Hamworthy Heating

Help with identifying fault and error codes

Use the tool below for instant help with common error codes on Hamworthy commercial boilers and water heaters.

Simply select the product and then type in the error code as displayed on the screen. For boilers with Siemens LMS controls do not include any letters. For all other products make sure you include the letters and numbers, e.g. E161

*Note - This tool only displays fault codes for the following products:

  • Boilers with Siemens LMS controls - Upton, Purewell Variheat mk2, Wessex ModuMax mk3, Modumax mk4, Stratton mk2, and Varmax.
  • Boilers with Siemens LMU controls - Purewell VariHeat, Fleet, Stratton mk1, and Wessex ModuMax mk2 & HE.
  • Water Heaters - Dorchester DR-FC Evo, Dorchester DR-CC

For all other products please refer to the operating manual as these list all the fault codes and explanations per product.

If you still need help, please email technical@hamworthy-heating.com or call us on 01202 662505.

Error codes that are not listed and any work on commercial boilers and water heaters should only be investigated by a trained and competent person.

Should an error code appear which cannot be reset, or an error code repeatedly occurs, contact our technical team for assistance. Do not continue to operate or use the boiler/water heater as this may cause damage to the controls.

You may also want to refer to the product operating manual. If you don’t have a copy to hand you can download an electronic copy in the online technical library.

ProductError codeCause & actionDescription
Wessex ModuMax10

Cause: Fault outside sensor.

Action: Check connection, check sensor, check cable.

Wessex ModuMax28

Cause: Fault flue gas sensor.

Action: Check connection, check sensor, check cable.

Wessex ModuMax32

Cause: Fault flow temperature sensor 2.

Action: Check connection, check sensor, check cable.

Wessex ModuMax50

Cause: Fault DHW temperature sensor 1.

Action: Check connection, check sensor, check cable.

Wessex ModuMax52

Cause: Fault DHW temperature sensor 2.

Action: Check connection, check sensor, check cable.

Wessex ModuMax61

Cause: Fault room unit 1.

Action: Check room device.

Wessex ModuMax62

Cause: Wrong room unit 1 or wrong radio clock connected.

Action: Connect compatible room control unit.

Wessex ModuMax77

Cause: Fault air pressure sensor.

Action: Check connection, check sensor, check cable.

Wessex ModuMax78

Cause: Fault water pressure sensor.

Action: Check connection, check sensor, check cable.

Wessex ModuMax82

Cause: Address collision on LPB.

Action: Check addresses of connected modules.

Wessex ModuMax91

Cause: Data overflow in EEPROM.

Action: Hardware fault, LMU may need replacing.

Wessex ModuMax92

Cause: Hardware fault in electronics.

Action: Hardware fault, LMU may need replacing.

Wessex ModuMax95

Cause: Invalid time of day.

Action: Set correct time.

Wessex ModuMax100

Cause: 2 clock time masters.

Action: Check settings of LMU, only 1 master allowed.

Wessex ModuMax105

Cause: Maintenance message.

Action: P629 to reset : change from 0 to 1.

Wessex ModuMax110

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Wessex ModuMax111

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Wessex ModuMax113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Wessex ModuMax117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor

Wessex ModuMax118

Cause: Water pressure too low.

Action: Check system pressure, check water pressure sensor

Wessex ModuMax119

Cause: Water pressure switch has cut out.

Action: Check water pressure.

Wessex ModuMax128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Wessex ModuMax129

Cause: Fan speed maximum/minimum has been violated.

Action: Check fan.

Wessex ModuMax130

Cause: Flue gas limit temperature exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Wessex ModuMax132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Wessex ModuMax133

Cause: No flame on completion of safety time.

Action: Check operation of gas valve. Check spark igniter.

Wessex ModuMax134

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Wessex ModuMax140

Cause: Inadmissible LPB segment number/device N°.

Action: Check settings of LMU and boiler address settings.

Wessex ModuMax148

Cause: Incompatibility LPB... interface / basic unit.

Action: Check settings of LMU

Wessex ModuMax151

Cause: Internal fault with LMU.

Action: Check connections to clip in, replace module, check LMU.

Wessex ModuMax152

Cause: Fault in connection with LMU settings.

Action: Check LMU settings.

Wessex ModuMax153

Cause: LMU has locked out.

Action: Press reset button (code appears if reset button is pressed when there are no faults).

Wessex ModuMax154

Cause: Flow Problems.

Action: Check water flow through the boiler & check the pumps.

Wessex ModuMax160

Cause: Fan speed threshold not reached.

Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris.

Wessex ModuMax161

Cause: Maximum fan speed exceeded.

Action: Check parameters.

Wessex ModuMax162

Cause: Fault air pressure switch (does not close).

Action: Check air pressure switch and cable and connections.

Wessex ModuMax164

Cause: Fault heating circuit flow switch / pressure switch.

Action: Check air pressure switch and cable and connections.

Wessex ModuMax166

Cause: Fault air pressure switch (does not open).

Action: Check air pressure switch and cable and connections.

Wessex ModuMax180

Cause: Chimney sweep function active.

Action: Check boiler operation setting.

Wessex ModuMax181

Cause: Controller stop function active.

Action: Check boiler operation setting.

Wessex ModuMax183

Cause: LMU in parameter setting mode.

Action: Unit in programme mode.

Wessex ModuMax mk210

Cause: Fault outside sensor.

Action: Check connection, check sensor, check cable.

Wessex ModuMax mk228

Cause: Fault flue gas sensor.

Action: Check connection, check sensor, check cable.

Wessex ModuMax mk232

Cause: Fault flow temperature sensor 2.

Action: Check connection, check sensor, check cable.

Wessex ModuMax mk250

Cause: Fault DHW temperature sensor 1.

Action: Check connection, check sensor, check cable.

Wessex ModuMax mk252

Cause: Fault DHW temperature sensor 2.

Action: Check connection, check sensor, check cable.

Wessex ModuMax mk261

Cause: Fault room unit 1.

Action: Check room device.

Wessex ModuMax mk262

Cause: Wrong room unit 1 or wrong radio clock connected.

Action: Connect compatible room control unit.

Wessex ModuMax mk277

Cause: Fault air pressure sensor.

Action: Check connection, check sensor, check cable.

Wessex ModuMax mk278

Cause: Fault water pressure sensor.

Action: Check connection, check sensor, check cable.

Wessex ModuMax mk282

Cause: Address collision on LPB.

Action: Check addresses of connected modules.

Wessex ModuMax mk291

Cause: Data overflow in EEPROM.

Action: Hardware fault, LMU may need replacing.

Wessex ModuMax mk292

Cause: Hardware fault in electronics.

Action: Hardware fault, LMU may need replacing.

Wessex ModuMax mk295

Cause: Invalid time of day.

Action: Set correct time.

Wessex ModuMax mk2100

Cause: 2 clock time masters.

Action: Check settings of LMU, only 1 master allowed.

Wessex ModuMax mk2105

Cause: Maintenance message.

Action: P629 to reset : change from 0 to 1.

Wessex ModuMax mk2110

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Wessex ModuMax mk2111

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Wessex ModuMax mk2113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Wessex ModuMax mk2117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor

Wessex ModuMax mk2118

Cause: Water pressure too low.

Action: Check system pressure, check water pressure sensor

Wessex ModuMax mk2119

Cause: Water pressure switch has cut out.

Action: Check water pressure.

Wessex ModuMax mk2128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Wessex ModuMax mk2129

Cause: Fan speed maximum/minimum has been violated.

Action: Check fan.

Wessex ModuMax mk2130

Cause: Flue gas limit temperature exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Wessex ModuMax mk2132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Wessex ModuMax mk2133

Cause: No flame on completion of safety time.

Action: Check operation of gas valve. Check spark igniter.

Wessex ModuMax mk2134

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Wessex ModuMax mk2140

Cause: Inadmissible LPB segment number/device N°.

Action: Check settings of LMU and boiler address settings.

Wessex ModuMax mk2148

Cause: Incompatibility LPB... interface / basic unit.

Action: Check settings of LMU

Wessex ModuMax mk2151

Cause: Internal fault with LMU.

Action: Check connections to clip in, replace module, check LMU.

Wessex ModuMax mk2152

Cause: Fault in connection with LMU settings.

Action: Check LMU settings.

Wessex ModuMax mk2153

Cause: LMU has locked out.

Action: Press reset button (code appears if reset button is pressed when there are no faults).

Wessex ModuMax mk2154

Cause: Flow Problems.

Action: Check water flow through the boiler & check the pumps.

Wessex ModuMax mk2160

Cause: Fan speed threshold not reached.

Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris.

Wessex ModuMax mk2161

Cause: Maximum fan speed exceeded.

Action: Check parameters.

Wessex ModuMax mk2162

Cause: Fault air pressure switch (does not close).

Action: Check air pressure switch and cable and connections.

Wessex ModuMax mk2164

Cause: Fault heating circuit flow switch / pressure switch.

Action: Check air pressure switch and cable and connections.

Wessex ModuMax mk2166

Cause: Fault air pressure switch (does not open).

Action: Check air pressure switch and cable and connections.

Wessex ModuMax mk2180

Cause: Chimney sweep function active.

Action: Check boiler operation setting.

Wessex ModuMax mk2181

Cause: Controller stop function active.

Action: Check boiler operation setting.

Wessex ModuMax mk2183

Cause: LMU in parameter setting mode.

Action: Unit in programme mode.

Wessex ModuMax mk310

Cause: Outside temperature sensor error

Action: Check connection, check sensor, check cable

Wessex ModuMax mk320

Cause: Boiler temperature 1 sensor error

Action: Check connection, check sensor, check cable

Wessex ModuMax mk325

Cause: Boiler temperature solid fuel sensor error

Action: Check connection, check sensor, check cable

Wessex ModuMax mk326

Cause: Common flow temprerature sensor error

Action: Check connection, check sensor, check cable

Wessex ModuMax mk328

Cause: Flue gas temperature sensor fault.

Action: Check connection, check sensor, check cable

Wessex ModuMax mk330

Cause: Flow temperature 1 sensor error

Action: Check connection, check sensor, check cable

Wessex ModuMax mk331

Cause: Flow temperature 1 cooling sensor error

Action: Check connection, check sensor, check cable

Wessex ModuMax mk332

Cause: Flow temperature 2 sensor error

Action: Check connection, check sensor, check cable

Wessex ModuMax mk338

Cause: Flow temperature primary controller

Action: Check connection, check sensor, check cable

Wessex ModuMax mk340

Cause: Return temperature 1 sensor error

Action: Check connection, check sensor, check cable

Wessex ModuMax mk346

Cause: Cascade return tremperature sensor error

Action: Check connection, check sensor, check cable

Wessex ModuMax mk347

Cause: Common return termperature sensor error

Action: Check connection, check sensor, check cable

Wessex ModuMax mk350

Cause: DHW temperature sensor/thermostat 1 fault.

Action: Check connection, check sensor, check cable

Wessex ModuMax mk352

Cause: DHW temperature sensor/thermostat 2 fault.

Action: Check connection, check sensor, check cable

Wessex ModuMax mk354

Cause: Flow temperature DHW

Action: Check connection, check sensor, check cable

Wessex ModuMax mk357

Cause: DHW

Action: Check connection, check sensor, check cable

Wessex ModuMax mk360

Cause: Room temperature 1, sensor error

Action: Check connection, check sensor, check cable

Wessex ModuMax mk361

Cause: Fault room unit 1.

Action: Check room device.

