlet sensor fault. Action: Check connection, check sensor, check cable | |
| Purewell VariHeat mk2 | 322 | Cause: Water pressure 3 too high. Action: Check system pressure. | |
| Purewell VariHeat mk2 | 323 | Cause: Water pressure 3 too low. Action: Check system pressure. | |
| Purewell VariHeat mk2 | 324 | Cause: Same sensor Input BX. Action: Check parameters. | |
| Purewell VariHeat mk2 | 325 | Cause: Same sensor Input BX/extension module. Action: Check parameters. | |
| Purewell VariHeat mk2 | 326 | Cause: Same sensor Input BX/mixing valve group. Action: Check parameters. | |
| Purewell VariHeat mk2 | 327 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Purewell VariHeat mk2 | 328 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Purewell VariHeat mk2 | 329 | Cause: Same funct ext module/mixing valve group. Action: Check parameters. | |
| Purewell VariHeat mk2 | 330 | Cause: Sensor input BX1 no function. Action: Sensor not Parameterised. | |
| Purewell VariHeat mk2 | 331 | Cause: Sensor input BX2 no function. Action: Sensor not Parameterised. | |
| Purewell VariHeat mk2 | 332 | Cause: Sensor input BX3 no function. Action: Sensor not Parameterised. | |
| Purewell VariHeat mk2 | 333 | Cause: Sensor input BX4 no function. Action: Sensor not Parameterised. | |
| Purewell VariHeat mk2 | 335 | Cause: Sensor input BX21 no function. Action: Sensor not Parameterised. | |
| Purewell VariHeat mk2 | 336 | Cause: Sensor input BX22 no function. Action: Sensor not Parameterised. | |
| Purewell VariHeat mk2 | 337 | Cause: Sensor input B1 no function. Action: Sensor not Parameterised. | |
| Purewell VariHeat mk2 | 338 | Cause: Sensor input B12 no function. Action: Sensor not Parameterised. | |
| Purewell VariHeat mk2 | 353 | Cause: Cascade flow sensor B10 missing. Action: Sensor not Parameterised. | |
| Purewell VariHeat mk2 | 372 | Cause: Limit thermostat HC3. Action: Allow the boiler to cool and reset thermostat | |
| Purewell VariHeat mk2 | 385 | Cause: Mains undervoltage. Action: Check incoming voltage. | |
| Purewell VariHeat mk2 | 386 | Cause: Fan speed tolerance. Action: Check fan connection | |
| Purewell VariHeat mk2 | 387 | Cause: Air pressure tolerance. Action: Check air pressure switch | |
| Purewell VariHeat mk2 | 388 | Cause: DHW sensor no function. Action: Sensor not parameterised . | |
| Purewell VariHeat mk2 | 429 | Cause: Dyn water pressure too high. Action: Check water pressure. | |
| Purewell VariHeat mk2 | 430 | Cause: Dyn water pressure too low. Action: Check water pressure. | |
| Purewell VariHeat mk2 | 432 | Cause: Function ground missing. Action: Check earth connection. | |
| Purewell VariHeat mk2 | 433 | Cause: Heat exchanger temperature. Action: Allow the boiler to cool and reset thermostat | |
| Stratton | 10 | Cause: Fault outside sensor. Action: Check connection, check sensor, check cable. | |
| Stratton | 28 | Cause: Fault flue gas sensor. Action: Check connection, check sensor, check cable. | |
| Stratton | 32 | Cause: Fault flow temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Stratton | 50 | Cause: Fault DHW temperature sensor 1. Action: Check connection, check sensor, check cable. | |
| Stratton | 52 | Cause: Fault DHW temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Stratton | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Stratton | 62 | Cause: Wrong room unit 1 or wrong radio clock connected. Action: Connect compatible room control unit. | |
| Stratton | 77 | Cause: Fault air pressure sensor. Action: Check connection, check sensor, check cable. | |
| Stratton | 78 | Cause: Fault water pressure sensor. Action: Check connection, check sensor, check cable. | |
| Stratton | 82 | Cause: Address collision on LPB. Action: Check addresses of connected modules. | |
| Stratton | 91 | Cause: Data overflow in EEPROM. Action: Hardware fault, LMU may need replacing. | |
| Stratton | 92 | Cause: Hardware fault in electronics. Action: Hardware fault, LMU may need replacing. | |
| Stratton | 95 | Cause: Invalid time of day. Action: Set correct time. | |
| Stratton | 100 | Cause: 2 clock time masters. Action: Check settings of LMU, only 1 master allowed. | |
| Stratton | 105 | Cause: Maintenance message. Action: P629 to reset : change from 0 to 1. | |
| Stratton | 110 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Stratton | 111 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Stratton | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Stratton | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor | |
| Stratton | 118 | Cause: Water pressure too low. Action: Check system pressure, check water pressure sensor | |
| Stratton | 119 | Cause: Water pressure switch has cut out. Action: Check water pressure. | |
| Stratton | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Stratton | 129 | Cause: Fan speed maximum/minimum has been violated. Action: Check fan. | |
| Stratton | 130 | Cause: Flue gas limit temperature exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Stratton | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Stratton | 133 | Cause: No flame on completion of safety time. Action: Check operation of gas valve. Check spark igniter. | |
| Stratton | 134 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Stratton | 140 | Cause: Inadmissible LPB segment number/device N°. Action: Check settings of LMU and boiler address settings. | |
| Stratton | 148 | Cause: Incompatibility LPB... interface / basic unit. Action: Check settings of LMU | |
| Stratton | 151 | Cause: Internal fault with LMU. Action: Check connections to clip in, replace module, check LMU. | |
| Stratton | 152 | Cause: Fault in connection with LMU settings. Action: Check LMU settings. | |
| Stratton | 153 | Cause: LMU has locked out. Action: Press reset button (code appears if reset button is pressed when there are no faults). | |
| Stratton | 154 | Cause: Flow Problems. Action: Check water flow through the boiler & check the pumps. | |
| Stratton | 160 | Cause: Fan speed threshold not reached. Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris. | |
| Stratton | 161 | Cause: Maximum fan speed exceeded. Action: Check parameters. | |
| Stratton | 162 | Cause: Fault air pressure switch (does not close). Action: Check air pressure switch and cable and connections. | |
| Stratton | 164 | Cause: Fault heating circuit flow switch / pressure switch. Action: Check air pressure switch and cable and connections. | |
| Stratton | 166 | Cause: Fault air pressure switch (does not open). Action: Check air pressure switch and cable and connections. | |
| Stratton | 180 | Cause: Chimney sweep function active. Action: Check boiler operation setting. | |
| Stratton | 181 | Cause: Controller stop function active. Action: Check boiler operation setting. | |
| Stratton | 183 | Cause: LMU in parameter setting mode. Action: Unit in programme mode. | |
