Purewell Variheat mk2 condensing cast iron boiler
- Available in 5 condensing models with outputs (@50/30°C) of 70, 95, 110, 140 and 180 kW.
- The only cast iron condensing commercial boiler that is compliant with the Energy related Products Directive (ErP) available in the UK.
Product information
Proven reliability with a 10-year heat exchanger warranty
The only cast iron condensing commercial boiler that is compliant with the Energy related Products Directive (ErP) available in the UK.
Built in boiler sequence controls capable of controlling up to 16 boiler modules and hot water circuits
Easy access for servicing with quick to remove front cover hooks
Full spark ignitor enables servicing without the need to remove the whole burner
Low NOx performance (<40mg/kWh, European Class 6)
Non complicated design means the Purewell Variheat mk2 is easy to operate & maintain, saving on time and money
Highly efficient offering up to 96% gross seasonal efficiency, reducing carbon emissions and saving the end user money on fuel bills
Sits on same footprint as many traditional and atmospheric cast iron boilers reducing space concerns
Easy access to plant room as the Purewell Variheat mk2 fits through a standard doorway
Can be disassembled for plant rooms with difficult access
Tolerant of existing heating systems making the Purewell Variheat mk2 the perfect choice when replacing old atmospheric boilers
Operates in sealed and open vented heating systems (you can read about the differences of Sealed 'v' Open Vented heating systems here)
Suitable for use with LPG Air for installation in the Channel Islands
BIM objects available to assist in design and management
Ideal uses/applications
Easy fit replacement for refurbishment projects.
Medium sized commercial and public buildings including schools, care homes, hotels, churches and retail units.
Smaller commercial and public buildings including community schools, care homes, hotels, churches and retail units.
Locations with substantial and continuous heating load including hospitals, care homes and hotels.
Ideal replacement for atmospheric boilers.
Optional extras
Reverse return header kit available for:
2 boiler installation
3 boiler installation
4 boiler installation ( 2 x 2 boiler installation kit)
Flues available
Choose from a wide range of service contracts to help maintain optimum performance.
Book commissioning at the same time as placing your order for improved warranty terms.
- Energy
Units
PV70c
PV95c
PV110c
PV140c
PV180c
Building regulations - seasonal efficiency
(%) gross
95.3
95.6
95.8
95.7
94.6
ErP efficiency rating (modules ≤ 70 kW only)
A
N/A
N/A
N/A
N/A
Boiler output (non-condensing) mean 70°C - max
kW
63.5
86.3
99.8
134.4
172.8
Boiler output (non-condensing) mean 70°C - min
kW
21.2
28.8
33.3
44.8
50.3
Boiler output (condensing) mean 40°C - max
kW
70
95
110
140
180
Boiler output (condensing) mean 40°C - min
kW
23.3
31.67
36.37
46.67
53.0
Gross boiler input - max
kW
72.2
98.4
115
151.3
194.6
Gross boiler input - min
kW
24.1
26.7
38.3
50.4
56.6
Net boiler input - max
kW
65
88.6
103.5
136.3
175.2
Net boiler input - min
kW
21.7
29.6
34.5
45.4
51.0
- Water
Units
PV70c
PV95c
PV110c
PV140c
PV180c
Water content
litres
8
8
8
11
11
System design flow rate @ 20°C ∆T rise
l/s
0.8
1.1
1.3
1.7
2.1
Water side pressure loss @ 20°C ∆T rise
mbar
32
52
72
134
221
System design flow rate @ 11°C ∆T rise
l/s
1.5
2.1
2.4
3
3.9
Water side pressure loss @ 11°C ∆T rise
mbar
96
176
244
442
731
Maximum water pressure
bar g
6
6
6
6
6
- Gas
Units
PV70c
PV95c
PV110c
PV140c
PV180c
Gas flow rate natural gas (G20) - max
m3/hr
6.9
9.4
10.9
14.4
18.5
Nominal inlet pressure natural gas (G20) - max
mbar
20
20
20
20
20
Maximum gas inlet pressure natural gas (G20)
mbar
25
25
25
25
25
- Flue
Units
PV70c
PV95c
PV110c
PV140c
PV180c
Flue Gas Flow Rate@ 15°C, 9.5% CO2
m3/hr
86
117
137
180
232
Approx. flue gas temperature @ 50/30°C
°C
40
40
45
50
50
Approx. flue gas temperature @ 80/60°C
°C
60
60
65
70
75
Pressure at boiler flue spigot @full load
Pa
100
100
100
100
100
Dry NOx emission*
mg/kWh
21.3
31.1
39.1
32
37.8
- Connection
Units
PV70c
PV95c
PV110c
PV140c
PV180c
Water flow/return connections
inches
R2”
R2”
R2”
R2”
R2”
Gas inlet connection pipe thread size
inches
R1”
R1”
R1”
R1”
R1”
Nominal flue diameter (I/D)
mm
150
150
150
150
150
- Electrics
Units
PV70c
PV95c
PV110c
PV140c
PV180c
Electrical supply
230 V 1 Ph 50 Hz
230 V 1 Ph 50 Hz
230 V 1 Ph 50 Hz
230 V 1 Ph 50 Hz
230 V 1 Ph 50 Hz
Power consumption @ max
W
94
94
94
207
207
IEC power outlet power consumption @ max
W
460
460
460
460
460
Start current and run current
Amp
0.54
0.54
0.54
0.6
0.6
Approx shipping weight
kg
195
195
195
250
250
Noise emission @1 m and @maximum boiler modulation
Max dB (A)
53
53
53
65
65
CO2 (±0.25%) - max
%
9.5
9.5
9.5
9.5
9.5
CO2 (±0.25%) - min
%
9.5
9.5
9.5
8.5
8.5
*0% excess oxygen, dry air free, European Class 6
Brochures
Hydraulic Schematics
Installation And Servicing
- CAD
sb08605-a-variheat-mk2-boiler-dwg-pv70
sb08605-a-variheat-mk2-boiler-dwg-pv110
variheat-water-2-blr-70c-p
sb08605-a-variheat-mk2-boiler-dwg-pv95
sb08204-a-variheat-mk2-2d-layout-2-boilers
sb08204-a-variheat-mk2-2d-layout-3-boilers
variheat-water-2-blr-70c-r
variheat-water-3-blr-95c-r
variheat-water-2-blr-110c-f
variheat-water-2-blr-140c-p
variheat-water-3-blr-70c-f
variheat-water-2-blr-110c-p
variheat-water-3-blr-140c-r