Halstock stainless steel calorifier
- Stainless steel single coil and twin coil calorifiers for indirect hot water.
- 5 unvented calorifier models and 4 open-vented calorifiers available with continuous outputs (@44°C ∆T) of 390, 527, 1,843 and 2,106 l/h.
Product information
Power outputs 20-108kW and storage capacities 305-965 litres
Indirect method of producing safe and hygienic domestic hot water (want to understand the difference between Indirect vs Direct Hot Water Systems?)
Fast recovery for constant hot water – as little as 13 minutes (Recovery times for 70% of the cylinder volume to 50°C 13-22 minutes)
Hot water cylinder and coil made out of corrosion resistant stainless steel for a long life backed up by a 5 year cylinder warranty
Now available with twin coils for flexibility and high performance hot water (models 500-965 only)
Can be integrated with solar thermal for a renewable energy option
Minimal heat loss for maximum economy thanks to layer of CFC-free polyurethane tank insulation under protective plastisol cladding
Highly efficient heat transfer from a corrugated coil design
Low maintenance as no sacrificial anodes or powered corrosion protection systems needed
Can be located wherever convenient
Versatility in use – coupled to Hamworthy commercial boilers or backup via immersion heater
UK manufactured hot water calorifiers
Compliant with Energy Labelling requirements of ErP
Available for next day delivery (dependent on stock availability, charges apply, order cut-off 12pm).
Ideal uses/applications
To provide domestic hot water for any type of commercial building.
Designed for use with natural gas, LPG or oil-fired commercial boilers for primary heat source.
Direct heating via optional Incoloy 800 electrical immersion heaters.
Suited to all areas of the UK, particularly locations with soft water (read here why).
Optional extras
Electric immersion heater kits
Top-to-bottom re-circulation/de-stratification kit to prevent stratification and protect against legionella within the water heater (factory fitted – please specify at time of ordering)
Choose from a wide range of service contracts to help maintain optimum performance.
- Water
Units
HS305
HS400
HS5002CO
HS8102CO
HS9652CO
Capacity, nominal
litres
305
400
500
810
965
Capacity with coil
litres
298
396
496
803
958
Continuous output @44°C ΔT
l/h
390
527
1843
1843
2106
Continuous output @50°C ΔT
l/h
344
464
1622
1622
1853
Maximum working pressure, tank
bar
6
6
6
6
6
Hydraulic test pressure
bar
9
9
9
9
9
- Energy
Units
HS305
HS400
HS5002CO
HS8102CO
HS9652CO
Number of coils
1
1
2
2
2
Lower coil output
kW
20
27
67.5
67.5
81
Heat up time @50°C ΔT,lower coil only
min
54
53
26
42
42
Upper coil output
kW
N/A
N/A
27
27
27
Heat up time @50°C ΔT,top coil only
min
N/A
N/A
66
105
126
Heat up time @50°C ΔT,combined coils
min
N/A
N/A
19
31
31
Recovery time 70% @50°C ΔT, combined coils
min
38
36
13
21
22
10 min peak output @50°C ΔT
litres
361
481
770
1080
1274
Coil max operating temperature
°C
100
100
100
100
100
Coil max operating pressure
bar
3
3
3
3
3
Upper coil tube diameter
DN
NA
NA
DN25
DN25
DN25
Upper coil surface area
m2
NA
NA
1
1
1
Lower coil tube diameter
DN
DN20
DN25
DN25
DN25
DN25
Lower coil surface area
m2
0.75
1
2.5
2.5
3
Reheat total delta T 50degC lower
mins
38
36
18
29
29
Reheat total delta T 50degC both
mins
N/A
N/A
13
21
22
Standby losses
kW/24hr
1.77
2.35
2.74
3.29
3.43
ErP efficiency rating
-
C
C
C
Compliant
Compliant
- Immersion
Units
HS305
HS400
HS5002CO
HS8102CO
HS9652CO
Immersion heater option, power
kW
3
6
6
9
12
Immersion heater option, phase
ph
1ph
3ph/1ph
3ph/1ph
3ph
3ph
Heat up time, Immersion only
hour
5.8
3.9
4.9
5.3
4.7
Recovery time, Immersion only
hour
4.1
2.7
3.4
3.7
3.3
- Misc
Units
HS305
HS400
HS5002CO
HS8102CO
HS9652CO
Expansion vessel size
litres
24
35
35
50
80
Weight empty
kg
75
105
115
140
180
Weight full
kg
379
505
615
950
1145