Wessex ModuMax mk365

Cause: Room temperature 2

Action: Check connection, check sensor, check cable

Wessex ModuMax mk368

Cause: Room temperature 3

Action: Check connection, check sensor, check cable

Wessex ModuMax mk370

Cause: Storage tank temperature 1 (top)

Action: Check connection, check sensor, check cable

Wessex ModuMax mk371

Cause: Storage tank temperature 2 (bottom)

Action: Check connection, check sensor, check cable

Wessex ModuMax mk372

Cause: Storage tank temrperature 3 (middle)

Action: Check connection, check sensor, check cable

Wessex ModuMax mk373

Cause: Collector temperature 1

Action: Check connection, check sensor, check cable

Wessex ModuMax mk374

Cause: Collector temperature 2 sensor error.

Action: Check connection, check sensor, check cable

Wessex ModuMax mk378

Cause: Water pressure

Action: Check connection, check sensor, check cable

Wessex ModuMax mk381

Cause: LPB short-circuit or no bus power supply.

Action: Check wiring, check polarity

Wessex ModuMax mk382

Cause: LPB address collision.

Action: Check connection, check address

Wessex ModuMax mk383

Cause: BSB-Wire short-circuit or no communication.

Action: Check wiring, check polarity

Wessex ModuMax mk384

Cause: BSB wire address collision.

Action: Check wiring, check polarity

Wessex ModuMax mk385

Cause: BSB radio communication fault.

Action: Connect compatible room control unit. Check wireless communication.

Wessex ModuMax mk391

Cause: Data overrun in EEPROM.

Action: Contact Hamworthy Heating.

Wessex ModuMax mk398

Cause: Mixing valve clip in 1 fault.

Action: Check wiring, check polarity

Wessex ModuMax mk399

Cause: Mixing valve clip in 2 fault.

Action: Check wiring, check polarity

Wessex ModuMax mk3100

Cause: Two clock time masters.

Action: Check parameter setting.

Wessex ModuMax mk3102

Cause: Clock time master without power reserve.

Action: Check wiring, check polarity

Wessex ModuMax mk3105

Cause: Maintenance message.

Action: Reset in parameters.

Wessex ModuMax mk3109

Cause: Supervision boiler temperature.

Action: Allow the boiler to cool, investigate cause of overheating.

Wessex ModuMax mk3110

Cause: SLT lockout.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Wessex ModuMax mk3111

Cause: Temperature limiter safety shutdown.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Wessex ModuMax mk3113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Wessex ModuMax mk3117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor.

Wessex ModuMax mk3118

Cause: Water pressure too low 6.

Action: Check system pressure, check water pressure sensor.

Wessex ModuMax mk3119

Cause: Water pressure switch has cut out 6.

Action: Check water pressure.

Wessex ModuMax mk3125

Cause: Maximum boiler temperature exceeded.

Action: Check water flow rate, check pumps, check controls.

Wessex ModuMax mk3128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Wessex ModuMax mk3130

Cause: Flue gas temperature limit exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Wessex ModuMax mk3132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Wessex ModuMax mk3133

Cause: Safety time for establishment of flame exceeded.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Wessex ModuMax mk3146

Cause: Sensor/actuator configuration error.

Action: Check parameter setting.

Wessex ModuMax mk3151

Cause: BMU fault internal.

Action: Check connections to clip in, replace module, check LMS.

Wessex ModuMax mk3152

Cause: Parameterization error.

Action: Check parameters.

Wessex ModuMax mk3153

Cause: Unit manually locked.

Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults).

Wessex ModuMax mk3160

Cause: Fan speed threshold not reached.

Action: Check fan connection, replace fan

Wessex ModuMax mk3162

Cause: Air pressure switch does not close.

Action: Check air pressure switch cable and connections

Wessex ModuMax mk3164

Cause: Flow/pressure switch heating circuit error

Action: Check flow pressure switch and cable and connections.

Wessex ModuMax mk3166

Cause: Air pressure switch error does not open

Action: Check air pressure switch and cable and connections.

Wessex ModuMax mk3170

Cause: Water pressure primary.

Action: Check flow pressure switch cable and connections.

Wessex ModuMax mk3176

Cause: Water pressure 2 too high.

Action: Check system pressure.

Wessex ModuMax mk3177

Cause: Water pressure 2 too low.

Action: Check system pressure.

Wessex ModuMax mk3178

Cause: Limit thermostat HC1.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Wessex ModuMax mk3179

Cause: Limit thermostat HC2.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Wessex ModuMax mk3183

Cause: Unit in parameterization mode.

Action: Escape back to main screen.

Wessex ModuMax mk3193

Cause: Start prevention.

Action: Check external controls.

Wessex ModuMax mk3217

Cause: Sensor error.

Action: Check connection, check sensor, check cable

Wessex ModuMax mk3320

Cause: DHW charging temp sensor fault.

Action: Check connection, check sensor, check cable

Wessex ModuMax mk3321

Cause: DHW outlet sensor fault.

Action: Check connection, check sensor, check cable

Wessex ModuMax mk3322

Cause: Water pressure 3 too high.

Action: Check system pressure.

Wessex ModuMax mk3323

Cause: Water pressure 3 too low.

Action: Check system pressure.

Wessex ModuMax mk3324

Cause: Same sensor Input BX.

Action: Check parameters.

Wessex ModuMax mk3325

Cause: Same sensor Input BX/extension module.

Action: Check parameters.

Wessex ModuMax mk3326

Cause: Same sensor Input BX/mixing valve group.

Action: Check parameters.

Wessex ModuMax mk3327

Cause: Same function mixing valve group.

Action: Check parameters.

Wessex ModuMax mk3328

Cause: Same function mixing valve group.

Action: Check parameters.

Wessex ModuMax mk3329

Cause: Same funct ext module/mixing valve group.

Action: Check parameters.

Wessex ModuMax mk3330

Cause: Sensor input BX1 no function.

Action: Sensor not Parameterised.

Wessex ModuMax mk3331

Cause: Sensor input BX2 no function.

Action: Sensor not Parameterised.

Wessex ModuMax mk3332

Cause: Sensor input BX3 no function.

Action: Sensor not Parameterised.

Wessex ModuMax mk3333

Cause: Sensor input BX4 no function.

Action: Sensor not Parameterised.

Wessex ModuMax mk3335

Cause: Sensor input BX21 no function.

Action: Sensor not Parameterised.

Wessex ModuMax mk3336

Cause: Sensor input BX22 no function.

Action: Sensor not Parameterised.

Wessex ModuMax mk3337

Cause: Sensor input B1 no function.

Action: Sensor not Parameterised.

Wessex ModuMax mk3338

Cause: Sensor input B12 no function.

Action: Sensor not Parameterised.

Wessex ModuMax mk3353

Cause: Cascade flow sensor B10 missing.

Action: Sensor not Parameterised.

Wessex ModuMax mk3372

Cause: Limit thermostat HC3.

Action: Allow the boiler to cool and reset thermostat

Wessex ModuMax mk3385

Cause: Mains undervoltage.

Action: Check incoming voltage.

Wessex ModuMax mk3386

Cause: Fan speed tolerance.

Action: Check fan connection

Wessex ModuMax mk3387

Cause: Air pressure tolerance.

Action: Check air pressure switch

Wessex ModuMax mk3388

Cause: DHW sensor no function.

Action: Sensor not parameterised .

Wessex ModuMax mk3429

Cause: Dyn water pressure too high.

Action: Check water pressure.

Wessex ModuMax mk3430

Cause: Dyn water pressure too low.

Action: Check water pressure.

Wessex ModuMax mk3432

Cause: Function ground missing.

Action: Check earth connection.

Wessex ModuMax mk3433

Cause: Heat exchanger temperature.

Action: Allow the boiler to cool and reset thermostat

Modumax mk410

Cause: Outside temperature sensor error

Action: Check connection, check sensor, check cable

Modumax mk420

Cause: Boiler temperature 1 sensor error

Action: Check connection, check sensor, check cable

Modumax mk425

Cause: Boiler temperature solid fuel sensor error

Action: Check connection, check sensor, check cable

Modumax mk426

Cause: Common flow temprerature sensor error

Action: Check connection, check sensor, check cable

Modumax mk428

Cause: Flue gas temperature sensor fault.

Action: Check connection, check sensor, check cable

Modumax mk430

Cause: Flow temperature 1 sensor error

Action: Check connection, check sensor, check cable

Modumax mk431

Cause: Flow temperature 1 cooling sensor error

Action: Check connection, check sensor, check cable

Modumax mk432

Cause: Flow temperature 2 sensor error

Action: Check connection, check sensor, check cable

Modumax mk438

Cause: Flow temperature primary controller

Action: Check connection, check sensor, check cable

Modumax mk440

Cause: Return temperature 1 sensor error

Action: Check connection, check sensor, check cable

Modumax mk446

Cause: Cascade return tremperature sensor error

Action: Check connection, check sensor, check cable

Modumax mk447

Cause: Common return termperature sensor error

Action: Check connection, check sensor, check cable

Modumax mk450

Cause: DHW temperature sensor/thermostat 1 fault.

Action: Check connection, check sensor, check cable

Modumax mk452

Cause: DHW temperature sensor/thermostat 2 fault.

Action: Check connection, check sensor, check cable

Modumax mk454

Cause: Flow temperature DHW

Action: Check connection, check sensor, check cable

Modumax mk457

Cause: DHW

Action: Check connection, check sensor, check cable

Modumax mk460

Cause: Room temperature 1, sensor error

Action: Check connection, check sensor, check cable

Modumax mk461

Cause: Fault room unit 1.

Action: Check room device.

Modumax mk465

Cause: Room temperature 2

Action: Check connection, check sensor, check cable

Modumax mk468

Cause: Room temperature 3

Action: Check connection, check sensor, check cable

Modumax mk470

Cause: Storage tank temperature 1 (top)

Action: Check connection, check sensor, check cable

Modumax mk471

Cause: Storage tank temperature 2 (bottom)

Action: Check connection, check sensor, check cable

Modumax mk472

Cause: Storage tank temrperature 3 (middle)

Action: Check connection, check sensor, check cable

Modumax mk473

Cause: Collector temperature 1

Action: Check connection, check sensor, check cable

Modumax mk474

Cause: Collector temperature 2 sensor error.

Action: Check connection, check sensor, check cable

Modumax mk478

Cause: Water pressure

Action: Check connection, check sensor, check cable

Modumax mk481

Cause: LPB short-circuit or no bus power supply.

Action: Check wiring, check polarity

Modumax mk482

Cause: LPB address collision.

Action: Check connection, check address

Modumax mk483

Cause: BSB-Wire short-circuit or no communication.

Action: Check wiring, check polarity

Modumax mk484

Cause: BSB wire address collision.

Action: Check wiring, check polarity

Modumax mk485

Cause: BSB radio communication fault.

Action: Connect compatible room control unit. Check wireless communication.

Modumax mk491

Cause: Data overrun in EEPROM.

Action: Contact Hamworthy Heating.

Modumax mk498

Cause: Mixing valve clip in 1 fault.

Action: Check wiring, check polarity

Modumax mk499

Cause: Mixing valve clip in 2 fault.

Action: Check wiring, check polarity

Modumax mk4100

Cause: Two clock time masters.

Action: Check parameter setting.

Modumax mk4102

Cause: Clock time master without power reserve.

Action: Check wiring, check polarity

Modumax mk4105

Cause: Maintenance message.

Action: Reset in parameters.

Modumax mk4109

Cause: Supervision boiler temperature.

Action: Allow the boiler to cool, investigate cause of overheating.

Modumax mk4110

Cause: SLT lockout.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Modumax mk4111

Cause: Temperature limiter safety shutdown.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Modumax mk4113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Modumax mk4117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor.

Modumax mk4118

Cause: Water pressure too low 6.

Action: Check system pressure, check water pressure sensor.

Modumax mk4119

Cause: Water pressure switch has cut out 6.

Action: Check water pressure.

Modumax mk4125

Cause: Maximum boiler temperature exceeded.

Action: Check water flow rate, check pumps, check controls.