| Stratton mk2 | 10 | Cause: Outside temperature sensor error Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 20 | Cause: Boiler temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 25 | Cause: Boiler temperature solid fuel sensor error Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 26 | Cause: Common flow temprerature sensor error Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 28 | Cause: Flue gas temperature sensor fault. Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 30 | Cause: Flow temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 31 | Cause: Flow temperature 1 cooling sensor error Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 32 | Cause: Flow temperature 2 sensor error Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 38 | Cause: Flow temperature primary controller Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 40 | Cause: Return temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 46 | Cause: Cascade return tremperature sensor error Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 47 | Cause: Common return termperature sensor error Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 50 | Cause: DHW temperature sensor/thermostat 1 fault. Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 52 | Cause: DHW temperature sensor/thermostat 2 fault. Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 54 | Cause: Flow temperature DHW Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 57 | Cause: DHW Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 60 | Cause: Room temperature 1, sensor error Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Stratton mk2 | 65 | Cause: Room temperature 2 Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 68 | Cause: Room temperature 3 Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 70 | Cause: Storage tank temperature 1 (top) Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 71 | Cause: Storage tank temperature 2 (bottom) Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 72 | Cause: Storage tank temrperature 3 (middle) Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 73 | Cause: Collector temperature 1 Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 74 | Cause: Collector temperature 2 sensor error. Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 78 | Cause: Water pressure Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 81 | Cause: LPB short-circuit or no bus power supply. Action: Check wiring, check polarity | |
| Stratton mk2 | 82 | Cause: LPB address collision. Action: Check connection, check address | |
| Stratton mk2 | 83 | Cause: BSB-Wire short-circuit or no communication. Action: Check wiring, check polarity | |
| Stratton mk2 | 84 | Cause: BSB wire address collision. Action: Check wiring, check polarity | |
| Stratton mk2 | 85 | Cause: BSB radio communication fault. Action: Connect compatible room control unit. Check wireless communication. | |
| Stratton mk2 | 91 | Cause: Data overrun in EEPROM. Action: Contact Hamworthy Heating. | |
| Stratton mk2 | 98 | Cause: Mixing valve clip in 1 fault. Action: Check wiring, check polarity | |
| Stratton mk2 | 99 | Cause: Mixing valve clip in 2 fault. Action: Check wiring, check polarity | |
| Stratton mk2 | 100 | Cause: Two clock time masters. Action: Check parameter setting. | |
| Stratton mk2 | 102 | Cause: Clock time master without power reserve. Action: Check wiring, check polarity | |
| Stratton mk2 | 105 | Cause: Maintenance message. Action: Reset in parameters. | |
| Stratton mk2 | 109 | Cause: Supervision boiler temperature. Action: Allow the boiler to cool, investigate cause of overheating. | |
| Stratton mk2 | 110 | Cause: SLT lockout. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Stratton mk2 | 111 | Cause: Temperature limiter safety shutdown. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Stratton mk2 | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Stratton mk2 | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor. | |
| Stratton mk2 | 118 | Cause: Water pressure too low 6. Action: Check system pressure, check water pressure sensor. | |
| Stratton mk2 | 119 | Cause: Water pressure switch has cut out 6. Action: Check water pressure. | |
| Stratton mk2 | 125 | Cause: Maximum boiler temperature exceeded. Action: Check water flow rate, check pumps, check controls. | |
| Stratton mk2 | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Stratton mk2 | 130 | Cause: Flue gas temperature limit exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Stratton mk2 | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Stratton mk2 | 133 | Cause: Safety time for establishment of flame exceeded. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Stratton mk2 | 146 | Cause: Sensor/actuator configuration error. Action: Check parameter setting. | |
| Stratton mk2 | 151 | Cause: BMU fault internal. Action: Check connections to clip in, replace module, check LMS. | |
| Stratton mk2 | 152 | Cause: Parameterization error. Action: Check parameters. | |
| Stratton mk2 | 153 | Cause: Unit manually locked. Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults). | |
| Stratton mk2 | 160 | Cause: Fan speed threshold not reached. Action: Check fan connection, replace fan | |
| Stratton mk2 | 162 | Cause: Air pressure switch does not close. Action: Check air pressure switch cable and connections | |
| Stratton mk2 | 164 | Cause: Flow/pressure switch heating circuit error Action: Check flow pressure switch and cable and connections. | |
| Stratton mk2 | 166 | Cause: Air pressure switch error does not open Action: Check air pressure switch and cable and connections. | |
| Stratton mk2 | 170 | Cause: Water pressure primary. Action: Check flow pressure switch cable and connections. | |
| Stratton mk2 | 176 | Cause: Water pressure 2 too high. Action: Check system pressure. | |
| Stratton mk2 | 177 | Cause: Water pressure 2 too low. Action: Check system pressure. | |
| Stratton mk2 | 178 | Cause: Limit thermostat HC1. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Stratton mk2 | 179 | Cause: Limit thermostat HC2. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Stratton mk2 | 183 | Cause: Unit in parameterization mode. Action: Escape back to main screen. | |
| Stratton mk2 | 193 | Cause: Start prevention. Action: Check external controls. | |
| Stratton mk2 | 217 | Cause: Sensor error. Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 320 | Cause: DHW charging temp sensor fault. Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 321 | Cause: DHW outlet sensor fault. Action: Check connection, check sensor, check cable | |
| Stratton mk2 | 322 | Cause: Water pressure 3 too high. Action: Check system pressure. | |
| Stratton mk2 | 323 | Cause: Water pressure 3 too low. Action: Check system pressure. | |
| Stratton mk2 | 324 | Cause: Same sensor Input BX. Action: Check parameters. | |
| Stratton mk2 | 325 | Cause: Same sensor Input BX/extension module. Action: Check parameters. | |
| Stratton mk2 | 326 | Cause: Same sensor Input BX/mixing valve group. Action: Check parameters. | |
| Stratton mk2 | 327 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Stratton mk2 | 328 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Stratton mk2 | 329 | Cause: Same funct ext module/mixing valve group. Action: Check parameters. | |
