Dorchester DR-FC Evo condensing water heater
- Fully automatic, condensing direct fired water heater for domestic hot water.
- 7 models available with continuous outputs (@44°C ∆T) of 600, 630, 970, 1200, 1700, 2000 & 2400 l/h.
Product information
Power outputs 30-119kW and storage capacities of 227-504 litres.
Safe and clean domestic hot water generation.
Reduces energy use and running costs by maximising condensing water heater performance.
Meets the strict standards for efficiencies and NOx emissions in new buildings.
Ultra-quiet operation means it can be installed close to point of use without disturbance to occupants.
Closely matches hot water demand, reducing wastage.
Down firing pre-mix modulating burner reduces the risk of scale build up impacting on the heat transfer.
Large range of time and temperature control features built in as standard.
Electronic Anode fitted as standard.
Natural gas and lpg water heater options.
Easy access for service and maintenance.
Full project assistance available from our dedicated hot water expert to help with hot water sizing and selection of equipment to match the application.
Extensive back up and support from our team of experienced engineers across the UK.
Long term commitment to spare parts.
Water heater BIM objects available to assist in project design and management
Available for next day delivery (dependent on stock availability, charges apply, order cut-off 12pm).
Ideal uses/applications
New build projects.
Large commercial and public buildings including schools, hospitals and hotels.
Locations with substantial and continuous hot water demands including hospitals, hotels and sports facilities.
To see where Dorchester condensing water heaters have been used, visit the case study section of our website.
Optional extras
Unvented water supply kit - essential for any unvented application and includes an expansion vessel sized for the water heater and local pipework only.
Top to bottom pump recirculation pump kit to prevent stratification and protect against legionella within the water heater.
Remote monitoring unit.
Room Sealed Flue Systems:
Concentric flue systems type C13–Horizontal termination.
Concentric flue systems type C33–Vertical termination.
Twin duct flue systems type C53–Vertical flue termination with Horizontal air inlet.
Conventional Open Flue Systems:
Open flue systems type B23–Vertical termination.
Choose from a wide range of service contracts to help maintain optimum performance.
Ensure your new Hamworthy products are set to our recommendations and benefit from improved warranty terms with a commissioning package.
- Energy
Units
DR-FC Evo 25
DR-FC Evo 30
DR-FC Evo 45
DR-FC Evo 60
DR-FC Evo 80
DR-FC Evo 95
DR-FC Evo 120
Building Regulations thermal efficiency gross
%
96
98
96
95
97
95
95
ErP efficiency rating (modules ≤ 70 kW only)
-
A
A
A
A
N/A
N/A
N/A
Heating-up time, ΔT = 44°C
min.
23
37
24
20
19
16
13
Heating-up time, ΔT = 50°C
min.
26
42
27
23
21
18
15
Heating-up time, ΔT = 55°C
min.
29
46
30
25
23
20
16
Standby losses
kW/24h
4.2
4.7
4.7
4.7
6.7
6.7
6.7
- Water
Units
DR-FC Evo 25
DR-FC Evo 30
DR-FC Evo 45
DR-FC Evo 60
DR-FC Evo 80
DR-FC Evo 95
DR-FC Evo 120
Continuous output with 44°C ΔT
l/h
600
630
790
1200
1700
2000
2400
1st hour output with 44°C ΔT
l
730
870
1300
1500
1900
2200
2600
Continuous output with 50°C ΔT
l/h
530
560
850
1100
1500
1700
2100
1st hour output with 50°C ΔT
l
630
730
1100
1300
1700
1900
2300
Continuous output with 55°C ΔT
l/h
480
510
780
930
1300
1600
1900
1st hour output with 55°C ΔT
l
560
640
930
1100
1500
1700
2000
Storage capacity
litres
227
386
386
386
504
504
504
Maximum operating water pressure (open vented)
bar
8
8
8
8
8
8
8
Maximum operating water pressure (unvented)
bar
5.3
5.3
5.3
5.3
5.3
5.3
5.3
Expansion relief valve setting (unvented kit)
bar
6
6
6
6
6
6
6
ErP load profile
-
XXL
XXL
XXL
XXL
3XL
3XL
3XL
- Nat Gas
Units
DR-FC Evo 25
DR-FC Evo 30
DR-FC Evo 45
DR-FC Evo 60
DR-FC Evo 80
DR-FC Evo 95
DR-FC Evo 120
Input, gross – maximum
kW
31.6
32.6
51.2
62.1
85
103.4
126.3
Output – maximum
kW
30.5
32
49.3
59.3
82.6
98.7
119.4
Gas inlet pressure – nominal
mbar
20
20
20
20
20
20
20
Gas flow rate – maximum @1013.25 mbar and 15°C
m3/h
3.1
3.2
5
6
8.3
10.1
12.3
- LPG
Units
DR-FC Evo 25
DR-FC Evo 30
DR-FC Evo 45
DR-FC Evo 60
DR-FC Evo 80
DR-FC Evo 95
DR-FC Evo 120
Input, gross – maximum
kW
31
32
50.1
60.8
83.2
101.2
123.6
Output – maximum
kW
30.5
32
49.3
59.3
82.6
98.7
119.4
Gas inlet pressure – nominal
mbar
37
37
37
37
37
37
37
Gas flow rate – maximum@1013.25 mbar and 15°C
kg/h
2.3
2.3
3.7
4.4
6.1
7.4
9
- Flue
Units
DR-FC Evo 25
DR-FC Evo 30
DR-FC Evo 45
DR-FC Evo 60
DR-FC Evo 80
DR-FC Evo 95
DR-FC Evo 120
Approximate flue gas volume @15°C, 9.8% CO2, N.T.P. (Nat. Gas - G20)
kg/h
51.7
53.5
84.6
103.7
141.9
172.9
213.3
Flue gas temperature – maximum
°C
45
50
60
65
50
55
60
NOx emission, dry air free,European Class 5. Maximum (at part load)
mg/kWh
24
32
36
37
34
36
37
Pressure at the flue outlet only (B23) with zero pressure at air inlet
Pa
52
62
133
173
88
126
180
- Electrical
Units
DR-FC Evo 25
DR-FC Evo 30
DR-FC Evo 45
DR-FC Evo 60
DR-FC Evo 80
DR-FC Evo 95
DR-FC Evo 120
Start current–maximum (maximum power)
A (W)
0.59 (135)
0.59 (135)
0.59 (135)
0.59 (135)
0.61 (140)
0.61 (140)
0.61 (140)
Run current–maximum (maximum power)
A (W)
0.2 (45)
0.2 (45)
0.32 (75)
0.5 (115)
0.41 (95)
0.63 (145)
1.05 (240)
Electrical supply
Vac
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
Voltage tolerance
% of Vac
-15% +10%
-15% +10%
-15% +10%
-15% +10%
-15% +10%
-15% +10%
-15% +10%
- Misc.
Units
DR-FC Evo 25
DR-FC Evo 30
DR-FC Evo 45
DR-FC Evo 60
DR-FC Evo 80
DR-FC Evo 95
DR-FC Evo 120
Noise level @2m from flue terminal
dB(A)
<45
<45
<45
<45
<45
<45
<45
Number of (power) anodes
-
1
2
2
2
2
2
2
Weight when empty
kg
196
239
239
239
405
405
405
Approximate shipping weight
kg
215
260
260
260
426
426
426
Maximum floor load/ weight filled with water
kg
423
625
625
625
909
909
909