Modumax mk4128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Modumax mk4130

Cause: Flue gas temperature limit exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Modumax mk4132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Modumax mk4133

Cause: Safety time for establishment of flame exceeded.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Modumax mk4146

Cause: Sensor/actuator configuration error.

Action: Check parameter setting.

Modumax mk4151

Cause: BMU fault internal.

Action: Check connections to clip in, replace module, check LMS.

Modumax mk4152

Cause: Parameterization error.

Action: Check parameters.

Modumax mk4153

Cause: Unit manually locked.

Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults).

Modumax mk4160

Cause: Fan speed threshold not reached.

Action: Check fan connection, replace fan

Modumax mk4162

Cause: Air pressure switch does not close.

Action: Check air pressure switch cable and connections

Modumax mk4164

Cause: Flow/pressure switch heating circuit error

Action: Check flow pressure switch and cable and connections.

Modumax mk4166

Cause: Air pressure switch error does not open

Action: Check air pressure switch and cable and connections.

Modumax mk4170

Cause: Water pressure primary.

Action: Check flow pressure switch cable and connections.

Modumax mk4176

Cause: Water pressure 2 too high.

Action: Check system pressure.

Modumax mk4177

Cause: Water pressure 2 too low.

Action: Check system pressure.

Modumax mk4178

Cause: Limit thermostat HC1.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Modumax mk4179

Cause: Limit thermostat HC2.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Modumax mk4183

Cause: Unit in parameterization mode.

Action: Escape back to main screen.

Modumax mk4193

Cause: Start prevention.

Action: Check external controls.

Modumax mk4217

Cause: Sensor error.

Action: Check connection, check sensor, check cable

Modumax mk4320

Cause: DHW charging temp sensor fault.

Action: Check connection, check sensor, check cable

Modumax mk4321

Cause: DHW outlet sensor fault.

Action: Check connection, check sensor, check cable

Modumax mk4322

Cause: Water pressure 3 too high.

Action: Check system pressure.

Modumax mk4323

Cause: Water pressure 3 too low.

Action: Check system pressure.

Modumax mk4324

Cause: Same sensor Input BX.

Action: Check parameters.

Modumax mk4325

Cause: Same sensor Input BX/extension module.

Action: Check parameters.

Modumax mk4326

Cause: Same sensor Input BX/mixing valve group.

Action: Check parameters.

Modumax mk4327

Cause: Same function mixing valve group.

Action: Check parameters.

Modumax mk4328

Cause: Same function mixing valve group.

Action: Check parameters.

Modumax mk4329

Cause: Same funct ext module/mixing valve group.

Action: Check parameters.

Modumax mk4330

Cause: Sensor input BX1 no function.

Action: Sensor not Parameterised.

Modumax mk4331

Cause: Sensor input BX2 no function.

Action: Sensor not Parameterised.

Modumax mk4332

Cause: Sensor input BX3 no function.

Action: Sensor not Parameterised.

Modumax mk4333

Cause: Sensor input BX4 no function.

Action: Sensor not Parameterised.

Modumax mk4335

Cause: Sensor input BX21 no function.

Action: Sensor not Parameterised.

Modumax mk4336

Cause: Sensor input BX22 no function.

Action: Sensor not Parameterised.

Modumax mk4337

Cause: Sensor input B1 no function.

Action: Sensor not Parameterised.

Modumax mk4338

Cause: Sensor input B12 no function.

Action: Sensor not Parameterised.

Modumax mk4353

Cause: Cascade flow sensor B10 missing.

Action: Sensor not Parameterised.

Modumax mk4372

Cause: Limit thermostat HC3.

Action: Allow the boiler to cool and reset thermostat

Modumax mk4385

Cause: Mains undervoltage.

Action: Check incoming voltage.

Modumax mk4386

Cause: Fan speed tolerance.

Action: Check fan connection

Modumax mk4387

Cause: Air pressure tolerance.

Action: Check air pressure switch

Modumax mk4388

Cause: DHW sensor no function.

Action: Sensor not parameterised .

Modumax mk4429

Cause: Dyn water pressure too high.

Action: Check water pressure.

Modumax mk4430

Cause: Dyn water pressure too low.

Action: Check water pressure.

Modumax mk4432

Cause: Function ground missing.

Action: Check earth connection.

Modumax mk4433

Cause: Heat exchanger temperature.

Action: Allow the boiler to cool and reset thermostat

Purewell VariHeat c10

Cause: Fault outside sensor.

Action: Check connection, check sensor, check cable.

Purewell VariHeat c28

Cause: Fault flue gas sensor.

Action: Check connection, check sensor, check cable.

Purewell VariHeat c32

Cause: Fault flow temperature sensor 2.

Action: Check connection, check sensor, check cable.

Purewell VariHeat c50

Cause: Fault DHW temperature sensor 1.

Action: Check connection, check sensor, check cable.

Purewell VariHeat c52

Cause: Fault DHW temperature sensor 2.

Action: Check connection, check sensor, check cable.

Purewell VariHeat c61

Cause: Fault room unit 1.

Action: Check room device.

Purewell VariHeat c62

Cause: Wrong room unit 1 or wrong radio clock connected.

Action: Connect compatible room control unit.

Purewell VariHeat c77

Cause: Fault air pressure sensor.

Action: Check connection, check sensor, check cable.

Purewell VariHeat c78

Cause: Fault water pressure sensor.

Action: Check connection, check sensor, check cable.

Purewell VariHeat c82

Cause: Address collision on LPB.

Action: Check addresses of connected modules.

Purewell VariHeat c91

Cause: Data overflow in EEPROM.

Action: Hardware fault, LMU may need replacing.

Purewell VariHeat c92

Cause: Hardware fault in electronics.

Action: Hardware fault, LMU may need replacing.

Purewell VariHeat c95

Cause: Invalid time of day.

Action: Set correct time.

Purewell VariHeat c100

Cause: 2 clock time masters.

Action: Check settings of LMU, only 1 master allowed.

Purewell VariHeat c105

Cause: Maintenance message.

Action: P629 to reset : change from 0 to 1.

Purewell VariHeat c110

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Purewell VariHeat c111

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Purewell VariHeat c113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Purewell VariHeat c117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor

Purewell VariHeat c118

Cause: Water pressure too low.

Action: Check system pressure, check water pressure sensor

Purewell VariHeat c119

Cause: Water pressure switch has cut out.

Action: Check water pressure.

Purewell VariHeat c128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Purewell VariHeat c129

Cause: Fan speed maximum/minimum has been violated.

Action: Check fan.

Purewell VariHeat c130

Cause: Flue gas limit temperature exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Purewell VariHeat c132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Purewell VariHeat c133

Cause: No flame on completion of safety time.

Action: Check operation of gas valve. Check spark igniter.

Purewell VariHeat c134

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Purewell VariHeat c140

Cause: Inadmissible LPB segment number/device N°.

Action: Check settings of LMU and boiler address settings.

Purewell VariHeat c148

Cause: Incompatibility LPB... interface / basic unit.

Action: Check settings of LMU

Purewell VariHeat c151

Cause: Internal fault with LMU.

Action: Check connections to clip in, replace module, check LMU.

Purewell VariHeat c152

Cause: Fault in connection with LMU settings.

Action: Check LMU settings.

Purewell VariHeat c153

Cause: LMU has locked out.

Action: Press reset button (code appears if reset button is pressed when there are no faults).

Purewell VariHeat c154

Cause: Flow Problems.

Action: Check water flow through the boiler & check the pumps.

Purewell VariHeat c160

Cause: Fan speed threshold not reached.

Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris.

Purewell VariHeat c161

Cause: Maximum fan speed exceeded.

Action: Check parameters.

Purewell VariHeat c162

Cause: Fault air pressure switch (does not close).

Action: Check air pressure switch and cable and connections.

Purewell VariHeat c164

Cause: Fault heating circuit flow switch / pressure switch.

Action: Check air pressure switch and cable and connections.

Purewell VariHeat c166

Cause: Fault air pressure switch (does not open).

Action: Check air pressure switch and cable and connections.

Purewell VariHeat c180

Cause: Chimney sweep function active.

Action: Check boiler operation setting.

Purewell VariHeat c181

Cause: Controller stop function active.

Action: Check boiler operation setting.

Purewell VariHeat c183

Cause: LMU in parameter setting mode.

Action: Unit in programme mode.

Purewell VariHeat he10

Cause: Fault outside sensor.

Action: Check connection, check sensor, check cable.

Purewell VariHeat he28

Cause: Fault flue gas sensor.

Action: Check connection, check sensor, check cable.

Purewell VariHeat he32

Cause: Fault flow temperature sensor 2.

Action: Check connection, check sensor, check cable.

Purewell VariHeat he50

Cause: Fault DHW temperature sensor 1.

Action: Check connection, check sensor, check cable.

Purewell VariHeat he52

Cause: Fault DHW temperature sensor 2.

Action: Check connection, check sensor, check cable.

Purewell VariHeat he61

Cause: Fault room unit 1.

Action: Check room device.

Purewell VariHeat he62

Cause: Wrong room unit 1 or wrong radio clock connected.

Action: Connect compatible room control unit.

Purewell VariHeat he77

Cause: Fault air pressure sensor.

Action: Check connection, check sensor, check cable.

Purewell VariHeat he78

Cause: Fault water pressure sensor.

Action: Check connection, check sensor, check cable.

Purewell VariHeat he82

Cause: Address collision on LPB.

Action: Check addresses of connected modules.

Purewell VariHeat he91

Cause: Data overflow in EEPROM.

Action: Hardware fault, LMU may need replacing.

Purewell VariHeat he92

Cause: Hardware fault in electronics.

Action: Hardware fault, LMU may need replacing.

Purewell VariHeat he95

Cause: Invalid time of day.

Action: Set correct time.

Purewell VariHeat he100

Cause: 2 clock time masters.

Action: Check settings of LMU, only 1 master allowed.

Purewell VariHeat he105

Cause: Maintenance message.

Action: P629 to reset : change from 0 to 1.

Purewell VariHeat he110

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Purewell VariHeat he111

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Purewell VariHeat he113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Purewell VariHeat he117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor

Purewell VariHeat he118

Cause: Water pressure too low.

Action: Check system pressure, check water pressure sensor

Purewell VariHeat he119

Cause: Water pressure switch has cut out.

Action: Check water pressure.

Purewell VariHeat he128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Purewell VariHeat he129

Cause: Fan speed maximum/minimum has been violated.

Action: Check fan.

Purewell VariHeat he130

Cause: Flue gas limit temperature exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Purewell VariHeat he132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Purewell VariHeat he133

Cause: No flame on completion of safety time.

Action: Check operation of gas valve. Check spark igniter.

Purewell VariHeat he134

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Purewell VariHeat he140

Cause: Inadmissible LPB segment number/device N°.

Action: Check settings of LMU and boiler address settings.

Purewell VariHeat he148

Cause: Incompatibility LPB... interface / basic unit.

Action: Check settings of LMU

Purewell VariHeat he151

Cause: Internal fault with LMU.

Action: Check connections to clip in, replace module, check LMU.

Purewell VariHeat he152

Cause: Fault in connection with LMU settings.

Action: Check LMU settings.

Purewell VariHeat he153

Cause: LMU has locked out.

Action: Press reset button (code appears if reset button is pressed when there are no faults).

Purewell VariHeat he154

Cause: Flow Problems.

Action: Check water flow through the boiler & check the pumps.

Purewell VariHeat he160

Cause: Fan speed threshold not reached.

Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris.

Purewell VariHeat he161

Cause: Maximum fan speed exceeded.

Action: Check parameters.

Purewell VariHeat he162

Cause: Fault air pressure switch (does not close).

Action: Check air pressure switch and cable and connections.

Purewell VariHeat he164

Cause: Fault heating circuit flow switch / pressure switch.

Action: Check air pressure switch and cable and connections.

Purewell VariHeat he166

Cause: Fault air pressure switch (does not open).