| Stratton mk2 | 330 | Cause: Sensor input BX1 no function. Action: Sensor not Parameterised. | |
| Stratton mk2 | 331 | Cause: Sensor input BX2 no function. Action: Sensor not Parameterised. | |
| Stratton mk2 | 332 | Cause: Sensor input BX3 no function. Action: Sensor not Parameterised. | |
| Stratton mk2 | 333 | Cause: Sensor input BX4 no function. Action: Sensor not Parameterised. | |
| Stratton mk2 | 335 | Cause: Sensor input BX21 no function. Action: Sensor not Parameterised. | |
| Stratton mk2 | 336 | Cause: Sensor input BX22 no function. Action: Sensor not Parameterised. | |
| Stratton mk2 | 337 | Cause: Sensor input B1 no function. Action: Sensor not Parameterised. | |
| Stratton mk2 | 338 | Cause: Sensor input B12 no function. Action: Sensor not Parameterised. | |
| Stratton mk2 | 353 | Cause: Cascade flow sensor B10 missing. Action: Sensor not Parameterised. | |
| Stratton mk2 | 372 | Cause: Limit thermostat HC3. Action: Allow the boiler to cool and reset thermostat | |
| Stratton mk2 | 385 | Cause: Mains undervoltage. Action: Check incoming voltage. | |
| Stratton mk2 | 386 | Cause: Fan speed tolerance. Action: Check fan connection | |
| Stratton mk2 | 387 | Cause: Air pressure tolerance. Action: Check air pressure switch | |
| Stratton mk2 | 388 | Cause: DHW sensor no function. Action: Sensor not parameterised . | |
| Stratton mk2 | 429 | Cause: Dyn water pressure too high. Action: Check water pressure. | |
| Stratton mk2 | 430 | Cause: Dyn water pressure too low. Action: Check water pressure. | |
| Stratton mk2 | 432 | Cause: Function ground missing. Action: Check earth connection. | |
| Stratton mk2 | 433 | Cause: Heat exchanger temperature. Action: Allow the boiler to cool and reset thermostat | |
| Upton | 10 | Cause: Outside temperature sensor error Action: Check connection, check sensor, check cable | |
| Upton | 20 | Cause: Boiler temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Upton | 25 | Cause: Boiler temperature solid fuel sensor error Action: Check connection, check sensor, check cable | |
| Upton | 26 | Cause: Common flow temprerature sensor error Action: Check connection, check sensor, check cable | |
| Upton | 28 | Cause: Flue gas temperature sensor fault. Action: Check connection, check sensor, check cable | |
| Upton | 30 | Cause: Flow temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Upton | 31 | Cause: Flow temperature 1 cooling sensor error Action: Check connection, check sensor, check cable | |
| Upton | 32 | Cause: Flow temperature 2 sensor error Action: Check connection, check sensor, check cable | |
| Upton | 38 | Cause: Flow temperature primary controller Action: Check connection, check sensor, check cable | |
| Upton | 40 | Cause: Return temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Upton | 46 | Cause: Cascade return tremperature sensor error Action: Check connection, check sensor, check cable | |
| Upton | 47 | Cause: Common return termperature sensor error Action: Check connection, check sensor, check cable | |
| Upton | 50 | Cause: DHW temperature sensor/thermostat 1 fault. Action: Check connection, check sensor, check cable | |
| Upton | 52 | Cause: DHW temperature sensor/thermostat 2 fault. Action: Check connection, check sensor, check cable | |
| Upton | 54 | Cause: Flow temperature DHW Action: Check connection, check sensor, check cable | |
| Upton | 57 | Cause: DHW Action: Check connection, check sensor, check cable | |
| Upton | 60 | Cause: Room temperature 1, sensor error Action: Check connection, check sensor, check cable | |
| Upton | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Upton | 65 | Cause: Room temperature 2 Action: Check connection, check sensor, check cable | |
| Upton | 68 | Cause: Room temperature 3 Action: Check connection, check sensor, check cable | |
| Upton | 70 | Cause: Storage tank temperature 1 (top) Action: Check connection, check sensor, check cable | |
| Upton | 71 | Cause: Storage tank temperature 2 (bottom) Action: Check connection, check sensor, check cable | |
| Upton | 72 | Cause: Storage tank temrperature 3 (middle) Action: Check connection, check sensor, check cable | |
| Upton | 73 | Cause: Collector temperature 1 Action: Check connection, check sensor, check cable | |
| Upton | 74 | Cause: Collector temperature 2 sensor error. Action: Check connection, check sensor, check cable | |
| Upton | 78 | Cause: Water pressure Action: Check connection, check sensor, check cable | |
| Upton | 81 | Cause: LPB short-circuit or no bus power supply. Action: Check wiring, check polarity | |
| Upton | 82 | Cause: LPB address collision. Action: Check connection, check address | |
| Upton | 83 | Cause: BSB-Wire short-circuit or no communication. Action: Check wiring, check polarity | |
| Upton | 84 | Cause: BSB wire address collision. Action: Check wiring, check polarity | |
| Upton | 85 | Cause: BSB radio communication fault. Action: Connect compatible room control unit. Check wireless communication. | |
| Upton | 91 | Cause: Data overrun in EEPROM. Action: Contact Hamworthy Heating. | |
| Upton | 98 | Cause: Mixing valve clip in 1 fault. Action: Check wiring, check polarity | |
| Upton | 99 | Cause: Mixing valve clip in 2 fault. Action: Check wiring, check polarity | |
| Upton | 100 | Cause: Two clock time masters. Action: Check parameter setting. | |
| Upton | 102 | Cause: Clock time master without power reserve. Action: Check wiring, check polarity | |
| Upton | 105 | Cause: Maintenance message. Action: Reset in parameters. | |
| Upton | 109 | Cause: Supervision boiler temperature. Action: Allow the boiler to cool, investigate cause of overheating. | |
| Upton | 110 | Cause: SLT lockout. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Upton | 111 | Cause: Temperature limiter safety shutdown. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Upton | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Upton | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor. | |
| Upton | 118 | Cause: Water pressure too low 6. Action: Check system pressure, check water pressure sensor. | |
| Upton | 119 | Cause: Water pressure switch has cut out 6. Action: Check water pressure. | |
| Upton | 125 | Cause: Maximum boiler temperature exceeded. Action: Check water flow rate, check pumps, check controls. | |
| Upton | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Upton | 130 | Cause: Flue gas temperature limit exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Upton | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Upton | 133 | Cause: Safety time for establishment of flame exceeded. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Upton | 146 | Cause: Sensor/actuator configuration error. Action: Check parameter setting. | |
| Upton | 151 | Cause: BMU fault internal. Action: Check connections to clip in, replace module, check LMS. | |
| Upton | 152 | Cause: Parameterization error. Action: Check parameters. | |