Action: Check air pressure switch and cable and connections.

Purewell VariHeat he180

Cause: Chimney sweep function active.

Action: Check boiler operation setting.

Purewell VariHeat he181

Cause: Controller stop function active.

Action: Check boiler operation setting.

Purewell VariHeat he183

Cause: LMU in parameter setting mode.

Action: Unit in programme mode.

Purewell VariHeat mk210

Cause: Outside temperature sensor error

Action: Check connection, check sensor, check cable

Purewell VariHeat mk220

Cause: Boiler temperature 1 sensor error

Action: Check connection, check sensor, check cable

Purewell VariHeat mk225

Cause: Boiler temperature solid fuel sensor error

Action: Check connection, check sensor, check cable

Purewell VariHeat mk226

Cause: Common flow temprerature sensor error

Action: Check connection, check sensor, check cable

Purewell VariHeat mk228

Cause: Flue gas temperature sensor fault.

Action: Check connection, check sensor, check cable

Purewell VariHeat mk230

Cause: Flow temperature 1 sensor error

Action: Check connection, check sensor, check cable

Purewell VariHeat mk231

Cause: Flow temperature 1 cooling sensor error

Action: Check connection, check sensor, check cable

Purewell VariHeat mk232

Cause: Flow temperature 2 sensor error

Action: Check connection, check sensor, check cable

Purewell VariHeat mk238

Cause: Flow temperature primary controller

Action: Check connection, check sensor, check cable

Purewell VariHeat mk240

Cause: Return temperature 1 sensor error

Action: Check connection, check sensor, check cable

Purewell VariHeat mk246

Cause: Cascade return tremperature sensor error

Action: Check connection, check sensor, check cable

Purewell VariHeat mk247

Cause: Common return termperature sensor error

Action: Check connection, check sensor, check cable

Purewell VariHeat mk250

Cause: DHW temperature sensor/thermostat 1 fault.

Action: Check connection, check sensor, check cable

Purewell VariHeat mk252

Cause: DHW temperature sensor/thermostat 2 fault.

Action: Check connection, check sensor, check cable

Purewell VariHeat mk254

Cause: Flow temperature DHW

Action: Check connection, check sensor, check cable

Purewell VariHeat mk257

Cause: DHW

Action: Check connection, check sensor, check cable

Purewell VariHeat mk260

Cause: Room temperature 1, sensor error

Action: Check connection, check sensor, check cable

Purewell VariHeat mk261

Cause: Fault room unit 1.

Action: Check room device.

Purewell VariHeat mk265

Cause: Room temperature 2

Action: Check connection, check sensor, check cable

Purewell VariHeat mk268

Cause: Room temperature 3

Action: Check connection, check sensor, check cable

Purewell VariHeat mk270

Cause: Storage tank temperature 1 (top)

Action: Check connection, check sensor, check cable

Purewell VariHeat mk271

Cause: Storage tank temperature 2 (bottom)

Action: Check connection, check sensor, check cable

Purewell VariHeat mk272

Cause: Storage tank temrperature 3 (middle)

Action: Check connection, check sensor, check cable

Purewell VariHeat mk273

Cause: Collector temperature 1

Action: Check connection, check sensor, check cable

Purewell VariHeat mk274

Cause: Collector temperature 2 sensor error.

Action: Check connection, check sensor, check cable

Purewell VariHeat mk278

Cause: Water pressure

Action: Check connection, check sensor, check cable

Purewell VariHeat mk281

Cause: LPB short-circuit or no bus power supply.

Action: Check wiring, check polarity

Purewell VariHeat mk282

Cause: LPB address collision.

Action: Check connection, check address

Purewell VariHeat mk283

Cause: BSB-Wire short-circuit or no communication.

Action: Check wiring, check polarity

Purewell VariHeat mk284

Cause: BSB wire address collision.

Action: Check wiring, check polarity

Purewell VariHeat mk285

Cause: BSB radio communication fault.

Action: Connect compatible room control unit. Check wireless communication.

Purewell VariHeat mk291

Cause: Data overrun in EEPROM.

Action: Contact Hamworthy Heating.

Purewell VariHeat mk298

Cause: Mixing valve clip in 1 fault.

Action: Check wiring, check polarity

Purewell VariHeat mk299

Cause: Mixing valve clip in 2 fault.

Action: Check wiring, check polarity

Purewell VariHeat mk2100

Cause: Two clock time masters.

Action: Check parameter setting.

Purewell VariHeat mk2102

Cause: Clock time master without power reserve.

Action: Check wiring, check polarity

Purewell VariHeat mk2105

Cause: Maintenance message.

Action: Reset in parameters.

Purewell VariHeat mk2109

Cause: Supervision boiler temperature.

Action: Allow the boiler to cool, investigate cause of overheating.

Purewell VariHeat mk2110

Cause: SLT lockout.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Purewell VariHeat mk2111

Cause: Temperature limiter safety shutdown.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Purewell VariHeat mk2113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Purewell VariHeat mk2117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor.

Purewell VariHeat mk2118

Cause: Water pressure too low 6.

Action: Check system pressure, check water pressure sensor.

Purewell VariHeat mk2119

Cause: Water pressure switch has cut out 6.

Action: Check water pressure.

Purewell VariHeat mk2125

Cause: Maximum boiler temperature exceeded.

Action: Check water flow rate, check pumps, check controls.

Purewell VariHeat mk2128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Purewell VariHeat mk2130

Cause: Flue gas temperature limit exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Purewell VariHeat mk2132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Purewell VariHeat mk2133

Cause: Safety time for establishment of flame exceeded.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Purewell VariHeat mk2146

Cause: Sensor/actuator configuration error.

Action: Check parameter setting.

Purewell VariHeat mk2151

Cause: BMU fault internal.

Action: Check connections to clip in, replace module, check LMS.

Purewell VariHeat mk2152

Cause: Parameterization error.

Action: Check parameters.

Purewell VariHeat mk2153

Cause: Unit manually locked.

Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults).

Purewell VariHeat mk2160

Cause: Fan speed threshold not reached.

Action: Check fan connection, replace fan

Purewell VariHeat mk2162

Cause: Air pressure switch does not close.

Action: Check air pressure switch cable and connections

Purewell VariHeat mk2164

Cause: Flow/pressure switch heating circuit error

Action: Check flow pressure switch and cable and connections.

Purewell VariHeat mk2166

Cause: Air pressure switch error does not open

Action: Check air pressure switch and cable and connections.

Purewell VariHeat mk2170

Cause: Water pressure primary.

Action: Check flow pressure switch cable and connections.

Purewell VariHeat mk2176

Cause: Water pressure 2 too high.

Action: Check system pressure.

Purewell VariHeat mk2177

Cause: Water pressure 2 too low.

Action: Check system pressure.

Purewell VariHeat mk2178

Cause: Limit thermostat HC1.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Purewell VariHeat mk2179

Cause: Limit thermostat HC2.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Purewell VariHeat mk2183

Cause: Unit in parameterization mode.

Action: Escape back to main screen.

Purewell VariHeat mk2193

Cause: Start prevention.

Action: Check external controls.

Purewell VariHeat mk2217

Cause: Sensor error.

Action: Check connection, check sensor, check cable

Purewell VariHeat mk2320

Cause: DHW charging temp sensor fault.

Action: Check connection, check sensor, check cable

Purewell VariHeat mk2321

Cause: DHW outlet sensor fault.

Action: Check connection, check sensor, check cable

Purewell VariHeat mk2322

Cause: Water pressure 3 too high.

Action: Check system pressure.

Purewell VariHeat mk2323

Cause: Water pressure 3 too low.

Action: Check system pressure.

Purewell VariHeat mk2324

Cause: Same sensor Input BX.

Action: Check parameters.

Purewell VariHeat mk2325

Cause: Same sensor Input BX/extension module.

Action: Check parameters.

Purewell VariHeat mk2326

Cause: Same sensor Input BX/mixing valve group.

Action: Check parameters.

Purewell VariHeat mk2327

Cause: Same function mixing valve group.

Action: Check parameters.

Purewell VariHeat mk2328

Cause: Same function mixing valve group.

Action: Check parameters.

Purewell VariHeat mk2329

Cause: Same funct ext module/mixing valve group.

Action: Check parameters.

Purewell VariHeat mk2330

Cause: Sensor input BX1 no function.

Action: Sensor not Parameterised.

Purewell VariHeat mk2331

Cause: Sensor input BX2 no function.

Action: Sensor not Parameterised.

Purewell VariHeat mk2332

Cause: Sensor input BX3 no function.

Action: Sensor not Parameterised.

Purewell VariHeat mk2333

Cause: Sensor input BX4 no function.

Action: Sensor not Parameterised.

Purewell VariHeat mk2335

Cause: Sensor input BX21 no function.

Action: Sensor not Parameterised.

Purewell VariHeat mk2336

Cause: Sensor input BX22 no function.

Action: Sensor not Parameterised.

Purewell VariHeat mk2337

Cause: Sensor input B1 no function.

Action: Sensor not Parameterised.

Purewell VariHeat mk2338

Cause: Sensor input B12 no function.

Action: Sensor not Parameterised.

Purewell VariHeat mk2353

Cause: Cascade flow sensor B10 missing.

Action: Sensor not Parameterised.

Purewell VariHeat mk2372

Cause: Limit thermostat HC3.

Action: Allow the boiler to cool and reset thermostat

Purewell VariHeat mk2385

Cause: Mains undervoltage.

Action: Check incoming voltage.

Purewell VariHeat mk2386

Cause: Fan speed tolerance.

Action: Check fan connection

Purewell VariHeat mk2387

Cause: Air pressure tolerance.

Action: Check air pressure switch

Purewell VariHeat mk2388

Cause: DHW sensor no function.

Action: Sensor not parameterised .

Purewell VariHeat mk2429

Cause: Dyn water pressure too high.

Action: Check water pressure.

Purewell VariHeat mk2430

Cause: Dyn water pressure too low.

Action: Check water pressure.

Purewell VariHeat mk2432

Cause: Function ground missing.

Action: Check earth connection.

Purewell VariHeat mk2433

Cause: Heat exchanger temperature.

Action: Allow the boiler to cool and reset thermostat

Stratton10

Cause: Fault outside sensor.

Action: Check connection, check sensor, check cable.

Stratton28

Cause: Fault flue gas sensor.

Action: Check connection, check sensor, check cable.

Stratton32

Cause: Fault flow temperature sensor 2.

Action: Check connection, check sensor, check cable.

Stratton50

Cause: Fault DHW temperature sensor 1.

Action: Check connection, check sensor, check cable.

Stratton52

Cause: Fault DHW temperature sensor 2.

Action: Check connection, check sensor, check cable.

Stratton61

Cause: Fault room unit 1.

Action: Check room device.

Stratton62

Cause: Wrong room unit 1 or wrong radio clock connected.

Action: Connect compatible room control unit.

Stratton77

Cause: Fault air pressure sensor.

Action: Check connection, check sensor, check cable.

Stratton78

Cause: Fault water pressure sensor.

Action: Check connection, check sensor, check cable.

Stratton82

Cause: Address collision on LPB.

Action: Check addresses of connected modules.

Stratton91

Cause: Data overflow in EEPROM.

Action: Hardware fault, LMU may need replacing.

Stratton92

Cause: Hardware fault in electronics.

Action: Hardware fault, LMU may need replacing.

Stratton95

Cause: Invalid time of day.

Action: Set correct time.

Stratton100

Cause: 2 clock time masters.

Action: Check settings of LMU, only 1 master allowed.

Stratton105

Cause: Maintenance message.

Action: P629 to reset : change from 0 to 1.

Stratton110

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Stratton111

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Stratton113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Stratton117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor

Stratton118

Cause: Water pressure too low.

Action: Check system pressure, check water pressure sensor

Stratton119

Cause: Water pressure switch has cut out.