| Upton | 153 | Cause: Unit manually locked. Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults). | |
| Upton | 160 | Cause: Fan speed threshold not reached. Action: Check fan connection, replace fan | |
| Upton | 162 | Cause: Air pressure switch does not close. Action: Check air pressure switch cable and connections | |
| Upton | 164 | Cause: Flow/pressure switch heating circuit error Action: Check flow pressure switch and cable and connections. | |
| Upton | 166 | Cause: Air pressure switch error does not open Action: Check air pressure switch and cable and connections. | |
| Upton | 170 | Cause: Water pressure primary. Action: Check flow pressure switch cable and connections. | |
| Upton | 176 | Cause: Water pressure 2 too high. Action: Check system pressure. | |
| Upton | 177 | Cause: Water pressure 2 too low. Action: Check system pressure. | |
| Upton | 178 | Cause: Limit thermostat HC1. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Upton | 179 | Cause: Limit thermostat HC2. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Upton | 183 | Cause: Unit in parameterization mode. Action: Escape back to main screen. | |
| Upton | 193 | Cause: Start prevention. Action: Check external controls. | |
| Upton | 217 | Cause: Sensor error. Action: Check connection, check sensor, check cable | |
| Upton | 320 | Cause: DHW charging temp sensor fault. Action: Check connection, check sensor, check cable | |
| Upton | 321 | Cause: DHW outlet sensor fault. Action: Check connection, check sensor, check cable | |
| Upton | 322 | Cause: Water pressure 3 too high. Action: Check system pressure. | |
| Upton | 323 | Cause: Water pressure 3 too low. Action: Check system pressure. | |
| Upton | 324 | Cause: Same sensor Input BX. Action: Check parameters. | |
| Upton | 325 | Cause: Same sensor Input BX/extension module. Action: Check parameters. | |
| Upton | 326 | Cause: Same sensor Input BX/mixing valve group. Action: Check parameters. | |
| Upton | 327 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Upton | 328 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Upton | 329 | Cause: Same funct ext module/mixing valve group. Action: Check parameters. | |
| Upton | 330 | Cause: Sensor input BX1 no function. Action: Sensor not Parameterised. | |
| Upton | 331 | Cause: Sensor input BX2 no function. Action: Sensor not Parameterised. | |
| Upton | 332 | Cause: Sensor input BX3 no function. Action: Sensor not Parameterised. | |
| Upton | 333 | Cause: Sensor input BX4 no function. Action: Sensor not Parameterised. | |
| Upton | 335 | Cause: Sensor input BX21 no function. Action: Sensor not Parameterised. | |
| Upton | 336 | Cause: Sensor input BX22 no function. Action: Sensor not Parameterised. | |
| Upton | 337 | Cause: Sensor input B1 no function. Action: Sensor not Parameterised. | |
| Upton | 338 | Cause: Sensor input B12 no function. Action: Sensor not Parameterised. | |
| Upton | 353 | Cause: Cascade flow sensor B10 missing. Action: Sensor not Parameterised. | |
| Upton | 372 | Cause: Limit thermostat HC3. Action: Allow the boiler to cool and reset thermostat | |
| Upton | 385 | Cause: Mains undervoltage. Action: Check incoming voltage. | |
| Upton | 386 | Cause: Fan speed tolerance. Action: Check fan connection | |
| Upton | 387 | Cause: Air pressure tolerance. Action: Check air pressure switch | |
| Upton | 388 | Cause: DHW sensor no function. Action: Sensor not parameterised . | |
| Upton | 429 | Cause: Dyn water pressure too high. Action: Check water pressure. | |
| Upton | 430 | Cause: Dyn water pressure too low. Action: Check water pressure. | |
| Upton | 432 | Cause: Function ground missing. Action: Check earth connection. | |
| Upton | 433 | Cause: Heat exchanger temperature. Action: Allow the boiler to cool and reset thermostat | |
| Varmax | 10 | Cause: Outside temperature sensor error Action: Check connection, check sensor, check cable | |
| Varmax | 20 | Cause: Boiler temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Varmax | 25 | Cause: Boiler temperature solid fuel sensor error Action: Check connection, check sensor, check cable | |
| Varmax | 26 | Cause: Common flow temprerature sensor error Action: Check connection, check sensor, check cable | |
| Varmax | 28 | Cause: Flue gas temperature sensor fault. Action: Check connection, check sensor, check cable | |
| Varmax | 30 | Cause: Flow temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Varmax | 31 | Cause: Flow temperature 1 cooling sensor error Action: Check connection, check sensor, check cable | |
| Varmax | 32 | Cause: Flow temperature 2 sensor error Action: Check connection, check sensor, check cable | |
| Varmax | 38 | Cause: Flow temperature primary controller Action: Check connection, check sensor, check cable | |
| Varmax | 40 | Cause: Return temperature 1 sensor error Action: Check connection, check sensor, check cable | |
| Varmax | 46 | Cause: Cascade return tremperature sensor error Action: Check connection, check sensor, check cable | |
| Varmax | 47 | Cause: Common return termperature sensor error Action: Check connection, check sensor, check cable | |
| Varmax | 50 | Cause: DHW temperature sensor/thermostat 1 fault. Action: Check connection, check sensor, check cable | |
| Varmax | 52 | Cause: DHW temperature sensor/thermostat 2 fault. Action: Check connection, check sensor, check cable | |
| Varmax | 54 | Cause: Flow temperature DHW Action: Check connection, check sensor, check cable | |
| Varmax | 57 | Cause: DHW Action: Check connection, check sensor, check cable | |
| Varmax | 60 | Cause: Room temperature 1, sensor error Action: Check connection, check sensor, check cable | |
| Varmax | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Varmax | 65 | Cause: Room temperature 2 Action: Check connection, check sensor, check cable | |
| Varmax | 68 | Cause: Room temperature 3 Action: Check connection, check sensor, check cable | |
| Varmax | 70 | Cause: Storage tank temperature 1 (top) Action: Check connection, check sensor, check cable | |
| Varmax | 71 | Cause: Storage tank temperature 2 (bottom) Action: Check connection, check sensor, check cable | |
| Varmax | 72 | Cause: Storage tank temrperature 3 (middle) Action: Check connection, check sensor, check cable | |
| Varmax | 73 | Cause: Collector temperature 1 Action: Check connection, check sensor, check cable | |
| Varmax | 74 | Cause: Collector temperature 2 sensor error. Action: Check connection, check sensor, check cable | |
| Varmax | 78 | Cause: Water pressure Action: Check connection, check sensor, check cable | |
| Varmax | 81 | Cause: LPB short-circuit or no bus power supply. Action: Check wiring, check polarity | |
| Varmax | 82 | Cause: LPB address collision. Action: Check connection, check address | |
| Varmax | 83 | Cause: BSB-Wire short-circuit or no communication. Action: Check wiring, check polarity | |
| Varmax | 84 | Cause: BSB wire address collision. Action: Check wiring, check polarity | |
| Varmax | 85 | Cause: BSB radio communication fault. Action: Connect compatible room control unit. Check wireless communication. | |