Action: Check water pressure.

Stratton128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Stratton129

Cause: Fan speed maximum/minimum has been violated.

Action: Check fan.

Stratton130

Cause: Flue gas limit temperature exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Stratton132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Stratton133

Cause: No flame on completion of safety time.

Action: Check operation of gas valve. Check spark igniter.

Stratton134

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Stratton140

Cause: Inadmissible LPB segment number/device N°.

Action: Check settings of LMU and boiler address settings.

Stratton148

Cause: Incompatibility LPB... interface / basic unit.

Action: Check settings of LMU

Stratton151

Cause: Internal fault with LMU.

Action: Check connections to clip in, replace module, check LMU.

Stratton152

Cause: Fault in connection with LMU settings.

Action: Check LMU settings.

Stratton153

Cause: LMU has locked out.

Action: Press reset button (code appears if reset button is pressed when there are no faults).

Stratton154

Cause: Flow Problems.

Action: Check water flow through the boiler & check the pumps.

Stratton160

Cause: Fan speed threshold not reached.

Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris.

Stratton161

Cause: Maximum fan speed exceeded.

Action: Check parameters.

Stratton162

Cause: Fault air pressure switch (does not close).

Action: Check air pressure switch and cable and connections.

Stratton164

Cause: Fault heating circuit flow switch / pressure switch.

Action: Check air pressure switch and cable and connections.

Stratton166

Cause: Fault air pressure switch (does not open).

Action: Check air pressure switch and cable and connections.

Stratton180

Cause: Chimney sweep function active.

Action: Check boiler operation setting.

Stratton181

Cause: Controller stop function active.

Action: Check boiler operation setting.

Stratton183

Cause: LMU in parameter setting mode.

Action: Unit in programme mode.

Stratton mk210

Cause: Outside temperature sensor error

Action: Check connection, check sensor, check cable

Stratton mk220

Cause: Boiler temperature 1 sensor error

Action: Check connection, check sensor, check cable

Stratton mk225

Cause: Boiler temperature solid fuel sensor error

Action: Check connection, check sensor, check cable

Stratton mk226

Cause: Common flow temprerature sensor error

Action: Check connection, check sensor, check cable

Stratton mk228

Cause: Flue gas temperature sensor fault.

Action: Check connection, check sensor, check cable

Stratton mk230

Cause: Flow temperature 1 sensor error

Action: Check connection, check sensor, check cable

Stratton mk231

Cause: Flow temperature 1 cooling sensor error

Action: Check connection, check sensor, check cable

Stratton mk232

Cause: Flow temperature 2 sensor error

Action: Check connection, check sensor, check cable

Stratton mk238

Cause: Flow temperature primary controller

Action: Check connection, check sensor, check cable

Stratton mk240

Cause: Return temperature 1 sensor error

Action: Check connection, check sensor, check cable

Stratton mk246

Cause: Cascade return tremperature sensor error

Action: Check connection, check sensor, check cable

Stratton mk247

Cause: Common return termperature sensor error

Action: Check connection, check sensor, check cable

Stratton mk250

Cause: DHW temperature sensor/thermostat 1 fault.

Action: Check connection, check sensor, check cable

Stratton mk252

Cause: DHW temperature sensor/thermostat 2 fault.

Action: Check connection, check sensor, check cable

Stratton mk254

Cause: Flow temperature DHW

Action: Check connection, check sensor, check cable

Stratton mk257

Cause: DHW

Action: Check connection, check sensor, check cable

Stratton mk260

Cause: Room temperature 1, sensor error

Action: Check connection, check sensor, check cable

Stratton mk261

Cause: Fault room unit 1.

Action: Check room device.

Stratton mk265

Cause: Room temperature 2

Action: Check connection, check sensor, check cable

Stratton mk268

Cause: Room temperature 3

Action: Check connection, check sensor, check cable

Stratton mk270

Cause: Storage tank temperature 1 (top)

Action: Check connection, check sensor, check cable

Stratton mk271

Cause: Storage tank temperature 2 (bottom)

Action: Check connection, check sensor, check cable

Stratton mk272

Cause: Storage tank temrperature 3 (middle)

Action: Check connection, check sensor, check cable

Stratton mk273

Cause: Collector temperature 1

Action: Check connection, check sensor, check cable

Stratton mk274

Cause: Collector temperature 2 sensor error.

Action: Check connection, check sensor, check cable

Stratton mk278

Cause: Water pressure

Action: Check connection, check sensor, check cable

Stratton mk281

Cause: LPB short-circuit or no bus power supply.

Action: Check wiring, check polarity

Stratton mk282

Cause: LPB address collision.

Action: Check connection, check address

Stratton mk283

Cause: BSB-Wire short-circuit or no communication.

Action: Check wiring, check polarity

Stratton mk284

Cause: BSB wire address collision.

Action: Check wiring, check polarity

Stratton mk285

Cause: BSB radio communication fault.

Action: Connect compatible room control unit. Check wireless communication.

Stratton mk291

Cause: Data overrun in EEPROM.

Action: Contact Hamworthy Heating.

Stratton mk298

Cause: Mixing valve clip in 1 fault.

Action: Check wiring, check polarity

Stratton mk299

Cause: Mixing valve clip in 2 fault.

Action: Check wiring, check polarity

Stratton mk2100

Cause: Two clock time masters.

Action: Check parameter setting.

Stratton mk2102

Cause: Clock time master without power reserve.

Action: Check wiring, check polarity

Stratton mk2105

Cause: Maintenance message.

Action: Reset in parameters.

Stratton mk2109

Cause: Supervision boiler temperature.

Action: Allow the boiler to cool, investigate cause of overheating.

Stratton mk2110

Cause: SLT lockout.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Stratton mk2111

Cause: Temperature limiter safety shutdown.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Stratton mk2113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Stratton mk2117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor.

Stratton mk2118

Cause: Water pressure too low 6.

Action: Check system pressure, check water pressure sensor.

Stratton mk2119

Cause: Water pressure switch has cut out 6.

Action: Check water pressure.

Stratton mk2125

Cause: Maximum boiler temperature exceeded.

Action: Check water flow rate, check pumps, check controls.

Stratton mk2128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Stratton mk2130

Cause: Flue gas temperature limit exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Stratton mk2132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Stratton mk2133

Cause: Safety time for establishment of flame exceeded.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Stratton mk2146

Cause: Sensor/actuator configuration error.

Action: Check parameter setting.

Stratton mk2151

Cause: BMU fault internal.

Action: Check connections to clip in, replace module, check LMS.

Stratton mk2152

Cause: Parameterization error.

Action: Check parameters.

Stratton mk2153

Cause: Unit manually locked.

Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults).

Stratton mk2160

Cause: Fan speed threshold not reached.

Action: Check fan connection, replace fan

Stratton mk2162

Cause: Air pressure switch does not close.

Action: Check air pressure switch cable and connections

Stratton mk2164

Cause: Flow/pressure switch heating circuit error

Action: Check flow pressure switch and cable and connections.

Stratton mk2166

Cause: Air pressure switch error does not open

Action: Check air pressure switch and cable and connections.

Stratton mk2170

Cause: Water pressure primary.

Action: Check flow pressure switch cable and connections.

Stratton mk2176

Cause: Water pressure 2 too high.

Action: Check system pressure.

Stratton mk2177

Cause: Water pressure 2 too low.

Action: Check system pressure.

Stratton mk2178

Cause: Limit thermostat HC1.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Stratton mk2179

Cause: Limit thermostat HC2.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Stratton mk2183

Cause: Unit in parameterization mode.

Action: Escape back to main screen.

Stratton mk2193

Cause: Start prevention.

Action: Check external controls.

Stratton mk2217

Cause: Sensor error.

Action: Check connection, check sensor, check cable

Stratton mk2320

Cause: DHW charging temp sensor fault.

Action: Check connection, check sensor, check cable

Stratton mk2321

Cause: DHW outlet sensor fault.

Action: Check connection, check sensor, check cable

Stratton mk2322

Cause: Water pressure 3 too high.

Action: Check system pressure.

Stratton mk2323

Cause: Water pressure 3 too low.

Action: Check system pressure.

Stratton mk2324

Cause: Same sensor Input BX.

Action: Check parameters.

Stratton mk2325

Cause: Same sensor Input BX/extension module.

Action: Check parameters.

Stratton mk2326

Cause: Same sensor Input BX/mixing valve group.

Action: Check parameters.

Stratton mk2327

Cause: Same function mixing valve group.

Action: Check parameters.

Stratton mk2328

Cause: Same function mixing valve group.

Action: Check parameters.

Stratton mk2329

Cause: Same funct ext module/mixing valve group.

Action: Check parameters.

Stratton mk2330

Cause: Sensor input BX1 no function.

Action: Sensor not Parameterised.

Stratton mk2331

Cause: Sensor input BX2 no function.

Action: Sensor not Parameterised.

Stratton mk2332

Cause: Sensor input BX3 no function.

Action: Sensor not Parameterised.

Stratton mk2333

Cause: Sensor input BX4 no function.

Action: Sensor not Parameterised.

Stratton mk2335

Cause: Sensor input BX21 no function.

Action: Sensor not Parameterised.

Stratton mk2336

Cause: Sensor input BX22 no function.

Action: Sensor not Parameterised.

Stratton mk2337

Cause: Sensor input B1 no function.

Action: Sensor not Parameterised.

Stratton mk2338

Cause: Sensor input B12 no function.

Action: Sensor not Parameterised.

Stratton mk2353

Cause: Cascade flow sensor B10 missing.

Action: Sensor not Parameterised.

Stratton mk2372

Cause: Limit thermostat HC3.

Action: Allow the boiler to cool and reset thermostat

Stratton mk2385

Cause: Mains undervoltage.

Action: Check incoming voltage.

Stratton mk2386

Cause: Fan speed tolerance.

Action: Check fan connection

Stratton mk2387

Cause: Air pressure tolerance.

Action: Check air pressure switch

Stratton mk2388

Cause: DHW sensor no function.

Action: Sensor not parameterised .

Stratton mk2429

Cause: Dyn water pressure too high.

Action: Check water pressure.

Stratton mk2430

Cause: Dyn water pressure too low.

Action: Check water pressure.

Stratton mk2432

Cause: Function ground missing.

Action: Check earth connection.

Stratton mk2433

Cause: Heat exchanger temperature.

Action: Allow the boiler to cool and reset thermostat

Upton10

Cause: Outside temperature sensor error

Action: Check connection, check sensor, check cable

Upton20

Cause: Boiler temperature 1 sensor error

Action: Check connection, check sensor, check cable

Upton25

Cause: Boiler temperature solid fuel sensor error

Action: Check connection, check sensor, check cable

Upton26

Cause: Common flow temprerature sensor error

Action: Check connection, check sensor, check cable

Upton28

Cause: Flue gas temperature sensor fault.

Action: Check connection, check sensor, check cable

Upton30

Cause: Flow temperature 1 sensor error

Action: Check connection, check sensor, check cable

Upton31

Cause: Flow temperature 1 cooling sensor error

Action: Check connection, check sensor, check cable

Upton32

Cause: Flow temperature 2 sensor error

Action: Check connection, check sensor, check cable

Upton38

Cause: Flow temperature primary controller

Action: Check connection, check sensor, check cable

Upton40

Cause: Return temperature 1 sensor error

Action: Check connection, check sensor, check cable

Upton46

Cause: Cascade return tremperature sensor error

Action: Check connection, check sensor, check cable

Upton47

Cause: Common return termperature sensor error

Action: Check connection, check sensor, check cable

Upton50

Cause: DHW temperature sensor/thermostat 1 fault.

Action: Check connection, check sensor, check cable

Upton52

Cause: DHW temperature sensor/thermostat 2 fault.