| Varmax | 91 | Cause: Data overrun in EEPROM. Action: Contact Hamworthy Heating. | |
| Varmax | 98 | Cause: Mixing valve clip in 1 fault. Action: Check wiring, check polarity | |
| Varmax | 99 | Cause: Mixing valve clip in 2 fault. Action: Check wiring, check polarity | |
| Varmax | 100 | Cause: Two clock time masters. Action: Check parameter setting. | |
| Varmax | 102 | Cause: Clock time master without power reserve. Action: Check wiring, check polarity | |
| Varmax | 105 | Cause: Maintenance message. Action: Reset in parameters. | |
| Varmax | 109 | Cause: Supervision boiler temperature. Action: Allow the boiler to cool, investigate cause of overheating. | |
| Varmax | 110 | Cause: SLT lockout. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Varmax | 111 | Cause: Temperature limiter safety shutdown. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Varmax | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Varmax | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor. | |
| Varmax | 118 | Cause: Water pressure too low 6. Action: Check system pressure, check water pressure sensor. | |
| Varmax | 119 | Cause: Water pressure switch has cut out 6. Action: Check water pressure. | |
| Varmax | 125 | Cause: Maximum boiler temperature exceeded. Action: Check water flow rate, check pumps, check controls. | |
| Varmax | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Varmax | 130 | Cause: Flue gas temperature limit exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Varmax | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Varmax | 133 | Cause: Safety time for establishment of flame exceeded. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Varmax | 146 | Cause: Sensor/actuator configuration error. Action: Check parameter setting. | |
| Varmax | 151 | Cause: BMU fault internal. Action: Check connections to clip in, replace module, check LMS. | |
| Varmax | 152 | Cause: Parameterization error. Action: Check parameters. | |
| Varmax | 153 | Cause: Unit manually locked. Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults). | |
| Varmax | 160 | Cause: Fan speed threshold not reached. Action: Check fan connection, replace fan | |
| Varmax | 162 | Cause: Air pressure switch does not close. Action: Check air pressure switch cable and connections | |
| Varmax | 164 | Cause: Flow/pressure switch heating circuit error Action: Check flow pressure switch and cable and connections. | |
| Varmax | 166 | Cause: Air pressure switch error does not open Action: Check air pressure switch and cable and connections. | |
| Varmax | 170 | Cause: Water pressure primary. Action: Check flow pressure switch cable and connections. | |
| Varmax | 176 | Cause: Water pressure 2 too high. Action: Check system pressure. | |
| Varmax | 177 | Cause: Water pressure 2 too low. Action: Check system pressure. | |
| Varmax | 178 | Cause: Limit thermostat HC1. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Varmax | 179 | Cause: Limit thermostat HC2. Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating. | |
| Varmax | 183 | Cause: Unit in parameterization mode. Action: Escape back to main screen. | |
| Varmax | 193 | Cause: Start prevention. Action: Check external controls. | |
| Varmax | 217 | Cause: Sensor error. Action: Check connection, check sensor, check cable | |
| Varmax | 320 | Cause: DHW charging temp sensor fault. Action: Check connection, check sensor, check cable | |
| Varmax | 321 | Cause: DHW outlet sensor fault. Action: Check connection, check sensor, check cable | |
| Varmax | 322 | Cause: Water pressure 3 too high. Action: Check system pressure. | |
| Varmax | 323 | Cause: Water pressure 3 too low. Action: Check system pressure. | |
| Varmax | 324 | Cause: Same sensor Input BX. Action: Check parameters. | |
| Varmax | 325 | Cause: Same sensor Input BX/extension module. Action: Check parameters. | |
| Varmax | 326 | Cause: Same sensor Input BX/mixing valve group. Action: Check parameters. | |
| Varmax | 327 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Varmax | 328 | Cause: Same function mixing valve group. Action: Check parameters. | |
| Varmax | 329 | Cause: Same funct ext module/mixing valve group. Action: Check parameters. | |
| Varmax | 330 | Cause: Sensor input BX1 no function. Action: Sensor not Parameterised. | |
| Varmax | 331 | Cause: Sensor input BX2 no function. Action: Sensor not Parameterised. | |
| Varmax | 332 | Cause: Sensor input BX3 no function. Action: Sensor not Parameterised. | |
| Varmax | 333 | Cause: Sensor input BX4 no function. Action: Sensor not Parameterised. | |
| Varmax | 335 | Cause: Sensor input BX21 no function. Action: Sensor not Parameterised. | |
| Varmax | 336 | Cause: Sensor input BX22 no function. Action: Sensor not Parameterised. | |
| Varmax | 337 | Cause: Sensor input B1 no function. Action: Sensor not Parameterised. | |
| Varmax | 338 | Cause: Sensor input B12 no function. Action: Sensor not Parameterised. | |
| Varmax | 353 | Cause: Cascade flow sensor B10 missing. Action: Sensor not Parameterised. | |
| Varmax | 372 | Cause: Limit thermostat HC3. Action: Allow the boiler to cool and reset thermostat | |
| Varmax | 385 | Cause: Mains undervoltage. Action: Check incoming voltage. | |
| Varmax | 386 | Cause: Fan speed tolerance. Action: Check fan connection | |
| Varmax | 387 | Cause: Air pressure tolerance. Action: Check air pressure switch | |
| Varmax | 388 | Cause: DHW sensor no function. Action: Sensor not parameterised . | |
| Varmax | 429 | Cause: Dyn water pressure too high. Action: Check water pressure. | |
| Varmax | 430 | Cause: Dyn water pressure too low. Action: Check water pressure. | |
| Varmax | 432 | Cause: Function ground missing. Action: Check earth connection. | |
| Varmax | 433 | Cause: Heat exchanger temperature. Action: Allow the boiler to cool and reset thermostat | |
| Fleet Horizontal | 10 | Cause: Fault outside sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Horizontal | 28 | Cause: Fault flue gas sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Horizontal | 32 | Cause: Fault flow temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Fleet Horizontal | 50 | Cause: Fault DHW temperature sensor 1. Action: Check connection, check sensor, check cable. | |
| Fleet Horizontal | 52 | Cause: Fault DHW temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Fleet Horizontal | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Fleet Horizontal | 62 | Cause: Wrong room unit 1 or wrong radio clock connected. Action: Connect compatible room control unit. | |
| Fleet Horizontal | 77 | Cause: Fault air pressure sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Horizontal | 78 | Cause: Fault water pressure sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Horizontal | 82 | Cause: Address collision on LPB. Action: Check addresses of connected modules. | |
| Fleet Horizontal | 91 | Cause: Data overflow in EEPROM. Action: Hardware fault, LMU may need replacing. | |
| Fleet Horizontal | 92 | Cause: Hardware fault in electronics. Action: Hardware fault, LMU may need replacing. | |
| Fleet Horizontal | 95 | Cause: Invalid time of day. Action: Set correct time. | |
| Fleet Horizontal | 100 | Cause: 2 clock time masters. Action: Check settings of LMU, only 1 master allowed. | |
| Fleet Horizontal | 105 | Cause: Maintenance message. Action: P629 to reset : change from 0 to 1. | |
| Fleet Horizontal | 110 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Fleet Horizontal | 111 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Fleet Horizontal | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Fleet Horizontal | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor | |
| Fleet Horizontal | 118 | Cause: Water pressure too low. Action: Check system pressure, check water pressure sensor | |
| Fleet Horizontal | 119 | Cause: Water pressure switch has cut out. Action: Check water pressure. | |
| Fleet Horizontal | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Fleet Horizontal | 129 | Cause: Fan speed maximum/minimum has been violated. Action: Check fan. | |
| Fleet Horizontal | 130 | Cause: Flue gas limit temperature exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Fleet Horizontal | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Fleet Horizontal | 133 | Cause: No flame on completion of safety time. Action: Check operation of gas valve. Check spark igniter. | |
| Fleet Horizontal | 134 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Fleet Horizontal | 140 | Cause: Inadmissible LPB segment number/device N°. Action: Check settings of LMU and boiler address settings. | |
| Fleet Horizontal | 148 | Cause: Incompatibility LPB... interface / basic unit. Action: Check settings of LMU | |
| Fleet Horizontal | 151 | Cause: Internal fault with LMU. Action: Check connections to clip in, replace module, check LMU. | |
| Fleet Horizontal | 152 | Cause: Fault in connection with LMU settings. Action: Check LMU settings. | |
| Fleet Horizontal | 153 | Cause: LMU has locked out. Action: Press reset button (code appears if reset button is pressed when there are no faults). | |
| Fleet Horizontal | 154 | Cause: Flow Problems. Action: Check water flow through the boiler & check the pumps. | |
| Fleet Horizontal | 160 | Cause: Fan speed threshold not reached. Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris. | |
| Fleet Horizontal | 161 | Cause: Maximum fan speed exceeded. Action: Check parameters. | |
| Fleet Horizontal | 162 | Cause: Fault air pressure switch (does not close). Action: Check air pressure switch and cable and connections. | |
| Fleet Horizontal | 164 | Cause: Fault heating circuit flow switch / pressure switch. Action: Check air pressure switch and cable and connections. | |
| Fleet Horizontal | 166 | Cause: Fault air pressure switch (does not open). Action: Check air pressure switch and cable and connections. | |
| Fleet Horizontal | 180 | Cause: Chimney sweep function active. Action: Check boiler operation setting. | |
| Fleet Horizontal | 181 | Cause: Controller stop function active. Action: Check boiler operation setting. | |
| Fleet Horizontal | 183 | Cause: LMU in parameter setting mode. Action: Unit in programme mode. | |
| Fleet Vertical | 10 | Cause: Fault outside sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Vertical | 28 | Cause: Fault flue gas sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Vertical | 32 | Cause: Fault flow temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Fleet Vertical | 50 | Cause: Fault DHW temperature sensor 1. Action: Check connection, check sensor, check cable. | |
| Fleet Vertical | 52 | Cause: Fault DHW temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Fleet Vertical | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Fleet Vertical | 62 | Cause: Wrong room unit 1 or wrong radio clock connected. Action: Connect compatible room control unit. | |
| Fleet Vertical | 77 | Cause: Fault air pressure sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Vertical | 78 | Cause: Fault water pressure sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Vertical | 82 | Cause: Address collision on LPB. Action: Check addresses of connected modules. | |
| Fleet Vertical | 91 | Cause: Data overflow in EEPROM. Action: Hardware fault, LMU may need replacing. | |
| Fleet Vertical | 92 | Cause: Hardware fault in electronics. Action: Hardware fault, LMU may need replacing. | |
| Fleet Vertical | 95 | Cause: Invalid time of day. Action: Set correct time. | |
| Fleet Vertical | 100 | Cause: 2 clock time masters. Action: Check settings of LMU, only 1 master allowed. | |
| Fleet Vertical | 105 | Cause: Maintenance message. Action: P629 to reset : change from 0 to 1. | |
| Fleet Vertical | 110 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Fleet Vertical | 111 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Fleet Vertical | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Fleet Vertical | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor | |
| Fleet Vertical | 118 | Cause: Water pressure too low. Action: Check system pressure, check water pressure sensor | |
| Fleet Vertical | 119 | Cause: Water pressure switch has cut out. Action: Check water pressure. | |
| Fleet Vertical | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Fleet Vertical | 129 | Cause: Fan speed maximum/minimum has been violated. Action: Check fan. | |
| Fleet Vertical | 130 | Cause: Flue gas limit temperature exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Fleet Vertical | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Fleet Vertical | 133 | Cause: No flame on completion of safety time. Action: Check operation of gas valve. Check spark igniter. | |
| Fleet Vertical | 134 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Fleet Vertical | 140 | Cause: Inadmissible LPB segment number/device N°. Action: Check settings of LMU and boiler address settings. | |
| Fleet Vertical | 148 | Cause: Incompatibility LPB... interface / basic unit. Action: Check settings of LMU | |
| Fleet Vertical | 151 | Cause: Internal fault with LMU. Action: Check connections to clip in, replace module, check LMU. | |
| Fleet Vertical | 152 | Cause: Fault in connection with LMU settings. Action: Check LMU settings. | |
| Fleet Vertical | 153 | Cause: LMU has locked out. Action: Press reset button (code appears if reset button is pressed when there are no faults). | |
| Fleet Vertical | 154 | Cause: Flow Problems. Action: Check water flow through the boiler & check the pumps. | |
| Fleet Vertical | 160 | Cause: Fan speed threshold not reached. Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris. | |
| Fleet Vertical | 161 | Cause: Maximum fan speed exceeded. Action: Check parameters. | |
| Fleet Vertical | 162 | Cause: Fault air pressure switch (does not close). Action: Check air pressure switch and cable and connections. | |
| Fleet Vertical | 164 | Cause: Fault heating circuit flow switch / pressure switch. Action: Check air pressure switch and cable and connections. | |