Action: Check connection, check sensor, check cable

Upton54

Cause: Flow temperature DHW

Action: Check connection, check sensor, check cable

Upton57

Cause: DHW

Action: Check connection, check sensor, check cable

Upton60

Cause: Room temperature 1, sensor error

Action: Check connection, check sensor, check cable

Upton61

Cause: Fault room unit 1.

Action: Check room device.

Upton65

Cause: Room temperature 2

Action: Check connection, check sensor, check cable

Upton68

Cause: Room temperature 3

Action: Check connection, check sensor, check cable

Upton70

Cause: Storage tank temperature 1 (top)

Action: Check connection, check sensor, check cable

Upton71

Cause: Storage tank temperature 2 (bottom)

Action: Check connection, check sensor, check cable

Upton72

Cause: Storage tank temrperature 3 (middle)

Action: Check connection, check sensor, check cable

Upton73

Cause: Collector temperature 1

Action: Check connection, check sensor, check cable

Upton74

Cause: Collector temperature 2 sensor error.

Action: Check connection, check sensor, check cable

Upton78

Cause: Water pressure

Action: Check connection, check sensor, check cable

Upton81

Cause: LPB short-circuit or no bus power supply.

Action: Check wiring, check polarity

Upton82

Cause: LPB address collision.

Action: Check connection, check address

Upton83

Cause: BSB-Wire short-circuit or no communication.

Action: Check wiring, check polarity

Upton84

Cause: BSB wire address collision.

Action: Check wiring, check polarity

Upton85

Cause: BSB radio communication fault.

Action: Connect compatible room control unit. Check wireless communication.

Upton91

Cause: Data overrun in EEPROM.

Action: Contact Hamworthy Heating.

Upton98

Cause: Mixing valve clip in 1 fault.

Action: Check wiring, check polarity

Upton99

Cause: Mixing valve clip in 2 fault.

Action: Check wiring, check polarity

Upton100

Cause: Two clock time masters.

Action: Check parameter setting.

Upton102

Cause: Clock time master without power reserve.

Action: Check wiring, check polarity

Upton105

Cause: Maintenance message.

Action: Reset in parameters.

Upton109

Cause: Supervision boiler temperature.

Action: Allow the boiler to cool, investigate cause of overheating.

Upton110

Cause: SLT lockout.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Upton111

Cause: Temperature limiter safety shutdown.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Upton113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Upton117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor.

Upton118

Cause: Water pressure too low 6.

Action: Check system pressure, check water pressure sensor.

Upton119

Cause: Water pressure switch has cut out 6.

Action: Check water pressure.

Upton125

Cause: Maximum boiler temperature exceeded.

Action: Check water flow rate, check pumps, check controls.

Upton128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Upton130

Cause: Flue gas temperature limit exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Upton132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Upton133

Cause: Safety time for establishment of flame exceeded.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Upton146

Cause: Sensor/actuator configuration error.

Action: Check parameter setting.

Upton151

Cause: BMU fault internal.

Action: Check connections to clip in, replace module, check LMS.

Upton152

Cause: Parameterization error.

Action: Check parameters.

Upton153

Cause: Unit manually locked.

Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults).

Upton160

Cause: Fan speed threshold not reached.

Action: Check fan connection, replace fan

Upton162

Cause: Air pressure switch does not close.

Action: Check air pressure switch cable and connections

Upton164

Cause: Flow/pressure switch heating circuit error

Action: Check flow pressure switch and cable and connections.

Upton166

Cause: Air pressure switch error does not open

Action: Check air pressure switch and cable and connections.

Upton170

Cause: Water pressure primary.

Action: Check flow pressure switch cable and connections.

Upton176

Cause: Water pressure 2 too high.

Action: Check system pressure.

Upton177

Cause: Water pressure 2 too low.

Action: Check system pressure.

Upton178

Cause: Limit thermostat HC1.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Upton179

Cause: Limit thermostat HC2.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Upton183

Cause: Unit in parameterization mode.

Action: Escape back to main screen.

Upton193

Cause: Start prevention.

Action: Check external controls.

Upton217

Cause: Sensor error.

Action: Check connection, check sensor, check cable

Upton320

Cause: DHW charging temp sensor fault.

Action: Check connection, check sensor, check cable

Upton321

Cause: DHW outlet sensor fault.

Action: Check connection, check sensor, check cable

Upton322

Cause: Water pressure 3 too high.

Action: Check system pressure.

Upton323

Cause: Water pressure 3 too low.

Action: Check system pressure.

Upton324

Cause: Same sensor Input BX.

Action: Check parameters.

Upton325

Cause: Same sensor Input BX/extension module.

Action: Check parameters.

Upton326

Cause: Same sensor Input BX/mixing valve group.

Action: Check parameters.

Upton327

Cause: Same function mixing valve group.

Action: Check parameters.

Upton328

Cause: Same function mixing valve group.

Action: Check parameters.

Upton329

Cause: Same funct ext module/mixing valve group.

Action: Check parameters.

Upton330

Cause: Sensor input BX1 no function.

Action: Sensor not Parameterised.

Upton331

Cause: Sensor input BX2 no function.

Action: Sensor not Parameterised.

Upton332

Cause: Sensor input BX3 no function.

Action: Sensor not Parameterised.

Upton333

Cause: Sensor input BX4 no function.

Action: Sensor not Parameterised.

Upton335

Cause: Sensor input BX21 no function.

Action: Sensor not Parameterised.

Upton336

Cause: Sensor input BX22 no function.

Action: Sensor not Parameterised.

Upton337

Cause: Sensor input B1 no function.

Action: Sensor not Parameterised.

Upton338

Cause: Sensor input B12 no function.

Action: Sensor not Parameterised.

Upton353

Cause: Cascade flow sensor B10 missing.

Action: Sensor not Parameterised.

Upton372

Cause: Limit thermostat HC3.

Action: Allow the boiler to cool and reset thermostat

Upton385

Cause: Mains undervoltage.

Action: Check incoming voltage.

Upton386

Cause: Fan speed tolerance.

Action: Check fan connection

Upton387

Cause: Air pressure tolerance.

Action: Check air pressure switch

Upton388

Cause: DHW sensor no function.

Action: Sensor not parameterised .

Upton429

Cause: Dyn water pressure too high.

Action: Check water pressure.

Upton430

Cause: Dyn water pressure too low.

Action: Check water pressure.

Upton432

Cause: Function ground missing.

Action: Check earth connection.

Upton433

Cause: Heat exchanger temperature.

Action: Allow the boiler to cool and reset thermostat

Varmax10

Cause: Outside temperature sensor error

Action: Check connection, check sensor, check cable

Varmax20

Cause: Boiler temperature 1 sensor error

Action: Check connection, check sensor, check cable

Varmax25

Cause: Boiler temperature solid fuel sensor error

Action: Check connection, check sensor, check cable

Varmax26

Cause: Common flow temprerature sensor error

Action: Check connection, check sensor, check cable

Varmax28

Cause: Flue gas temperature sensor fault.

Action: Check connection, check sensor, check cable

Varmax30

Cause: Flow temperature 1 sensor error

Action: Check connection, check sensor, check cable

Varmax31

Cause: Flow temperature 1 cooling sensor error

Action: Check connection, check sensor, check cable

Varmax32

Cause: Flow temperature 2 sensor error

Action: Check connection, check sensor, check cable

Varmax38

Cause: Flow temperature primary controller

Action: Check connection, check sensor, check cable

Varmax40

Cause: Return temperature 1 sensor error

Action: Check connection, check sensor, check cable

Varmax46

Cause: Cascade return tremperature sensor error

Action: Check connection, check sensor, check cable

Varmax47

Cause: Common return termperature sensor error

Action: Check connection, check sensor, check cable

Varmax50

Cause: DHW temperature sensor/thermostat 1 fault.

Action: Check connection, check sensor, check cable

Varmax52

Cause: DHW temperature sensor/thermostat 2 fault.

Action: Check connection, check sensor, check cable

Varmax54

Cause: Flow temperature DHW

Action: Check connection, check sensor, check cable

Varmax57

Cause: DHW

Action: Check connection, check sensor, check cable

Varmax60

Cause: Room temperature 1, sensor error

Action: Check connection, check sensor, check cable

Varmax61

Cause: Fault room unit 1.

Action: Check room device.

Varmax65

Cause: Room temperature 2

Action: Check connection, check sensor, check cable

Varmax68

Cause: Room temperature 3

Action: Check connection, check sensor, check cable

Varmax70

Cause: Storage tank temperature 1 (top)

Action: Check connection, check sensor, check cable

Varmax71

Cause: Storage tank temperature 2 (bottom)

Action: Check connection, check sensor, check cable

Varmax72

Cause: Storage tank temrperature 3 (middle)

Action: Check connection, check sensor, check cable

Varmax73

Cause: Collector temperature 1

Action: Check connection, check sensor, check cable

Varmax74

Cause: Collector temperature 2 sensor error.

Action: Check connection, check sensor, check cable

Varmax78

Cause: Water pressure

Action: Check connection, check sensor, check cable

Varmax81

Cause: LPB short-circuit or no bus power supply.

Action: Check wiring, check polarity

Varmax82

Cause: LPB address collision.

Action: Check connection, check address

Varmax83

Cause: BSB-Wire short-circuit or no communication.

Action: Check wiring, check polarity

Varmax84

Cause: BSB wire address collision.

Action: Check wiring, check polarity

Varmax85

Cause: BSB radio communication fault.

Action: Connect compatible room control unit. Check wireless communication.

Varmax91

Cause: Data overrun in EEPROM.

Action: Contact Hamworthy Heating.

Varmax98

Cause: Mixing valve clip in 1 fault.

Action: Check wiring, check polarity

Varmax99

Cause: Mixing valve clip in 2 fault.

Action: Check wiring, check polarity

Varmax100

Cause: Two clock time masters.

Action: Check parameter setting.

Varmax102

Cause: Clock time master without power reserve.

Action: Check wiring, check polarity

Varmax105

Cause: Maintenance message.

Action: Reset in parameters.

Varmax109

Cause: Supervision boiler temperature.

Action: Allow the boiler to cool, investigate cause of overheating.

Varmax110

Cause: SLT lockout.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Varmax111

Cause: Temperature limiter safety shutdown.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Varmax113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Varmax117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor.

Varmax118

Cause: Water pressure too low 6.

Action: Check system pressure, check water pressure sensor.

Varmax119

Cause: Water pressure switch has cut out 6.

Action: Check water pressure.

Varmax125

Cause: Maximum boiler temperature exceeded.

Action: Check water flow rate, check pumps, check controls.

Varmax128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Varmax130

Cause: Flue gas temperature limit exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Varmax132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Varmax133

Cause: Safety time for establishment of flame exceeded.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Varmax146

Cause: Sensor/actuator configuration error.

Action: Check parameter setting.

Varmax151

Cause: BMU fault internal.

Action: Check connections to clip in, replace module, check LMS.

Varmax152

Cause: Parameterization error.

Action: Check parameters.

Varmax153

Cause: Unit manually locked.

Action: Reset button pressed to long (code appears if reset button is pressed when there are no faults).

Varmax160

Cause: Fan speed threshold not reached.

Action: Check fan connection, replace fan

Varmax162

Cause: Air pressure switch does not close.

Action: Check air pressure switch cable and connections

Varmax164

Cause: Flow/pressure switch heating circuit error

Action: Check flow pressure switch and cable and connections.

Varmax166

Cause: Air pressure switch error does not open

Action: Check air pressure switch and cable and connections.

Varmax170

Cause: Water pressure primary.

Action: Check flow pressure switch cable and connections.

Varmax176

Cause: Water pressure 2 too high.

Action: Check system pressure.

Varmax177

Cause: Water pressure 2 too low.

Action: Check system pressure.

Varmax178

Cause: Limit thermostat HC1.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Varmax179

Cause: Limit thermostat HC2.