| Fleet Vertical | 166 | Cause: Fault air pressure switch (does not open). Action: Check air pressure switch and cable and connections. | |
| Fleet Vertical | 180 | Cause: Chimney sweep function active. Action: Check boiler operation setting. | |
| Fleet Vertical | 181 | Cause: Controller stop function active. Action: Check boiler operation setting. | |
| Fleet Vertical | 183 | Cause: LMU in parameter setting mode. Action: Unit in programme mode. | |
| Fleet Wall Hung | 10 | Cause: Fault outside sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Wall Hung | 28 | Cause: Fault flue gas sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Wall Hung | 32 | Cause: Fault flow temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Fleet Wall Hung | 50 | Cause: Fault DHW temperature sensor 1. Action: Check connection, check sensor, check cable. | |
| Fleet Wall Hung | 52 | Cause: Fault DHW temperature sensor 2. Action: Check connection, check sensor, check cable. | |
| Fleet Wall Hung | 61 | Cause: Fault room unit 1. Action: Check room device. | |
| Fleet Wall Hung | 62 | Cause: Wrong room unit 1 or wrong radio clock connected. Action: Connect compatible room control unit. | |
| Fleet Wall Hung | 77 | Cause: Fault air pressure sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Wall Hung | 78 | Cause: Fault water pressure sensor. Action: Check connection, check sensor, check cable. | |
| Fleet Wall Hung | 82 | Cause: Address collision on LPB. Action: Check addresses of connected modules. | |
| Fleet Wall Hung | 91 | Cause: Data overflow in EEPROM. Action: Hardware fault, LMU may need replacing. | |
| Fleet Wall Hung | 92 | Cause: Hardware fault in electronics. Action: Hardware fault, LMU may need replacing. | |
| Fleet Wall Hung | 95 | Cause: Invalid time of day. Action: Set correct time. | |
| Fleet Wall Hung | 100 | Cause: 2 clock time masters. Action: Check settings of LMU, only 1 master allowed. | |
| Fleet Wall Hung | 105 | Cause: Maintenance message. Action: P629 to reset : change from 0 to 1. | |
| Fleet Wall Hung | 110 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Fleet Wall Hung | 111 | Cause: Limit thermostat has cut out. Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating. | |
| Fleet Wall Hung | 113 | Cause: Flue gas supervision equipment has cut out. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Fleet Wall Hung | 117 | Cause: Water pressure too high. Action: Check system pressure, check water pressure sensor | |
| Fleet Wall Hung | 118 | Cause: Water pressure too low. Action: Check system pressure, check water pressure sensor | |
| Fleet Wall Hung | 119 | Cause: Water pressure switch has cut out. Action: Check water pressure. | |
| Fleet Wall Hung | 128 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Fleet Wall Hung | 129 | Cause: Fan speed maximum/minimum has been violated. Action: Check fan. | |
| Fleet Wall Hung | 130 | Cause: Flue gas limit temperature exceeded. Action: Check the cause of high flue gas temperature. Check sensor. | |
| Fleet Wall Hung | 132 | Cause: Safety shutdown. Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches. | |
| Fleet Wall Hung | 133 | Cause: No flame on completion of safety time. Action: Check operation of gas valve. Check spark igniter. | |
| Fleet Wall Hung | 134 | Cause: Loss of flame during operation. Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing. | |
| Fleet Wall Hung | 140 | Cause: Inadmissible LPB segment number/device N°. Action: Check settings of LMU and boiler address settings. | |
| Fleet Wall Hung | 148 | Cause: Incompatibility LPB... interface / basic unit. Action: Check settings of LMU | |
| Fleet Wall Hung | 151 | Cause: Internal fault with LMU. Action: Check connections to clip in, replace module, check LMU. | |
| Fleet Wall Hung | 152 | Cause: Fault in connection with LMU settings. Action: Check LMU settings. | |
| Fleet Wall Hung | 153 | Cause: LMU has locked out. Action: Press reset button (code appears if reset button is pressed when there are no faults). | |
| Fleet Wall Hung | 154 | Cause: Flow Problems. Action: Check water flow through the boiler & check the pumps. | |
| Fleet Wall Hung | 160 | Cause: Fan speed threshold not reached. Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris. | |
| Fleet Wall Hung | 161 | Cause: Maximum fan speed exceeded. Action: Check parameters. | |
| Fleet Wall Hung | 162 | Cause: Fault air pressure switch (does not close). Action: Check air pressure switch and cable and connections. | |
| Fleet Wall Hung | 164 | Cause: Fault heating circuit flow switch / pressure switch. Action: Check air pressure switch and cable and connections. | |
| Fleet Wall Hung | 166 | Cause: Fault air pressure switch (does not open). Action: Check air pressure switch and cable and connections. | |
| Fleet Wall Hung | 180 | Cause: Chimney sweep function active. Action: Check boiler operation setting. | |
| Fleet Wall Hung | 181 | Cause: Controller stop function active. Action: Check boiler operation setting. | |
| Fleet Wall Hung | 183 | Cause: LMU in parameter setting mode. Action: Unit in programme mode. | |
| Dorchester DR-FC Evo | S01 | Cause: Sensor is not (correctly) connected. Action: Connect the sensor lead to JP3. Cause: Damaged cable and/or defective sensor. Action: Replace the cable and/or sensor. | (blocking error) Open circuit from temperature sensor T2 at the bottom of the tank. |
| Dorchester DR-FC Evo | S02 | Cause: Sensor is not (correctly) connected. Action: Connect the sensor lead to JP5. Cause: Damaged cable and/or defective sensor. Action: Damaged cable and/or defective sensor. | (blocking error) Open circuit from sensor 1 of temperature sensor T1 at the top of tank(1). |
| Dorchester DR-FC Evo | S03 | Cause: Sensor is not (correctly) connected. Action: Connect the sensor lead to JP5. Cause: Damaged cable and/or defective sensor. Action: Replace the cable and/or sensor. | (blocking error) Open circuit in sensor 2 of temperature sensor T1 at the top of the tank (1). |
| Dorchester DR-FC Evo | S04 | Cause: Dummy is not (correctly) connected. Action: Connect the dummy sensor (dummy sensor 1 and 2) leads to JP4. Cause: Defective dummy. Action: Replace the dummy sensor. | (blocking error) Open circuit from dummy1. |
| Dorchester DR-FC Evo | S05 | Cause: Dummy is not (correctly) connected. Action: Connect the dummy sensor (dummy sensor 1 and 2) leads to JP4. Cause: Defective dummy. Action: Replace the dummy sensor. | (blocking error) Open circuit from dummy 2. |
| Dorchester DR-FC Evo | S11 | Cause: Short circuit in sensor circuit. Action: Replace the cable and/or sensor. | (blocking error) Short circuit in temperature sensor T2 at the bottom of the tank. |
| Dorchester DR-FC Evo | S12 | Cause: Short circuit in sensor circuit. Action: Replace the cable and/or sensor. | (blocking error) Short circuit in sensor 1 of temperature sensor T1 at top of tank. |
| Dorchester DR-FC Evo | S13 | Cause: Short circuit in sensor circuit. Action: Replace the cable and/or sensor. | (blocking error) Short circuit in sensor 2 of temperature sensor T1 at the top of the tank. |
| Dorchester DR-FC Evo | S14 | Cause: Short circuit in sensor circuit. Action: Replace the dummy sensor. | (blocking error) Short circuit from dummy1. |
| Dorchester DR-FC Evo | S15 | Cause: Short circuit in sensor circuit. Action: Replace the dummy sensor. | (blocking error) Short circuit from dummy2. |
| Dorchester DR-FC Evo | F01 | Cause: Live and neutral connected wrong way around. Action: Be sure to connect the live and neutral correctly (3.10 Electrical connection in the installation manual). The water heater is phase-sensitive. Cause: Condensation on the flame probe. Action: 1. Disconnect the lead at the flame probe. 2. Ignite the water heater three times. 3. Reconnect the ionisation lead to the flame probe. 4. Ignite the water heater again. 5. The repeated ignition attempts will have caused the condensation to evaporate. Cause: Floating neutral. Action: Install an isolating transformer. | (blocking error) Defect in power supply circuit. |
| Dorchester DR-FC Evo | F02 | Cause: Because of a drop in the supply voltage the fan will not run at the correct speed. Action: 1. Check the supply voltage this must be 230VAC (-15% +10%) 2. Reset controller | (lock out error) Fan fails to run at correct speed. |
| Dorchester DR-FC Evo | F03 | Cause: Damaged wiring/Open circuit. Action: 1. Check the wiring between the pressure switch and the controller. 2. If necessary replace the wiring | (lock out error) The pressure switch fails to work correctly. |
| Dorchester DR-FC Evo | F04 | Cause: No gas. Action: 1. Open the main gas supply valve and/or the manual gas supply valve before the gas control valve. 2. Check supply pressure to the gas control valve. 3. If necessary Cause: Air in the gas pipes. Action: Bleed the air out of the gas pipe. Cause: Defect in the hot surface igniter circuit. Action: 1. Check that the hot surface igniter is correctly connected (JP2). 2. Check the wiring of the hot surface igniter. 3. Measure the resistance across the hot surface igniter. This must lie between 2 and 10 Ohm (at room temperature). 4. Check that the hot surface igniter lights up during ignition. 5. If necessary replace the hot surface igniter. Cause: Defect in the ionisation circuit. Action: 1. Check that the flame probe is correctly connected (JP2). 2. Check the wiring of the flame probe. 3. Measure the ionisation current. This must be a minimum of 1.5microA. 4. If necessary replace the wiring. Cause: Supply voltage too low. Action: Check the supply voltage | (lock out error) Three unsuccessful ignition attempts. |
| Dorchester DR-FC Evo | F05 | Cause: Incorrect roof or wall flue terminal. Recirculating flue gases. Action: 1. Check that the correct roof or wall flue terminal has been installed. 2. If necessary install the correct roof or wall flue terminal. 3. Check that the roof or wall flue terminal discharges into a permitted area. | (lock out error) Too many flame errors have been signalled. |
| Dorchester DR-FC Evo | F06 | Cause: Damaged cable in contact with metal surface or bent flame probe. Action: Check the wiring and the flame probe. Replace the wiring and/or flame probe if necessary. Cause: Ceramic part of the flame probe is broken/cracked. Action: 1. Check whether the ceramic part of the flame probe is still intact. 2. If not the flame probe must be replaced. | (blocking error) Short circuit between flame probe and earth. |
| Dorchester DR-FC Evo | F07 | Cause: Defective gas control valves. Action: 1. Check whether there is still burner pressure present after the gas control valves have closed. 2. Check whether a flame is still present after the gas control valves have closed. 3. If this is the case the gas control valve must be replaced. | (lock out error) A flame has been detected after the gas control valve was closed. |
| Dorchester DR-FC Evo | F08 | Cause: Flame detection before the gas control valve opened. Action: 1. Reset controller. 2. If the error appears again | (lock out error) Error message from safety relay. |
| Dorchester DR-FC Evo | F09 | Cause: Temperature at the top of the tank exceeds 93°C. Action: 1. Check that the circulation pump (if present) is working. 2. Check the position of temperature sensor T1. 3. Reset controller. | (lock out error) Water temperature protection. |
| Dorchester DR-FC Evo | F11 | Cause: Defective gas control valves. Action: 1. Check whether there is still burner pressure present after the gas control valves have closed.. 2. Check whether a flame is still present after the gas control valves have closed.. 3. If this is the case the gas control valve must be replaced. | (blocking error) Flame detection with closed gas control valve. |
| Dorchester DR-FC Evo | F19 | Cause: There is not enough supply voltage. Action: 1. Check that there is power to the controller. Cause: There is not enough supply voltage. Action: 2. The measured voltage must be 230 VAC (-15% +10%). | (blocking error) Power supply voltage is too low. |
| Dorchester DR-FC Evo | C02 | Cause: Incorrect reference voltage from the AD converter. Action: 1. Reset controller. 2. Check that the frequency of the power supply is compliant (3.4.2 "General and electrical specifications" in installation manual). If not contact your installation engineer. 3. If the frequency is correct but the error persists replace the controller. | (lock out error) Error message from the controller. |
| Dorchester DR-FC Evo | C03 | Cause: Too many resets in too short a period. Action: Wait for the error to disappear (maximum 1 hour). If the error does not disappear replace the water heater controller. | (blocking error) Reset error. |
| Dorchester DR-FC Evo | C04 | Cause: Incorrect water heater selection/Incorrect selection resistor. Action: 1. Check whether the correct water heater is selected (12.5"Display the selected water heater" in installation manual). 2. If the correct water heater is selected fit the correct selection resistor. 3. If incorrect water heater selected select the correct one. | (blocking error) Appliance selection error. |
| Dorchester DR-FC Evo | E01 | Cause: The temperature of the water at the top of the tank is >85°C. Action: None. This is a temporary message that may appear from time to time but will disappear automatically. | (blocking error) The temperature protection at the top of the tank has been activated. |
| Dorchester DR-FC Evo | E03 | Cause: The two temperature sensors in the tank detect a difference of >10°C over a period of at least 60 seconds. Action: 1. Check sensor position and wiring. 2. Reset the controller if necessary. Replace the sensor if the error persists. | (lock-out error) Error in temperature sensor T1 at the top of the tank. |
| Dorchester DR-FC Evo | E04 | Cause: The two temperature sensors detect a difference of >10°C over a period of at least 60 seconds. Action: 1. Check the wiring of the dummy1 and dummy2. 2. Reset the controller if necessary. Replace the dummy sensor if the error persists. | (lock-out error) Defect in the dummy sensor(2). |