Action: Allow the boiler to cool and reset thermostat. Investigate cause of overheating.

Varmax183

Cause: Unit in parameterization mode.

Action: Escape back to main screen.

Varmax193

Cause: Start prevention.

Action: Check external controls.

Varmax217

Cause: Sensor error.

Action: Check connection, check sensor, check cable

Varmax320

Cause: DHW charging temp sensor fault.

Action: Check connection, check sensor, check cable

Varmax321

Cause: DHW outlet sensor fault.

Action: Check connection, check sensor, check cable

Varmax322

Cause: Water pressure 3 too high.

Action: Check system pressure.

Varmax323

Cause: Water pressure 3 too low.

Action: Check system pressure.

Varmax324

Cause: Same sensor Input BX.

Action: Check parameters.

Varmax325

Cause: Same sensor Input BX/extension module.

Action: Check parameters.

Varmax326

Cause: Same sensor Input BX/mixing valve group.

Action: Check parameters.

Varmax327

Cause: Same function mixing valve group.

Action: Check parameters.

Varmax328

Cause: Same function mixing valve group.

Action: Check parameters.

Varmax329

Cause: Same funct ext module/mixing valve group.

Action: Check parameters.

Varmax330

Cause: Sensor input BX1 no function.

Action: Sensor not Parameterised.

Varmax331

Cause: Sensor input BX2 no function.

Action: Sensor not Parameterised.

Varmax332

Cause: Sensor input BX3 no function.

Action: Sensor not Parameterised.

Varmax333

Cause: Sensor input BX4 no function.

Action: Sensor not Parameterised.

Varmax335

Cause: Sensor input BX21 no function.

Action: Sensor not Parameterised.

Varmax336

Cause: Sensor input BX22 no function.

Action: Sensor not Parameterised.

Varmax337

Cause: Sensor input B1 no function.

Action: Sensor not Parameterised.

Varmax338

Cause: Sensor input B12 no function.

Action: Sensor not Parameterised.

Varmax353

Cause: Cascade flow sensor B10 missing.

Action: Sensor not Parameterised.

Varmax372

Cause: Limit thermostat HC3.

Action: Allow the boiler to cool and reset thermostat

Varmax385

Cause: Mains undervoltage.

Action: Check incoming voltage.

Varmax386

Cause: Fan speed tolerance.

Action: Check fan connection

Varmax387

Cause: Air pressure tolerance.

Action: Check air pressure switch

Varmax388

Cause: DHW sensor no function.

Action: Sensor not parameterised .

Varmax429

Cause: Dyn water pressure too high.

Action: Check water pressure.

Varmax430

Cause: Dyn water pressure too low.

Action: Check water pressure.

Varmax432

Cause: Function ground missing.

Action: Check earth connection.

Varmax433

Cause: Heat exchanger temperature.

Action: Allow the boiler to cool and reset thermostat

Fleet Horizontal10

Cause: Fault outside sensor.

Action: Check connection, check sensor, check cable.

Fleet Horizontal28

Cause: Fault flue gas sensor.

Action: Check connection, check sensor, check cable.

Fleet Horizontal32

Cause: Fault flow temperature sensor 2.

Action: Check connection, check sensor, check cable.

Fleet Horizontal50

Cause: Fault DHW temperature sensor 1.

Action: Check connection, check sensor, check cable.

Fleet Horizontal52

Cause: Fault DHW temperature sensor 2.

Action: Check connection, check sensor, check cable.

Fleet Horizontal61

Cause: Fault room unit 1.

Action: Check room device.

Fleet Horizontal62

Cause: Wrong room unit 1 or wrong radio clock connected.

Action: Connect compatible room control unit.

Fleet Horizontal77

Cause: Fault air pressure sensor.

Action: Check connection, check sensor, check cable.

Fleet Horizontal78

Cause: Fault water pressure sensor.

Action: Check connection, check sensor, check cable.

Fleet Horizontal82

Cause: Address collision on LPB.

Action: Check addresses of connected modules.

Fleet Horizontal91

Cause: Data overflow in EEPROM.

Action: Hardware fault, LMU may need replacing.

Fleet Horizontal92

Cause: Hardware fault in electronics.

Action: Hardware fault, LMU may need replacing.

Fleet Horizontal95

Cause: Invalid time of day.

Action: Set correct time.

Fleet Horizontal100

Cause: 2 clock time masters.

Action: Check settings of LMU, only 1 master allowed.

Fleet Horizontal105

Cause: Maintenance message.

Action: P629 to reset : change from 0 to 1.

Fleet Horizontal110

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Fleet Horizontal111

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Fleet Horizontal113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Fleet Horizontal117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor

Fleet Horizontal118

Cause: Water pressure too low.

Action: Check system pressure, check water pressure sensor

Fleet Horizontal119

Cause: Water pressure switch has cut out.

Action: Check water pressure.

Fleet Horizontal128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Fleet Horizontal129

Cause: Fan speed maximum/minimum has been violated.

Action: Check fan.

Fleet Horizontal130

Cause: Flue gas limit temperature exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Fleet Horizontal132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Fleet Horizontal133

Cause: No flame on completion of safety time.

Action: Check operation of gas valve. Check spark igniter.

Fleet Horizontal134

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Fleet Horizontal140

Cause: Inadmissible LPB segment number/device N°.

Action: Check settings of LMU and boiler address settings.

Fleet Horizontal148

Cause: Incompatibility LPB... interface / basic unit.

Action: Check settings of LMU

Fleet Horizontal151

Cause: Internal fault with LMU.

Action: Check connections to clip in, replace module, check LMU.

Fleet Horizontal152

Cause: Fault in connection with LMU settings.

Action: Check LMU settings.

Fleet Horizontal153

Cause: LMU has locked out.

Action: Press reset button (code appears if reset button is pressed when there are no faults).

Fleet Horizontal154

Cause: Flow Problems.

Action: Check water flow through the boiler & check the pumps.

Fleet Horizontal160

Cause: Fan speed threshold not reached.

Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris.

Fleet Horizontal161

Cause: Maximum fan speed exceeded.

Action: Check parameters.

Fleet Horizontal162

Cause: Fault air pressure switch (does not close).

Action: Check air pressure switch and cable and connections.

Fleet Horizontal164

Cause: Fault heating circuit flow switch / pressure switch.

Action: Check air pressure switch and cable and connections.

Fleet Horizontal166

Cause: Fault air pressure switch (does not open).

Action: Check air pressure switch and cable and connections.

Fleet Horizontal180

Cause: Chimney sweep function active.

Action: Check boiler operation setting.

Fleet Horizontal181

Cause: Controller stop function active.

Action: Check boiler operation setting.

Fleet Horizontal183

Cause: LMU in parameter setting mode.

Action: Unit in programme mode.

Fleet Vertical10

Cause: Fault outside sensor.

Action: Check connection, check sensor, check cable.

Fleet Vertical28

Cause: Fault flue gas sensor.

Action: Check connection, check sensor, check cable.

Fleet Vertical32

Cause: Fault flow temperature sensor 2.

Action: Check connection, check sensor, check cable.

Fleet Vertical50

Cause: Fault DHW temperature sensor 1.

Action: Check connection, check sensor, check cable.

Fleet Vertical52

Cause: Fault DHW temperature sensor 2.

Action: Check connection, check sensor, check cable.

Fleet Vertical61

Cause: Fault room unit 1.

Action: Check room device.

Fleet Vertical62

Cause: Wrong room unit 1 or wrong radio clock connected.

Action: Connect compatible room control unit.

Fleet Vertical77

Cause: Fault air pressure sensor.

Action: Check connection, check sensor, check cable.

Fleet Vertical78

Cause: Fault water pressure sensor.

Action: Check connection, check sensor, check cable.

Fleet Vertical82

Cause: Address collision on LPB.

Action: Check addresses of connected modules.

Fleet Vertical91

Cause: Data overflow in EEPROM.

Action: Hardware fault, LMU may need replacing.

Fleet Vertical92

Cause: Hardware fault in electronics.

Action: Hardware fault, LMU may need replacing.

Fleet Vertical95

Cause: Invalid time of day.

Action: Set correct time.

Fleet Vertical100

Cause: 2 clock time masters.

Action: Check settings of LMU, only 1 master allowed.

Fleet Vertical105

Cause: Maintenance message.

Action: P629 to reset : change from 0 to 1.

Fleet Vertical110

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Fleet Vertical111

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Fleet Vertical113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Fleet Vertical117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor

Fleet Vertical118

Cause: Water pressure too low.

Action: Check system pressure, check water pressure sensor

Fleet Vertical119

Cause: Water pressure switch has cut out.

Action: Check water pressure.

Fleet Vertical128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Fleet Vertical129

Cause: Fan speed maximum/minimum has been violated.

Action: Check fan.

Fleet Vertical130

Cause: Flue gas limit temperature exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Fleet Vertical132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Fleet Vertical133

Cause: No flame on completion of safety time.

Action: Check operation of gas valve. Check spark igniter.

Fleet Vertical134

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Fleet Vertical140

Cause: Inadmissible LPB segment number/device N°.

Action: Check settings of LMU and boiler address settings.

Fleet Vertical148

Cause: Incompatibility LPB... interface / basic unit.

Action: Check settings of LMU

Fleet Vertical151

Cause: Internal fault with LMU.

Action: Check connections to clip in, replace module, check LMU.

Fleet Vertical152

Cause: Fault in connection with LMU settings.

Action: Check LMU settings.

Fleet Vertical153

Cause: LMU has locked out.

Action: Press reset button (code appears if reset button is pressed when there are no faults).

Fleet Vertical154

Cause: Flow Problems.

Action: Check water flow through the boiler & check the pumps.

Fleet Vertical160

Cause: Fan speed threshold not reached.

Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris.

Fleet Vertical161

Cause: Maximum fan speed exceeded.

Action: Check parameters.

Fleet Vertical162

Cause: Fault air pressure switch (does not close).

Action: Check air pressure switch and cable and connections.

Fleet Vertical164

Cause: Fault heating circuit flow switch / pressure switch.

Action: Check air pressure switch and cable and connections.

Fleet Vertical166

Cause: Fault air pressure switch (does not open).

Action: Check air pressure switch and cable and connections.

Fleet Vertical180

Cause: Chimney sweep function active.

Action: Check boiler operation setting.

Fleet Vertical181

Cause: Controller stop function active.

Action: Check boiler operation setting.

Fleet Vertical183

Cause: LMU in parameter setting mode.

Action: Unit in programme mode.

Fleet Wall Hung10

Cause: Fault outside sensor.

Action: Check connection, check sensor, check cable.

Fleet Wall Hung28

Cause: Fault flue gas sensor.

Action: Check connection, check sensor, check cable.

Fleet Wall Hung32

Cause: Fault flow temperature sensor 2.

Action: Check connection, check sensor, check cable.

Fleet Wall Hung50

Cause: Fault DHW temperature sensor 1.

Action: Check connection, check sensor, check cable.

Fleet Wall Hung52

Cause: Fault DHW temperature sensor 2.

Action: Check connection, check sensor, check cable.

Fleet Wall Hung61

Cause: Fault room unit 1.

Action: Check room device.

Fleet Wall Hung62

Cause: Wrong room unit 1 or wrong radio clock connected.

Action: Connect compatible room control unit.

Fleet Wall Hung77

Cause: Fault air pressure sensor.

Action: Check connection, check sensor, check cable.

Fleet Wall Hung78

Cause: Fault water pressure sensor.

Action: Check connection, check sensor, check cable.

Fleet Wall Hung82

Cause: Address collision on LPB.

Action: Check addresses of connected modules.

Fleet Wall Hung91

Cause: Data overflow in EEPROM.

Action: Hardware fault, LMU may need replacing.

Fleet Wall Hung92

Cause: Hardware fault in electronics.

Action: Hardware fault, LMU may need replacing.

Fleet Wall Hung95

Cause: Invalid time of day.

Action: Set correct time.

Fleet Wall Hung100

Cause: 2 clock time masters.

Action: Check settings of LMU, only 1 master allowed.

Fleet Wall Hung105

Cause: Maintenance message.

Action: P629 to reset : change from 0 to 1.

Fleet Wall Hung110

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Fleet Wall Hung111

Cause: Limit thermostat has cut out.

Action: Allow the boiler to cool and reset thermostat, investigate cause of overheating.

Fleet Wall Hung113

Cause: Flue gas supervision equipment has cut out.

Action: Check the cause of high flue gas temperature. Check sensor.

Fleet Wall Hung117

Cause: Water pressure too high.

Action: Check system pressure, check water pressure sensor

Fleet Wall Hung118

Cause: Water pressure too low.

Action: Check system pressure, check water pressure sensor

Fleet Wall Hung119

Cause: Water pressure switch has cut out.

Action: Check water pressure.

Fleet Wall Hung128

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Fleet Wall Hung129

Cause: Fan speed maximum/minimum has been violated.

Action: Check fan.

Fleet Wall Hung130

Cause: Flue gas limit temperature exceeded.

Action: Check the cause of high flue gas temperature. Check sensor.

Fleet Wall Hung132

Cause: Safety shutdown.

Action: Check gas pressure. Check flue & condensate trap for blockages. Check safety switches.

Fleet Wall Hung133

Cause: No flame on completion of safety time.

Action: Check operation of gas valve. Check spark igniter.

Fleet Wall Hung134

Cause: Loss of flame during operation.

Action: Check connections to flame probe. Investigate flame probe condition. Check combustion when boiler is firing.

Fleet Wall Hung140

Cause: Inadmissible LPB segment number/device N°.

Action: Check settings of LMU and boiler address settings.

Fleet Wall Hung148

Cause: Incompatibility LPB... interface / basic unit.

Action: Check settings of LMU

Fleet Wall Hung151

Cause: Internal fault with LMU.

Action: Check connections to clip in, replace module, check LMU.

Fleet Wall Hung152

Cause: Fault in connection with LMU settings.

Action: Check LMU settings.

Fleet Wall Hung153

Cause: LMU has locked out.

Action: Press reset button (code appears if reset button is pressed when there are no faults).

Fleet Wall Hung154

Cause: Flow Problems.

Action: Check water flow through the boiler & check the pumps.

Fleet Wall Hung160

Cause: Fan speed threshold not reached.

Action: Check obstructions in fan, burner & flue. Check non-return valve operates. Check heat exchanger for debris.

Fleet Wall Hung161

Cause: Maximum fan speed exceeded.

Action: Check parameters.

Fleet Wall Hung162

Cause: Fault air pressure switch (does not close).

Action: Check air pressure switch and cable and connections.

Fleet Wall Hung164

Cause: Fault heating circuit flow switch / pressure switch.

Action: Check air pressure switch and cable and connections.

Fleet Wall Hung166

Cause: Fault air pressure switch (does not open).

Action: Check air pressure switch and cable and connections.

Fleet Wall Hung180

Cause: Chimney sweep function active.

Action: Check boiler operation setting.

Fleet Wall Hung181

Cause: Controller stop function active.

Action: Check boiler operation setting.

Fleet Wall Hung183

Cause: LMU in parameter setting mode.

Action: Unit in programme mode.

Dorchester DR-FC EvoS01

Cause: Sensor is not (correctly) connected.

Action: Connect the sensor lead to JP3.

Cause: Damaged cable and/or defective sensor.

Action: Replace the cable and/or sensor.

(blocking error) Open circuit from temperature sensor T2 at the bottom of the tank.
Dorchester DR-FC EvoS02

Cause: Sensor is not (correctly) connected.

Action: Connect the sensor lead to JP5.

Cause: Damaged cable and/or defective sensor.

Action: Damaged cable and/or defective sensor.

(blocking error) Open circuit from sensor 1 of temperature sensor T1 at the top of tank(1).
Dorchester DR-FC EvoS03

Cause: Sensor is not (correctly) connected.

Action: Connect the sensor lead to JP5.

Cause: Damaged cable and/or defective sensor.

Action: Replace the cable and/or sensor.

(blocking error) Open circuit in sensor 2 of temperature sensor T1 at the top of the tank (1).
Dorchester DR-FC EvoS04

Cause: Dummy is not (correctly) connected.

Action: Connect the dummy sensor (dummy sensor 1 and 2) leads to JP4.

Cause: Defective dummy.

Action: Replace the dummy sensor.

(blocking error) Open circuit from dummy1.
Dorchester DR-FC EvoS05

Cause: Dummy is not (correctly) connected.

Action: Connect the dummy sensor (dummy sensor 1 and 2) leads to JP4.

Cause: Defective dummy.

Action: Replace the dummy sensor.

(blocking error) Open circuit from dummy 2.
Dorchester DR-FC EvoS11

Cause: Short circuit in sensor circuit.

Action: Replace the cable and/or sensor.

(blocking error) Short circuit in temperature sensor T2 at the bottom of the tank.
Dorchester DR-FC EvoS12

Cause: Short circuit in sensor circuit.

Action: Replace the cable and/or sensor.

(blocking error) Short circuit in sensor 1 of temperature sensor T1 at top of tank.
Dorchester DR-FC EvoS13

Cause: Short circuit in sensor circuit.

Action: Replace the cable and/or sensor.

(blocking error) Short circuit in sensor 2 of temperature sensor T1 at the top of the tank.
Dorchester DR-FC EvoS14

Cause: Short circuit in sensor circuit.

Action: Replace the dummy sensor.

(blocking error) Short circuit from dummy1.
Dorchester DR-FC EvoS15

Cause: Short circuit in sensor circuit.

Action: Replace the dummy sensor.

(blocking error) Short circuit from dummy2.
Dorchester DR-FC EvoF01

Cause: Live and neutral connected wrong way around.

Action: Be sure to connect the live and neutral correctly (3.10 Electrical connection in the installation manual). The water heater is phase-sensitive.

Cause: Condensation on the flame probe.

Action: 1. Disconnect the lead at the flame probe. 2. Ignite the water heater three times. 3. Reconnect the ionisation lead to the flame probe. 4. Ignite the water heater again. 5. The repeated ignition attempts will have caused the condensation to evaporate.

Cause: Floating neutral.

Action: Install an isolating transformer.

(blocking error) Defect in power supply circuit.
Dorchester DR-FC EvoF02

Cause: Because of a drop in the supply voltage the fan will not run at the correct speed.

Action: 1. Check the supply voltage this must be 230VAC (-15% +10%) 2. Reset controller

(lock out error) Fan fails to run at correct speed.
Dorchester DR-FC EvoF03

Cause: Damaged wiring/Open circuit.

Action: 1. Check the wiring between the pressure switch and the controller. 2. If necessary replace the wiring

(lock out error) The pressure switch fails to work correctly.
Dorchester DR-FC EvoF04

Cause: No gas.

Action: 1. Open the main gas supply valve and/or the manual gas supply valve before the gas control valve. 2. Check supply pressure to the gas control valve. 3. If necessary

Cause: Air in the gas pipes.

Action: Bleed the air out of the gas pipe.

Cause: Defect in the hot surface igniter circuit.

Action: 1. Check that the hot surface igniter is correctly connected (JP2). 2. Check the wiring of the hot surface igniter. 3. Measure the resistance across the hot surface igniter. This must lie between 2 and 10 Ohm (at room temperature). 4. Check that the hot surface igniter lights up during ignition. 5. If necessary replace the hot surface igniter.

Cause: Defect in the ionisation circuit.

Action: 1. Check that the flame probe is correctly connected (JP2). 2. Check the wiring of the flame probe. 3. Measure the ionisation current. This must be a minimum of 1.5microA. 4. If necessary replace the wiring.

Cause: Supply voltage too low.

Action: Check the supply voltage

(lock out error) Three unsuccessful ignition attempts.
Dorchester DR-FC EvoF05

Cause: Incorrect roof or wall flue terminal. Recirculating flue gases.

Action: 1. Check that the correct roof or wall flue terminal has been installed. 2. If necessary install the correct roof or wall flue terminal. 3. Check that the roof or wall flue terminal discharges into a permitted area.

(lock out error) Too many flame errors have been signalled.
Dorchester DR-FC EvoF06

Cause: Damaged cable in contact with metal surface or bent flame probe.

Action: Check the wiring and the flame probe. Replace the wiring and/or flame probe if necessary.

Cause: Ceramic part of the flame probe is broken/cracked.

Action: 1. Check whether the ceramic part of the flame probe is still intact. 2. If not the flame probe must be replaced.

(blocking error) Short circuit between flame probe and earth.
Dorchester DR-FC EvoF07

Cause: Defective gas control valves.

Action: 1. Check whether there is still burner pressure present after the gas control valves have closed. 2. Check whether a flame is still present after the gas control valves have closed. 3. If this is the case the gas control valve must be replaced.

(lock out error) A flame has been detected after the gas control valve was closed.
Dorchester DR-FC EvoF08

Cause: Flame detection before the gas control valve opened.

Action: 1. Reset controller. 2. If the error appears again

(lock out error) Error message from safety relay.
Dorchester DR-FC EvoF09

Cause: Temperature at the top of the tank exceeds 93°C.

Action: 1. Check that the circulation pump (if present) is working. 2. Check the position of temperature sensor T1. 3. Reset controller.

(lock out error) Water temperature protection.
Dorchester DR-FC EvoF11

Cause: Defective gas control valves.

Action: 1. Check whether there is still burner pressure present after the gas control valves have closed.. 2. Check whether a flame is still present after the gas control valves have closed.. 3. If this is the case the gas control valve must be replaced.

(blocking error) Flame detection with closed gas control valve.
Dorchester DR-FC EvoF19

Cause: There is not enough supply voltage.

Action: 1. Check that there is power to the controller.

Cause: There is not enough supply voltage.

Action: 2. The measured voltage must be 230 VAC (-15% +10%).

(blocking error) Power supply voltage is too low.
Dorchester DR-FC EvoC02

Cause: Incorrect reference voltage from the AD converter.

Action: 1. Reset controller. 2. Check that the frequency of the power supply is compliant (3.4.2 "General and electrical specifications" in installation manual). If not contact your installation engineer. 3. If the frequency is correct but the error persists replace the controller.

(lock out error) Error message from the controller.
Dorchester DR-FC EvoC03

Cause: Too many resets in too short a period.

Action: Wait for the error to disappear (maximum 1 hour). If the error does not disappear replace the water heater controller.

(blocking error) Reset error.
Dorchester DR-FC EvoC04

Cause: Incorrect water heater selection/Incorrect selection resistor.

Action: 1. Check whether the correct water heater is selected (12.5"Display the selected water heater" in installation manual). 2. If the correct water heater is selected fit the correct selection resistor. 3. If incorrect water heater selected select the correct one.

(blocking error) Appliance selection error.
Dorchester DR-FC EvoE01

Cause: The temperature of the water at the top of the tank is >85°C.

Action: None. This is a temporary message that may appear from time to time but will disappear automatically.

(blocking error) The temperature protection at the top of the tank has been activated.
Dorchester DR-FC EvoE03

Cause: The two temperature sensors in the tank detect a difference of >10°C over a period of at least 60 seconds.

Action: 1. Check sensor position and wiring. 2. Reset the controller if necessary. Replace the sensor if the error persists.

(lock-out error) Error in temperature sensor T1 at the top of the tank.
Dorchester DR-FC EvoE04

Cause: The two temperature sensors detect a difference of >10°C over a period of at least 60 seconds.

Action: 1. Check the wiring of the dummy1 and dummy2. 2. Reset the controller if necessary. Replace the dummy sensor if the error persists.

(lock-out error) Defect in the dummy sensor(2).